MGE UPS Systems EX-5, EX-7, EX-11RT manual Always connect the earth ground wire first, Output

Page 40

EX 5/7/11RT Systems

Proceed as follows:

1.For normal AC input, make connections to L1, L2 and terminals only. No connections are required for Bypass AC input. Make connections to , L5, L6 terminals for output.

CAUTION:

Always connect the earth ground wire first.

 

Jumper must be between L1 and L3. System is factory configured for 208VAC

 

output.

 

 

2.Attach I/O Box to the Power Module with three screws.

Figure 2-12: Normal AC Input and Output Cables installation.

Power Module I/O Box

Output

Bypass AC source

200/208/220/230/240Vac

200/208/220/230/240Vac

Normal AC source

200/208/220/230/240Vac

L6 L5

L2 L1 L1

L4 L3

OFF

O

1

Normal AC Input

Jumper

Output

 

From Utility

208 VAC

To Load 208VAC

2

66074

OFF O

Output to Load or

Transformer Module (if applicable)

Simplified Connection Diagram

UPSTREAM

Bypass AC

 

CIRCUIT

 

BREAKER

 

(NOT SUPPLIED)

 

AC INPUT

Normal AC

To Load or

 

 

Transformer Module

 

 

(if applicable)

2 — 14

Installation

86-86000-00 B00

Image 40
Contents EX 5/7/11RT Systems Page MGE UPS SYSTEMS, INC Scenic Avenue Costa Mesa, CA 92626 714 Technical Support Customer Care Center Hours 24/7EX 5/7/11RT Systems Contents Setup and Installation Technical Support and Product Services Return Policy for Repair of Single Phase Products RGAFigures Tables Important Safety Instructions Certification StandardsSpecial Precautions EnvironmentAdditional Modules Serial Numbers Section Descriptions This page left blank intentionally Scope Input voltage must be the same as output voltage on HV unitsPart Number Description System Electrical Characteristics Transformer Module Characteristics RatingsStandard Configuration Tower ConfigurationModel Dimensions HxWxD Weights Rack ConfigurationPower Module EX 5/7/11 RT Rear Panel ComponentsEX RT Transformer Module Power Module Display and Control Panel1 1 R T Power Module Rail Kit Optional AccessoriesBattery/Transformer/CLA Module Rail Kit Multiple Battery Module Backup Time at Full Load Battery Extension Cable KitBattery Integration Kit with Casters Input/Output BoxEX RT Transformer Module Contents EX 5/7/11RT CLA Module ContentsRecommended Batteries Unpacking and Parts Check All Modules are shipped in separate boxesContents of Standard EX 5/7/11RT Systems Contents of EXB 5/7/11RT Battery Module PN 86207 /86209 Installation in Tower Configuration Installation in Rack Mounting Configuration Not to scale Page Install input/output cables Per .7 prior to this step Bracket SystemConnecting the RS232 Communication Port Communication PortsConnecting the Dry Relay Contact Communication Port Installation of Optional Transverse CardDual U-Talk/Basic Card JBus CardProper operation Dual port Shut CardRemote Emergency Power Off Repo Communication Port Max AWG EX 11RT System ConnectionsSources are open OFF/OPEN Always connect the earth ground wire first OutputProtection for all transformer output terminals Connecting EX RT Transformer Module120VAC output terminals Lb-N, La-N Bypass AC Mains Power Module I/O Box Connection of Battery Module EXB AC Input Connection of Optional CLA ModuleThis page left blank intentionally Initial Startup Required for initial startup onlyUPS Personalization Control Panel with scroll up and down buttonsDisplay Factory setting Options Display Factory setting Options CommentsMGE UPS SYSTEMS, INC Symptoms IT Network mode Industrial mode Then go to Advanced settings and UPS settings UPS personalization through external softwareFinal Startup sequence During the startup, if the Bypass AC source is outNormal double conversion Mode Operating ModesECO Mode ECO mode displayOperation on Battery Power Transfer to Battery PowerFirst Case Operation on battery Second Case Low battery warningReturn of Normal AC source Power to the loadShutdown Troubleshooting Symptoms Indication CorrectionBattery Fault LED Hot Swapping the Power Module 1CXXXXXXXRe-connecting the Power Module Disconnecting the Battery Module Hot Swapping the Battery ModuleRe-connecting the Battery Module This page left blank intentionally Electrical Specifications System Input/Output Power RatingsSystem Overload Characteristics Source Voltage FrequencySystem Short Circuit Protection System Backup CharacteristicsEX RT CLA Module Configuration for Hours backup time KVA / kW 25% 50% 75% 100% Output load percentageEnvironmental Characteristics Operation Mode On-line On BatteryHeat Rejection SystemMGE Standard Single Phrase Warranty Proprietary Rights StatementUser Information Warranty Extension Warranty+ not available on productsProduct information Scheduling Field Service Engineer Support Part Number Assembly Number Serial numberEX 5/7/11RT Systems Glossary IEC Osha This page left blank intentionally Reorder Form Scenic Avenue Costa Mesa, CA Contact MGE