Intel MPCMM0002 manual Interfacing FRUs to the CMM, Example Configurations

Page 66

Guidelines for Third Party Chassis Vendors—MPCMM0002 CMM

Three are wired to the Analog Devices* Complete Thermal System Management Controller ADM1026* on the CMM. Two of them (BP_AFT1 and BP_AFT2) can only be used for temperature readings from two different thermistors (which may be located anywhere on the chassis). These provide analog input via pins 35 (AIN6) and 34 (AIN7). The third pin must be used for thermistor return (BP_AFTREF), and is grounded via pin 21 (AGND) on the ADM1026.

13.4Interfacing FRUs to the CMM

The MPCMM0002 CMM can communicate with intelligent and non-intelligent FRUs sitting on any of the 42 IPMB buses. All 42 buses on the CMM are implemented on top of I2C. The two FPGAs shown in Figure 33 implement 42 I2C engines, one for each IPMB bus.

Depending on the requirements, one or more IPMB buses could be configured as I2C buses for non-intelligent FRUs. Any single bus can be configured as an IPMB or I2C bus via software. For intelligent FRUs, the bus must be configured as IPMB, and for non- intelligent FRUs that support I2C, the bus must be configured as I2C. FRUs of either type can either share a bus with other FRUs of the same kind or use a dedicated bus.

The following sub-sections explain how different types of intelligent and non-intelligent FRUs can be connected to the Chassis Management Module on an AdvancedTCA chassis.

13.4.1Example Configurations

Section 13.2, “IPMB Buses” on page 63 discusses the two basic IPMB bus topologies, radial and shared, that are supported by the Chassis Management Module. Following is a list of examples which allow different combinations of these topologies. This is not an exhaustive list of possible configurations, but just a few examples. The assumption here is that there is a mix of intelligent and non-intelligent FRUs, but there are no restrictions if a chassis consists of intelligent FRUs only. Also, for each of the example configuration below, redundancy has been assumed for intelligent FRUs.

Note: The following examples are only supported under firmware version 6.1 and above through appropriate configuration files.

13.4.1.1Example Chassis Configuration #1

Bus #18/39, configured as IPMB, shared by all 16 blades (shared topology)

Bus #1/22, configured as IPMB, shared by all intelligent PEMs and fan trays

Bus #2/23, configured as IPMB, for inter-CMM communication

Bus #3, configured as I2C bus, used solely by FRU1

Bus #24, configured as I2C bus, used solely by FRU2

Bus #5, configured as I2C bus, shared by other non-intelligent FRUs

13.4.1.2Example Chassis Configuration #2

Bus #1–16, configured as IPMB, one bus dedicated for each of the 16 blades (radial topology)

Bus #17, configured as I2C bus, shared by three non-intelligent fan trays

Bus #18/39, configured as IPMB, shared by two PEMs

Bus #19/40, configured as IPMB, for inter-CMM communication

Bus #20, configured as I2C bus, used solely by FRU1

 

