MGE UPS Systems EX-5, EX-7, EX-11RT manual Display Factory setting Options Comments

Page 49

 

 

 

 

 

Installation and User Manual

 

 

 

 

 

 

 

Table 3-1: Local Settings.

 

 

 

 

 

 

 

 

 

 

 

 

 

Display

Factory setting

 

Options

 

 

 

 

 

 

 

 

 

Language

English

 

French, Spanish, German, Italian

 

 

 

 

 

 

 

 

Date/time format

International

 

US

 

 

 

 

 

 

 

 

Date/time change

(DD-MM-YYYY/HH:MM)

MM-DD-YYYY/HH:MM adjustable

 

 

 

 

 

 

 

 

Audible alarm

Quick beeps

 

Slow beeps

 

 

 

 

 

 

 

 

Table 3-2: Output Features.

 

 

 

 

 

 

 

 

 

 

 

 

Display

Factory setting

Options

 

Comments

 

 

 

 

 

 

 

Output voltage

208 Volts AC (***)

200/208/220/230/240/250

Input voltage must be equal to

 

 

 

 

 

output voltage

 

 

 

 

 

 

 

 

Frequency converter

Disabled

Enabled

 

Bypass AC source disabled

 

 

 

 

 

 

 

 

Output frequency

Auto ranging

50/60 Hz

 

User selectable under

 

 

 

 

 

frequency converter mode

 

 

 

 

 

 

 

 

ECO mode

Disabled

Enabled

 

See section 3.4.2.

 

 

 

 

 

 

 

 

Hot standby

Disabled

Enabled

 

Full redundancy (see Figure 3-3)

 

 

 

 

 

 

 

 

Operating mode

Industrial

IT Network

 

(*) See Table 3-5.

 

 

 

 

 

 

 

Bypass

When bypass NOK

When bypass OK (**)

(*) See Table 3-5.

 

Transfer

 

 

 

 

 

 

 

 

 

 

 

 

Interrupt time

10 ms

10 to 200 ms

Interrupt time calibration during

 

 

 

(by steps of 10 ms)

during load transfer when

 

 

 

 

 

Bypass AC source

 

 

 

 

 

is out of tolerances

 

 

 

 

 

 

 

 

Overload level

102%

50/70%

 

 

 

(*): - Select "IT Network" for computer loads. Select “Industrial” for other applications or when there exists and absolute need for service continuity (with potential 10msec. interrupt) when Bypass AC source is not within set tolerances.

See table 3-5 for more details

(**)UPS will switch to Bypass AC Source if it is within the set tolerances. (***) Input voltage must be equal to output voltage.

Figure 3-3: Configuration used to provide cascade redundancy to critical loads.

BYPASS AC

Protective Device

NORMAL AC

Utility

AC Source

Protective Device NORMAL AC

Cascade redundancy configuration offers better protection to critical load, whereas the first UPS acts as the Bypass AC Source for the second UPS.

LOAD

86-86000-00 B00

Operation

3 — 3

Image 49
Contents EX 5/7/11RT Systems Page Technical Support Customer Care Center Hours 24/7 MGE UPS SYSTEMS, INC Scenic Avenue Costa Mesa, CA 92626 714EX 5/7/11RT Systems Contents Setup and Installation Return Policy for Repair of Single Phase Products RGA Technical Support and Product ServicesFigures Tables Certification Standards Important Safety InstructionsEnvironment Special PrecautionsAdditional Modules Serial Numbers Section Descriptions This page left blank intentionally Input voltage must be the same as output voltage on HV units ScopePart Number Description Transformer Module Characteristics Ratings System Electrical CharacteristicsTower Configuration Standard ConfigurationRack Configuration Model Dimensions HxWxD WeightsRear Panel Components Power Module EX 5/7/11 RTEX RT Transformer Module Power Module Display and Control Panel1 1 R T Power Module Rail Kit Optional AccessoriesBattery/Transformer/CLA Module Rail Kit Battery Extension Cable Kit Multiple Battery Module Backup Time at Full LoadInput/Output Box Battery Integration Kit with CastersEX RT Transformer Module Contents EX 5/7/11RT CLA Module ContentsRecommended Batteries All Modules are shipped in separate boxes Unpacking and Parts CheckContents of Standard EX 5/7/11RT Systems Contents of EXB 5/7/11RT Battery Module PN 86207 /86209 Installation in Tower Configuration Installation in Rack Mounting Configuration Not to scale Page Bracket System Install input/output cables Per .7 prior to this stepCommunication Ports Connecting the RS232 Communication PortInstallation of Optional Transverse Card Connecting the Dry Relay Contact Communication PortJBus Card Dual U-Talk/Basic CardProper operation Dual port Shut CardRemote Emergency Power Off Repo Communication Port Max AWG EX 11RT System ConnectionsSources are open OFF/OPEN Output Always connect the earth ground wire firstProtection for all transformer output terminals Connecting EX RT Transformer Module120VAC output terminals Lb-N, La-N Bypass AC Mains Power Module I/O Box Connection of Battery Module EXB Connection of Optional CLA Module AC InputThis page left blank intentionally Required for initial startup only Initial StartupControl Panel with scroll up and down buttons UPS PersonalizationDisplay Factory setting Options Comments Display Factory setting OptionsMGE UPS SYSTEMS, INC Symptoms IT Network mode Industrial mode UPS personalization through external software Then go to Advanced settings and UPS settingsFinal Startup sequence During the startup, if the Bypass AC source is outOperating Modes Normal double conversion ModeECO mode display ECO ModeTransfer to Battery Power Operation on Battery PowerFirst Case Operation on battery Second Case Low battery warningReturn of Normal AC source Power to the loadShutdown Symptoms Indication Correction TroubleshootingBattery Fault LED 1CXXXXXXX Hot Swapping the Power ModuleRe-connecting the Power Module Disconnecting the Battery Module Hot Swapping the Battery ModuleRe-connecting the Battery Module This page left blank intentionally System Input/Output Power Ratings Electrical SpecificationsSystem Overload Characteristics Source Voltage FrequencySystem Short Circuit Protection System Backup CharacteristicsEX RT CLA Module KVA / kW 25% 50% 75% 100% Output load percentage Configuration for Hours backup timeOperation Mode On-line On Battery Environmental CharacteristicsHeat Rejection SystemProprietary Rights Statement MGE Standard Single Phrase WarrantyUser Information Warranty Extension Warranty+ not available on productsProduct information Part Number Assembly Number Serial number Scheduling Field Service Engineer SupportEX 5/7/11RT Systems Glossary IEC Osha This page left blank intentionally Reorder Form Scenic Avenue Costa Mesa, CA Contact MGE