MGE UPS Systems EX-5, EX-7, EX-11RT manual Multiple Battery Module Backup Time at Full Load

Page 23

EX 5/7/11RT Systems

Installation and User Manual

 

 

 

1.5.3Multiple Battery Module Backup Time at Full Load

Standard EX 5/7/11RT systems (one Power Module, and one Battery Module), offers a standard backup time of 5 to 12 minutes at full load.

To increase backup time, it is possible to connect up to 5 additional Battery Modules to the standard system. See section 2.8 for connections between standard system and Battery Module (EXB 5/7/11RT)

Figure 1-9: Typical back-up time with multiple EXB’s at full load.

Standard

 

Optional

EX 5/7/11RT systems

 

Configurations

 

 

 

 

 

 

 

 

 

EX 5/7/11RT EXB 5/7/11RT +

EXB 5/7/11RT +

EXB 5/7/11RT +

EXB 5/7/11RT

+

EXB 5/7/11RT

+

EXB 5/7/11RT

5 kVA

:

9 min

25 min

45 min

60 min

84 min

100 min

7 kVA

:

7 min

20 min

32 min

45 min

57 min

72 min

11 kVA:

 

5 min

14 min

22 min

30 min

42 min

53 min

See Appendix for additional Back-up time information.

1.5.4Battery Extension Cable Kit

(6 ft./1.8 m, Part number 86006)

This extended battery cable kit will be used instead of the standard battery cable when Battery Modules (EXBs) are distant from each other (located in two different enclosures, for instance).

The battery extension cable kit includes a 6 ft. long, straight connector battery power cable and a 6 ft. long battery detection cable.

86-86000-00 B00

Introduction

1 — 9

Image 23
Contents EX 5/7/11RT Systems Page Technical Support Customer Care Center Hours 24/7 MGE UPS SYSTEMS, INC Scenic Avenue Costa Mesa, CA 92626 714EX 5/7/11RT Systems Contents Setup and Installation Return Policy for Repair of Single Phase Products RGA Technical Support and Product ServicesFigures Tables Certification Standards Important Safety InstructionsEnvironment Special PrecautionsAdditional Modules Serial Numbers Section Descriptions This page left blank intentionally Input voltage must be the same as output voltage on HV units ScopePart Number Description Transformer Module Characteristics Ratings System Electrical CharacteristicsTower Configuration Standard ConfigurationRack Configuration Model Dimensions HxWxD WeightsRear Panel Components Power Module EX 5/7/11 RT1 1 R T Power Module Display and Control PanelEX RT Transformer Module Battery/Transformer/CLA Module Rail Kit Optional AccessoriesPower Module Rail Kit Battery Extension Cable Kit Multiple Battery Module Backup Time at Full LoadInput/Output Box Battery Integration Kit with CastersEX RT Transformer Module Contents Recommended Batteries CLA Module ContentsEX 5/7/11RT All Modules are shipped in separate boxes Unpacking and Parts CheckContents of Standard EX 5/7/11RT Systems Contents of EXB 5/7/11RT Battery Module PN 86207 /86209 Installation in Tower Configuration Installation in Rack Mounting Configuration Not to scale Page Bracket System Install input/output cables Per .7 prior to this stepCommunication Ports Connecting the RS232 Communication PortInstallation of Optional Transverse Card Connecting the Dry Relay Contact Communication PortDual port Shut Card Dual U-Talk/Basic CardJBus Card Proper operationRemote Emergency Power Off Repo Communication Port Sources are open OFF/OPEN System ConnectionsMax AWG EX 11RT Output Always connect the earth ground wire first120VAC output terminals Lb-N, La-N Connecting EX RT Transformer ModuleProtection for all transformer output terminals Bypass AC Mains Power Module I/O Box Connection of Battery Module EXB Connection of Optional CLA Module AC InputThis page left blank intentionally Required for initial startup only Initial StartupControl Panel with scroll up and down buttons UPS PersonalizationDisplay Factory setting Options Comments Display Factory setting OptionsMGE UPS SYSTEMS, INC Symptoms IT Network mode Industrial mode During the startup, if the Bypass AC source is out Then go to Advanced settings and UPS settingsUPS personalization through external software Final Startup sequenceOperating Modes Normal double conversion ModeECO mode display ECO ModeSecond Case Low battery warning Operation on Battery PowerTransfer to Battery Power First Case Operation on batteryShutdown Power to the loadReturn of Normal AC source Symptoms Indication Correction TroubleshootingBattery Fault LED 1CXXXXXXX Hot Swapping the Power ModuleRe-connecting the Power Module Re-connecting the Battery Module Hot Swapping the Battery ModuleDisconnecting the Battery Module This page left blank intentionally Source Voltage Frequency Electrical SpecificationsSystem Input/Output Power Ratings System Overload CharacteristicsEX RT CLA Module System Backup CharacteristicsSystem Short Circuit Protection KVA / kW 25% 50% 75% 100% Output load percentage Configuration for Hours backup timeSystem Environmental CharacteristicsOperation Mode On-line On Battery Heat RejectionProprietary Rights Statement MGE Standard Single Phrase WarrantyProduct information Warranty Extension Warranty+ not available on productsUser Information Part Number Assembly Number Serial number Scheduling Field Service Engineer SupportEX 5/7/11RT Systems Glossary IEC Osha This page left blank intentionally Reorder Form Scenic Avenue Costa Mesa, CA Contact MGE