Gateway 312785C ControlLogix Configuration, Ethernet Module Properties

Page 73

ControlLogix Configuration

1.Run the RSLogix 5000 program and create a new configuration.

2.Add a 1756-ENET/B or a 1756-ENBT/A to your I/O configuration. You will need to:

a.Switch to offline mode.

b.Right click on the I/O Configuration node in the Controller Organizer view and choose Add Mod- ule.

c.In the Select Module Type window, choose

1756-ENET/B or 1756-ENBT/A entry. RSLogix will open the Module Properties window. See FIG. 69.

d.Enter the IP Address of the ENET/B or ENBT/A interface.

e.Click Finish to add the interface to your I/O con- figuration.

f.Download the configuration.

g.Switch to online mode and open the

1756-ENET/B or 1756-ENBT/A node proper- ties under the I/O Configuration in the Controller Organizer.

Appendix C: Graco Gateway to ControlLogix via Ethernet IP

h.Select the Port Configuration Tab from the Mod- ule Properties window. See FIG. 70.

i.Enter the IP Address and Subnet Mask. The IP Address must match the IP Address entered in the Properties window (FIG. 69).

j.Apply the settings using the Set button.

k.You can now verify the network module network communications with your unit using suitable diagnostic tools such as Ping.

3.Add the Graco Gateway to the RSLogix configura- tion as follows:

a.Switch to offline mode.

b.Right click on the 1756-ENET/B or

1756-ENBT/A node under the I/O Configuration in the Controller Organizer view and choose Add Module.

c.In the Select Module Type window, choose Generic Ethernet Module. See FIG. 71.

d.Click OK. This will open the Module Properties window. See FIG. 72.

IP Address

Finish Button

FIG. 69. Ethernet Module Properties

312785C

73

Image 73
Contents Gateway Network Communication Kits Important Safety InstructionsContents Related Manuals Graco Gateway KitsComponent Manuals in English Description Fire and Explosion Hazard Graco Gateway Overview Install the Gateway Module HardwareLocation MountingNON-HAZARDOUS Area Cabling Connections Connect the Module to EasyKeyEasyKey Bottom View Wiring Diagrams onGateway Module IG EasyKey and Module Cable Connection PointsRS232/PG Power Connector Expansion PortUSB/PG Ethernet Mount the Control on DIN Rail Install CompactFlash CardSystem Requirements Install the GracoConfig SoftwareLoad the Software Software UpdatesSet Communications Port to USB Download the Preconfigured Database to the Gateway ModuleStartup GracoConfig Main Graco Gateway Network Communications ConfigurationCommunications Button Balloon HelpPreconfigured Database Setup the DatabaseRename PLC1 Mapping Gateway Blocks Map DataSetting Block Size Block Mapping Data Start Mix Process Modbus and I/O DataStop Mix Process Color Change ProcessStart Mix Mode Process Flow Chart Mixing Mode Process Flow Chart Purge Mode Process Flow Chart Color Change Mode Process Flow Chart Alarm Processing Flow Chart Alarm ProcessingModbus and I/O Data ProMix 2KS Digital Outputs Modbus Register ProMix 2KS Active Alarms Modbus RegisterBit Digital Input Binary Name Details ProMix 2KS Active Alarms Modbus Register ProMix 2KS Modbus/TCP Variable Map EasyKey ProMix 2KS Modbus/TCP Variable MapModbus Status Register Description Units Low Limit High LimitProMix 2KS Recipe Bits ProMix 2KS Recipe BitsGeneral Troubleshooting TroubleshootingSee Serial Communication Trou Communication TroubleshootingBleshooting page 36 or Ethernet Problem Cause Solution Graco Gateway Messages Troubleshooting Serial Communication Troubleshooting Ethernet Communication Troubleshooting Status STS LED LED FunctionsUser Communication Ports TX/RX LEDs Ethernet LEDsNon-Hazardous Area System Electrical SchematicPart No. Description Qty Parts417 Wiring DiagramsOverview Appendix a DeviceNet Slave CommunicationIntroduction DeviceNet Port ProtocolsDeviceNet Port Pin Outs and PLC Connection Predefined Master/Slave Connection Set About DeviceNetLevel of Support Configure the Gateway DeviceNet Option Card Gateway ConfigurationHardware Select DeviceNet Server Device Settings Add a Gateway Block Create Gateway BlocksSelect Data Type Word as Long DeviceNet Block Mapping Automatic EDS Update Automatic Update of the EDS FileEDS Validation Configure the RSNetWorx for DeviceNet SoftwareReview EDS Registration Apply and Save Create Valid DeviceNet Scanner Configure the Allen Bradley ControlLogix PLCMain Task Tree Wire the DeviceNet NetworkProfibus Port Protocols Appendix B Profibus DP Slave CommunicationAlso see Appendix B Profibus DP Slave Communi- cation on DP Master About Profibus DPInstall the GSD file Setup the PLCBrowse to GSD File DP Properties Window Setup the Profibus NetworkOpen Profibus Properties Set Transmission Rate Add Graco Gateway to Profibus Network Add the Graco Gateway to the Profibus NetworkConfigure Data Blocks Setup the Profibus Communication Graco Gateway SetupSelect Profibus Server Create a Variable Setup TagsSelect Block Type PLC Addressing Scheme How Addressing WorksPLC Useful FormulasEthernet PLC Connection Appendix C Graco Gateway to ControlLogix via Ethernet IPEthernet Module Properties ControlLogix ConfigurationPort Configuration Window Ethernet Module Properties Ethernet Configuration Data Ethernet Block Settings Graco Gateway ConfigurationAppendix C Graco Gateway to ControlLogix via Ethernet IP Dimensions Dimensions Technical Data Graco Information Graco Standard Warranty