MGE UPS Systems EX-5, EX-7, EX-11RT manual Connecting the Dry Relay Contact Communication Port

Page 36
contact normally open. contact normally closed.

EX 5/7/11RT Systems

2.5.2 Connecting the Dry (Relay) Contact Communication Port 2

The system status is indicated by the connection of common pin (Pin 5) to the appropriate pins. Refer to the pin explanations below for details.

Figure 2-9: Relay Pin Connections for Communication Port.

 

5

4

3

2

1

 

 

 

9

8

7

6

 

NC

NO

 

NO

 

NO

NO

common

When the status is active, the contact between the common (Pin 5) and the relevant information pin is closed.

Pin 1, 2: not used.

Pin 3: Remote Power Off signal (5 to 27 VDC, 10 mA max).

Pin 4: Operation on mains (not on battery). (48VDC, 2A max.)

Pin 5: User common.

Pin 6: Operation on automatic bypass.

Pin 7: Low battery.

Pin 8: Load protected

Pin 9: Operation on battery.

Legend:

NO:

NC:

2.5.3Installation of Optional Transverse Card

It is not necessary to shut down the UPS to install the optional communications card, except for USB card. Following is a typical installation of the Transverse card (optional Network Management card PN 66074 is shown below).

Proceed as follows:

1.Remove the slot cover secured by two screws.

2. Insert the Transverse card into the slot 1 .

3.Secure the card with both screws.

4.Refer to user manual of the Network Management Card for set-up.

Figure 2-10: Communication Card Slot with Network Management Card installed.

1

2 — 10

Installation

86-86000-00 B00

Image 36
Contents EX 5/7/11RT Systems Page MGE UPS SYSTEMS, INC Scenic Avenue Costa Mesa, CA 92626 714 Technical Support Customer Care Center Hours 24/7EX 5/7/11RT Systems Contents Setup and Installation Technical Support and Product Services Return Policy for Repair of Single Phase Products RGAFigures Tables Important Safety Instructions Certification StandardsSpecial Precautions EnvironmentAdditional Modules Serial Numbers Section Descriptions This page left blank intentionally Scope Input voltage must be the same as output voltage on HV unitsPart Number Description System Electrical Characteristics Transformer Module Characteristics RatingsStandard Configuration Tower ConfigurationModel Dimensions HxWxD Weights Rack ConfigurationPower Module EX 5/7/11 RT Rear Panel ComponentsPower Module Display and Control Panel EX RT Transformer Module1 1 R T Optional Accessories Power Module Rail KitBattery/Transformer/CLA Module Rail Kit Multiple Battery Module Backup Time at Full Load Battery Extension Cable KitBattery Integration Kit with Casters Input/Output BoxEX RT Transformer Module Contents CLA Module Contents EX 5/7/11RTRecommended Batteries Unpacking and Parts Check All Modules are shipped in separate boxesContents of Standard EX 5/7/11RT Systems Contents of EXB 5/7/11RT Battery Module PN 86207 /86209 Installation in Tower Configuration Installation in Rack Mounting Configuration Not to scale Page Install input/output cables Per .7 prior to this step Bracket SystemConnecting the RS232 Communication Port Communication PortsConnecting the Dry Relay Contact Communication Port Installation of Optional Transverse CardDual U-Talk/Basic Card JBus CardProper operation Dual port Shut CardRemote Emergency Power Off Repo Communication Port System Connections Max AWG EX 11RTSources are open OFF/OPEN Always connect the earth ground wire first OutputConnecting EX RT Transformer Module Protection for all transformer output terminals120VAC output terminals Lb-N, La-N Bypass AC Mains Power Module I/O Box Connection of Battery Module EXB AC Input Connection of Optional CLA ModuleThis page left blank intentionally Initial Startup Required for initial startup onlyUPS Personalization Control Panel with scroll up and down buttonsDisplay Factory setting Options Display Factory setting Options CommentsMGE UPS SYSTEMS, INC Symptoms IT Network mode Industrial mode Then go to Advanced settings and UPS settings UPS personalization through external softwareFinal Startup sequence During the startup, if the Bypass AC source is outNormal double conversion Mode Operating ModesECO Mode ECO mode displayOperation on Battery Power Transfer to Battery PowerFirst Case Operation on battery Second Case Low battery warningPower to the load Return of Normal AC sourceShutdown Troubleshooting Symptoms Indication CorrectionBattery Fault LED Hot Swapping the Power Module 1CXXXXXXXRe-connecting the Power Module Hot Swapping the Battery Module Disconnecting the Battery ModuleRe-connecting the Battery Module This page left blank intentionally Electrical Specifications System Input/Output Power RatingsSystem Overload Characteristics Source Voltage FrequencySystem Backup Characteristics System Short Circuit ProtectionEX RT CLA Module Configuration for Hours backup time KVA / kW 25% 50% 75% 100% Output load percentageEnvironmental Characteristics Operation Mode On-line On BatteryHeat Rejection SystemMGE Standard Single Phrase Warranty Proprietary Rights StatementWarranty Extension Warranty+ not available on products User InformationProduct information Scheduling Field Service Engineer Support Part Number Assembly Number Serial numberEX 5/7/11RT Systems Glossary IEC Osha This page left blank intentionally Reorder Form Scenic Avenue Costa Mesa, CA Contact MGE