MGE UPS Systems EX-5, EX-7, EX-11RT Operation on Battery Power, Transfer to Battery Power

Page 55

Installation and User Manual

3.5Operation on Battery Power

Figure 3-6: Transfer, Threshold and End of backup time.

15 16

REMAINING TIME

10 minutes

OFFON

15 16

REMAINING TIME

2 minutes

OFFON

15 16

OFFON

3.5.1Transfer to Battery Power

The load continues to be protected by the UPS when the Normal AC source is not available. Power is supplied by the battery.

There are three possible cases:

First Case: Operation on battery

15LED is ON.

16LED is ON.

The audio alarm beeps every 10 seconds.

This indicate the load is supplied by the battery.

The LCD display indicates the battery remaining backup time.

Second Case: Low battery warning

15LED is ON.

16LED flashes.

The audio alarm beeps every 3 seconds.

Low battery warning on LCD display. There is very little remaining battery backup time. Close all applications because UPS automatic shutdown is pending.

Third Case: End of backup time

15LED is OFF.

16LED is OFF.

The audio alarm is stopped.

86-86000-00 B00

Operation

3 — 9

Image 55
Contents EX 5/7/11RT Systems Page Technical Support Customer Care Center Hours 24/7 MGE UPS SYSTEMS, INC Scenic Avenue Costa Mesa, CA 92626 714EX 5/7/11RT Systems Contents Setup and Installation Return Policy for Repair of Single Phase Products RGA Technical Support and Product ServicesFigures Tables Certification Standards Important Safety InstructionsEnvironment Special PrecautionsAdditional Modules Serial Numbers Section Descriptions This page left blank intentionally Input voltage must be the same as output voltage on HV units ScopePart Number Description Transformer Module Characteristics Ratings System Electrical CharacteristicsTower Configuration Standard ConfigurationRack Configuration Model Dimensions HxWxD WeightsRear Panel Components Power Module EX 5/7/11 RTEX RT Transformer Module Power Module Display and Control Panel1 1 R T Power Module Rail Kit Optional AccessoriesBattery/Transformer/CLA Module Rail Kit Battery Extension Cable Kit Multiple Battery Module Backup Time at Full LoadInput/Output Box Battery Integration Kit with CastersEX RT Transformer Module Contents EX 5/7/11RT CLA Module ContentsRecommended Batteries All Modules are shipped in separate boxes Unpacking and Parts CheckContents of Standard EX 5/7/11RT Systems Contents of EXB 5/7/11RT Battery Module PN 86207 /86209 Installation in Tower Configuration Installation in Rack Mounting Configuration Not to scale Page Bracket System Install input/output cables Per .7 prior to this stepCommunication Ports Connecting the RS232 Communication PortInstallation of Optional Transverse Card Connecting the Dry Relay Contact Communication PortDual port Shut Card Dual U-Talk/Basic CardJBus Card Proper operationRemote Emergency Power Off Repo Communication Port Max AWG EX 11RT System ConnectionsSources are open OFF/OPEN Output Always connect the earth ground wire firstProtection for all transformer output terminals Connecting EX RT Transformer Module120VAC output terminals Lb-N, La-N Bypass AC Mains Power Module I/O Box Connection of Battery Module EXB Connection of Optional CLA Module AC InputThis page left blank intentionally Required for initial startup only Initial StartupControl Panel with scroll up and down buttons UPS PersonalizationDisplay Factory setting Options Comments Display Factory setting OptionsMGE UPS SYSTEMS, INC Symptoms IT Network mode Industrial mode During the startup, if the Bypass AC source is out Then go to Advanced settings and UPS settingsUPS personalization through external software Final Startup sequenceOperating Modes Normal double conversion ModeECO mode display ECO ModeSecond Case Low battery warning Operation on Battery PowerTransfer to Battery Power First Case Operation on batteryReturn of Normal AC source Power to the loadShutdown Symptoms Indication Correction TroubleshootingBattery Fault LED 1CXXXXXXX Hot Swapping the Power ModuleRe-connecting the Power Module Disconnecting the Battery Module Hot Swapping the Battery ModuleRe-connecting the Battery Module This page left blank intentionally Source Voltage Frequency Electrical SpecificationsSystem Input/Output Power Ratings System Overload CharacteristicsSystem Short Circuit Protection System Backup CharacteristicsEX RT CLA Module KVA / kW 25% 50% 75% 100% Output load percentage Configuration for Hours backup timeSystem Environmental CharacteristicsOperation Mode On-line On Battery Heat RejectionProprietary Rights Statement MGE Standard Single Phrase WarrantyUser Information Warranty Extension Warranty+ not available on productsProduct information Part Number Assembly Number Serial number Scheduling Field Service Engineer SupportEX 5/7/11RT Systems Glossary IEC Osha This page left blank intentionally Reorder Form Scenic Avenue Costa Mesa, CA Contact MGE