MGE UPS Systems EX-7 manual System Connections, Max AWG EX 11RT, Sources are open OFF/OPEN

Page 39

Installation and User Manual

2.7System Connections

WARNING

This type of connections must be carried out by qualified electrical personnel.

 

Before carrying out any connections, check that battery circuit breaker 14 is

 

OFF and that the upstream protection devices (Normal and Bypass AC

 

sources) are open (OFF/OPEN).

 

 

2.7.1Connections with Common Normal and Bypass AC Sources (Single Mains)

Figure 2-11: Power Module I/O Box Terminal Block Diagram.

Output

Bypass AC source

200/208/220/230/240Vac

200/208/220/230/240Vac

Normal AC source

200/208/220/230/240Vac

L6 L5

L2 L1 L1

L4 L3

Terminal tightening torque:

– 18 lb-in. for EX 5/7RT Power Module

– 35 lb-in. for EX 11RT Power Module

Terminal block capacity:

 

 

 

 

 

 

 

 

 

 

 

 

- Max. 4AWG (EX 11RT)

 

 

 

 

 

 

Jumper

- Max. 6AWG (EX 5/7RT)

 

 

(see note)

 

 

 

 

 

 

 

 

 

 

NOTE

The

Power Module is factory configured for single input, whereas both Normal AC

 

 

 

and

Bypass AC sources are identical, by means of jumper between L1 and L3.

 

 

 

 

 

 

 

 

 

Jumper must be removed for separate Normal AC and Bypass AC sources (2 Mains) or with Frequency Converter application.

Keep Manual Bypass Switch 7 at Normal position.

86-86000-00 B00

Installation

2 — 13

Image 39
Contents EX 5/7/11RT Systems Page Technical Support Customer Care Center Hours 24/7 MGE UPS SYSTEMS, INC Scenic Avenue Costa Mesa, CA 92626 714EX 5/7/11RT Systems Contents Setup and Installation Return Policy for Repair of Single Phase Products RGA Technical Support and Product ServicesFigures Tables Certification Standards Important Safety InstructionsEnvironment Special PrecautionsAdditional Modules Serial Numbers Section Descriptions This page left blank intentionally Input voltage must be the same as output voltage on HV units ScopePart Number Description Transformer Module Characteristics Ratings System Electrical CharacteristicsTower Configuration Standard ConfigurationRack Configuration Model Dimensions HxWxD WeightsRear Panel Components Power Module EX 5/7/11 RTPower Module Display and Control Panel EX RT Transformer Module1 1 R T Optional Accessories Power Module Rail KitBattery/Transformer/CLA Module Rail Kit Battery Extension Cable Kit Multiple Battery Module Backup Time at Full LoadInput/Output Box Battery Integration Kit with CastersEX RT Transformer Module Contents CLA Module Contents EX 5/7/11RTRecommended Batteries All Modules are shipped in separate boxes Unpacking and Parts CheckContents of Standard EX 5/7/11RT Systems Contents of EXB 5/7/11RT Battery Module PN 86207 /86209 Installation in Tower Configuration Installation in Rack Mounting Configuration Not to scale Page Bracket System Install input/output cables Per .7 prior to this stepCommunication Ports Connecting the RS232 Communication PortInstallation of Optional Transverse Card Connecting the Dry Relay Contact Communication PortDual port Shut Card Dual U-Talk/Basic CardJBus Card Proper operationRemote Emergency Power Off Repo Communication Port System Connections Max AWG EX 11RTSources are open OFF/OPEN Output Always connect the earth ground wire firstConnecting EX RT Transformer Module Protection for all transformer output terminals120VAC output terminals Lb-N, La-N Bypass AC Mains Power Module I/O Box Connection of Battery Module EXB Connection of Optional CLA Module AC InputThis page left blank intentionally Required for initial startup only Initial StartupControl Panel with scroll up and down buttons UPS PersonalizationDisplay Factory setting Options Comments Display Factory setting OptionsMGE UPS SYSTEMS, INC Symptoms IT Network mode Industrial mode During the startup, if the Bypass AC source is out Then go to Advanced settings and UPS settingsUPS personalization through external software Final Startup sequenceOperating Modes Normal double conversion ModeECO mode display ECO ModeSecond Case Low battery warning Operation on Battery PowerTransfer to Battery Power First Case Operation on batteryPower to the load Return of Normal AC sourceShutdown Symptoms Indication Correction TroubleshootingBattery Fault LED 1CXXXXXXX Hot Swapping the Power ModuleRe-connecting the Power Module Hot Swapping the Battery Module Disconnecting the Battery ModuleRe-connecting the Battery Module This page left blank intentionally Source Voltage Frequency Electrical SpecificationsSystem Input/Output Power Ratings System Overload CharacteristicsSystem Backup Characteristics System Short Circuit ProtectionEX RT CLA Module KVA / kW 25% 50% 75% 100% Output load percentage Configuration for Hours backup timeSystem Environmental CharacteristicsOperation Mode On-line On Battery Heat RejectionProprietary Rights Statement MGE Standard Single Phrase WarrantyWarranty Extension Warranty+ not available on products User InformationProduct information Part Number Assembly Number Serial number Scheduling Field Service Engineer SupportEX 5/7/11RT Systems Glossary IEC Osha This page left blank intentionally Reorder Form Scenic Avenue Costa Mesa, CA Contact MGE