| Installation and User Manual | |
|
|
|
|
|
|
|
Table |
|
|
|
|
| |
|
|
|
|
|
|
|
| Display | Factory setting |
| Options |
|
|
|
|
|
|
|
| |
| Language | English |
| French, Spanish, German, Italian | ||
|
|
|
|
|
|
|
| Date/time format | International |
| US |
|
|
|
|
|
|
| ||
| Date/time change | |||||
|
|
|
|
|
|
|
| Audible alarm | Quick beeps |
| Slow beeps |
|
|
|
|
|
|
|
| |
Table |
|
|
|
| ||
|
|
|
|
|
|
|
| Display | Factory setting | Options |
| Comments | |
|
|
|
|
|
| |
| Output voltage | 208 Volts AC (***) | 200/208/220/230/240/250 | Input voltage must be equal to | ||
|
|
|
|
| output voltage | |
|
|
|
|
|
|
|
| Frequency converter | Disabled | Enabled |
| Bypass AC source disabled | |
|
|
|
|
|
|
|
| Output frequency | Auto ranging | 50/60 Hz |
| User selectable under | |
|
|
|
|
| frequency converter mode | |
|
|
|
|
|
|
|
| ECO mode | Disabled | Enabled |
| See section 3.4.2. | |
|
|
|
|
|
|
|
| Hot standby | Disabled | Enabled |
| Full redundancy (see Figure | |
|
|
|
|
|
|
|
| Operating mode | Industrial | IT Network |
| (*) See Table | |
|
|
|
|
|
| |
| Bypass | When bypass NOK | When bypass OK (**) | (*) See Table | ||
| Transfer |
|
|
|
|
|
|
|
|
|
|
| |
| Interrupt time | 10 ms | 10 to 200 ms | Interrupt time calibration during | ||
|
|
| (by steps of 10 ms) | during load transfer when | ||
|
|
|
|
| Bypass AC source | |
|
|
|
|
| is out of tolerances | |
|
|
|
|
|
|
|
| Overload level | 102% | 50/70% |
|
|
|
(*): - Select "IT Network" for computer loads. Select “Industrial” for other applications or when there exists and absolute need for service continuity (with potential 10msec. interrupt) when Bypass AC source is not within set tolerances.
See table
(**)UPS will switch to Bypass AC Source if it is within the set tolerances. (***) Input voltage must be equal to output voltage.
Figure 3-3: Configuration used to provide cascade redundancy to critical loads.
BYPASS AC
Protective Device
NORMAL AC
Utility
AC Source
Protective Device NORMAL AC
Cascade redundancy configuration offers better protection to critical load, whereas the first UPS acts as the Bypass AC Source for the second UPS.
LOAD
Operation | 3 — 3 |