Installation and User Manual
3.3Information Technology IT Network and Industrial Operating Modes
Table
Symptoms | IT Network mode | Industrial mode |
Overload, and Bypass | Load is transferred to Bypass AC source. |
source in tolerance. | UPS returns to normal mode if overload |
| is removed. |
Same as IT Network mode, but AC to the UPS does not return to normal mode if overload
is removed.
Overload, and Bypass | The UPS shuts down and load is not | Load is transferred to Bypass |
AC source not in tolerance. | transferred to Bypass AC source. | AC source with 10 milli- |
|
| seconds output break. |
|
| The UPS does not return to |
|
| normal mode if overload |
|
| is removed. |
Output short circuit and Bypass | The load remains powered by the UPS. | Load is transferred to Bypass |
AC source in tolerance. | The UPS shuts down after 3 minutes | AC source. The UPS does not |
| if the short circuit remains. | return to normal mode if the |
|
| short circuit is removed. |
Output short circuit and Bypass AC source not in tolerance.
The load remains powered by the UPS. The UPS shuts down after 3 minutes if the short circuit remains.
The load is transferred to Bypass AC source with
10 milliseconds output break. The UPS does not return to normal mode if the short circuit is removed.
Operation | 3 — 5 |