EX 5/7/11RT Systems
Table
kVA / kW | 25% | 50% | 75% | 100% | Output load percentage |
|
|
|
|
|
|
5kVA / | 96 | 97 | 96 | 97 | Output: 220 / 230 / 240 Volts |
4kWatts | 95 | 96 | 96 | 96 | Output: 200 / 208 / 250 Volts |
|
|
|
|
|
|
7kVA / | 96 | 97 | 96 | 97 | Output: 220 / 230 / 240 Volts |
4.9kWatts | 95 | 96 | 96 | 96 | Output: 200 / 208 / 250 Volts |
|
|
|
|
|
|
11kVA / | 96 | 97 | 96 | 97 | Output: 220 / 230 / 240 Volts |
8kWatts | 95 | 96 | 96 | 96 | Output: 200 / 208 / 250 Volts |
|
|
|
|
|
|
5.6Heat Rejection
Table
System |
| Operation Mode |
| |
|
|
| On Battery |
|
5kVA | 1350 |
| 1861 |
|
|
|
|
|
|
7kVA | 1654 |
| 2280 |
|
|
|
|
|
|
11kVA | 3033 |
| 3723 |
|
5.7Environmental Characteristics
◗The operating temperature is 0 to 40°C (8 hours at 45°C), however optimum operation is within the +20 to +25°C range and at
◗The storage temperature:
◗Battery backup time is adversely affected by high and low temperatures. It is significantly reduced at tempera- tures under 10°C. Above 25°C, battery service life is cut in half every 10°C. Above 40°C, battery manufacturers no longer guarantee operation due to the risk of thermal runaway.
◗Air enters through the front air vent grills and exits through the back. Always keep air vent grills unobstructed.
5 — 4 | Appendix |