4.2Hot Swapping the Power Module
This operation can be performed without interrupting the load. Figure
| 17 | Stop the system with the OFF button | 20 |
| |
| 1. |
| |||
|
| (press more than 3 seconds). System is now | |||
|
| powered by Bypass AC source. |
|
|
|
|
| Check if UPS is on Bypass AC source by |
| ||
| XXX FAULT | verifying that: |
|
|
|
|
|
|
|
| |
| 1CXXXXXXX | LED 17 is ON (If LED 17 is not ON, do not | |||
|
| ||||
OFF | ON | turn the manual bypass and call the after sales | |||
|
| support department). |
|
|
|
20 | 2. | Turn the manual bypass switch | 7 | to the | |
| BYPASS position. |
|
|
| |
|
|
|
|
| |
| 3. | Switch the battery circuit breaker(s) | 14 | to the | |
|
| OFF position. |
|
|
|
| 42 | CAUTION: Do not switch the Normal AC | |||
|
| ||||
| 40 | source | 8 to | ||
| 7 | the OFF position. |
|
| |
| Doing so will disconnect | ||||
|
| ||||
|
| power to the load. |
|
| |
| 4. Loosen three screws to remove the |
|
| ||
| 8 Step 4 in Tower | Input/Output box. |
|
|
|
|
|
|
|
| |
| configuration |
| 40 and | 42 | |
| 5. | Disconnect the battery cables |
from the Power Module.
The Power Module can be replaced.
The connected equipment is powered by the
Bypass AC source.
Step 4 in Rack configuration.
Maintenance | 4 — 3 |