MGE UPS Systems EX-5, EX-7, EX-11RT manual Return of Normal AC source, Shutdown, Power to the load

Page 56

EX 5/7/11RT Systems

3.6Return of Normal AC source

After an outage, the UPS restarts automatically when AC power is restored (unless this function has been disabled via UPS personalization).

3.7Shutdown

Figure 3-7: Shutdown display, circuit breaker, and AC source switch.

17

OFFON

20

14

1.Press the OFF button 20 more than 3 seconds.

CAUTION: The load is no longer protected by the UPS. It is powered via the Bypass AC source. If the UPS is set in frequency converter mode, the load will not be powered.

If the Bypass AC source is out of tolerance, the UPS will generate a calibrated 10msec output interrupt.

2.Set the battery circuit breaker(s) 14 to the OFF position.

3. Set the Normal AC source circuit breaker

8to the OFF position. LED 17 is now OFF.

CAUTION: Performing this step will disconnect

8

power to the load.

 

4.For the complete shutdown of the UPS (no input and output power), the upstream circuit breaker (not included) should be set to the OFF position.

3 — 10

Operation

86-86000-00 B00

Image 56
Contents EX 5/7/11RT Systems Page MGE UPS SYSTEMS, INC Scenic Avenue Costa Mesa, CA 92626 714 Technical Support Customer Care Center Hours 24/7EX 5/7/11RT Systems Contents Setup and Installation Technical Support and Product Services Return Policy for Repair of Single Phase Products RGAFigures Tables Important Safety Instructions Certification StandardsSpecial Precautions EnvironmentAdditional Modules Serial Numbers Section Descriptions This page left blank intentionally Scope Input voltage must be the same as output voltage on HV unitsPart Number Description System Electrical Characteristics Transformer Module Characteristics RatingsStandard Configuration Tower ConfigurationModel Dimensions HxWxD Weights Rack ConfigurationPower Module EX 5/7/11 RT Rear Panel Components1 1 R T Power Module Display and Control PanelEX RT Transformer Module Battery/Transformer/CLA Module Rail Kit Optional AccessoriesPower Module Rail Kit Multiple Battery Module Backup Time at Full Load Battery Extension Cable KitBattery Integration Kit with Casters Input/Output BoxEX RT Transformer Module Contents Recommended Batteries CLA Module ContentsEX 5/7/11RT Unpacking and Parts Check All Modules are shipped in separate boxesContents of Standard EX 5/7/11RT Systems Contents of EXB 5/7/11RT Battery Module PN 86207 /86209 Installation in Tower Configuration Installation in Rack Mounting Configuration Not to scale Page Install input/output cables Per .7 prior to this step Bracket SystemConnecting the RS232 Communication Port Communication PortsConnecting the Dry Relay Contact Communication Port Installation of Optional Transverse CardDual U-Talk/Basic Card JBus CardProper operation Dual port Shut CardRemote Emergency Power Off Repo Communication Port Sources are open OFF/OPEN System ConnectionsMax AWG EX 11RT Always connect the earth ground wire first Output120VAC output terminals Lb-N, La-N Connecting EX RT Transformer ModuleProtection for all transformer output terminals Bypass AC Mains Power Module I/O Box Connection of Battery Module EXB AC Input Connection of Optional CLA ModuleThis page left blank intentionally Initial Startup Required for initial startup onlyUPS Personalization Control Panel with scroll up and down buttonsDisplay Factory setting Options Display Factory setting Options CommentsMGE UPS SYSTEMS, INC Symptoms IT Network mode Industrial mode Then go to Advanced settings and UPS settings UPS personalization through external softwareFinal Startup sequence During the startup, if the Bypass AC source is outNormal double conversion Mode Operating ModesECO Mode ECO mode displayOperation on Battery Power Transfer to Battery PowerFirst Case Operation on battery Second Case Low battery warningShutdown Power to the loadReturn of Normal AC source Troubleshooting Symptoms Indication CorrectionBattery Fault LED Hot Swapping the Power Module 1CXXXXXXXRe-connecting the Power Module Re-connecting the Battery Module Hot Swapping the Battery ModuleDisconnecting the Battery Module This page left blank intentionally Electrical Specifications System Input/Output Power RatingsSystem Overload Characteristics Source Voltage FrequencyEX RT CLA Module System Backup CharacteristicsSystem Short Circuit Protection Configuration for Hours backup time KVA / kW 25% 50% 75% 100% Output load percentageEnvironmental Characteristics Operation Mode On-line On BatteryHeat Rejection SystemMGE Standard Single Phrase Warranty Proprietary Rights StatementProduct information Warranty Extension Warranty+ not available on productsUser Information Scheduling Field Service Engineer Support Part Number Assembly Number Serial numberEX 5/7/11RT Systems Glossary IEC Osha This page left blank intentionally Reorder Form Scenic Avenue Costa Mesa, CA Contact MGE