Intel NetStructure® MPCMM0002 Chassis Management Module

July 2007

Hardware TPS

Order Number: 309247-004US

67

Image 66
Contents Hardware Technical Product Specification Intel NetStructure MPCMM0002 Chassis Management ModuleOrder Number 309247-004US Contents 17.4 Figures TablesOrder Number 309247-004US Revision History Date Revision DescriptionDocument Organization Acronyms and Terms Acronyms and TermsAcronym/Term Meaning User Documentation Architecture SpecificationIntroduction Product DefinitionMPCMM0002 CMM-Introduction Installing the CMM Getting StartedQuick Start Block Diagram Module ComponentsCMM Top View Layout Processor Features Sheet 1 Intel 80321 ProcessorProcessor Features Sheet 2 PbgaMemory EthernetSerial Port UARTs Fpga Watchdog TimerFpga Features Redundancy and Hot Swap CpldRide-Through Support 10 ADM1026 ControllerHot Swap Controller Ipmb Isolation LogicDual Bus Ipmb Isolation Requirements Ipmb Dual Star IsolationFpga Dimensions Mechanical InformationCMM Backing Plate Dimensions CMM Side View Dimensions Front Panel HardwareCoplanar Mating Connectors Rear Connector PlacementMPCMM0002 CMM Rear Connectors Vertical Mating ConnectorsBackplane Considerations CMM PowerDC Power Input Ipmb RoutingCDM Power Voltage Max Where Used Monitored By CurrentVoltage Usage Power Switch Filter TrayEthernet Routing Chassis Elements Directly Driven by CMM HardwareChassis Component Element CMM Connector Pinouts CMM Power ConnectorRear Connections Power Connector Pinouts Pin Signal Purpose Pin LengthPin Staging Power Connector Pinouts MatrixPower Connector Receptacle Pin Placement Sheet 1 Order Mating Tail Pin Code LengthRear Connections-MPCMM0002 CMM CMM Data Connector CMM Data ConnectorData Connector Pinouts Sheet 1 Signal Name Count Type Description Pin Name From TableData Connector Pinouts Sheet 2 Data Connector Pinouts Matrix Sheet 1Data Connector Pinouts Matrix Sheet 2 Data Connector Pinouts Matrix Sheet 3 Order Mating Length Tail Length Pin CodeGuide Post CMM RedundancyMPCMM0002 CMM-Rear Connections CDM Management Chassis Data Modules CDMsCDM Overview CDM Health LED StatesCDM Power CDM RedundancyFront Panel Serial Port PinoutsSerial Port RJ-45 Connector Pin Signal DescriptionEthernet Port Pinouts Ethernet Port PinoutsTelco Alarm Connector Ethernet Port LED StatesLED Color Status Description Cascading the Telco Alarm Connectors Telco Alarm PinoutPin Description MxxReset Input Alarm Quiet Switch Ganged Telco Alarm Cable Pinouts with CablingAlarm LEDs LED Symbol Status DescriptionLEDs User-Definable LEDs Health LEDHot Swap LED CMM Health LED StatesGrounding Considerations ESD Discharge ProtectionChassis Ground and Logic Ground Module Orientation ThermalsProcessor Heat Sink Module Airflow PathSide-to-Side Air Flow Typical Airflow and Cooling Requirements Airflow RequirementsBoard Resistance Curve Category CMMsThermal Sensors Airflow GuidelinesMinimum Air Flow Air Temp Rise Management Module Specifications Feature SummaryDimensions and Weight Dimensions and Weight12.3 Environmental Characteristics Environmental CharacteristicsReliability Estimate Data Agency CertificationsAssumptions and Notes Reliability Measure Value UnitsGuidelines for Third Party Chassis Vendors High Level DesignO Signals of the CMM Ipmb BusesIpmb Signal Physical Bus Number Physical Bus Number MappingRadial Bus Topologya Gpio Pins Dedicated I/O PinsExample Configurations Interfacing FRUs to the CMMIntelligent FRUs Non-Intelligent FRUs with I2C* SupportFRUs Based on the ADM1026 Two-Wire Serial Interface Based Non-Intelligent FRUs without I2C SupportFRU Data Storage for Non-Intelligent Devices Related Documents Temperature Sensors Fronted by the CMMControllers and I/O Ports for Non-Intelligent Devices Related DocumentsWarranty Information Returning a Defective Product RMAFor the Americas For Europe, Middle East, and Africa EmeaFor Asia and Pacific Apac Warranty Information-MPCMM0002 CMM Customer Support Technical Support and Return for Service AssistanceCustomer Support Sales AssistanceMaterial Declaration Data Sheet CertificationsMaterial Declaration Data Sheet Agency Information North America FCC Class aEnglish Safety Instructions English and French-translated belowTaiwan Class a Warning Statement FrenchJapan Vcci Class a Korean Class a Australia, New Zealand Safety Warnings Mesures de Sécurité MPCMM0002 CMM-Safety Warnings Sicherheitshinweise MPCMM0002 CMM-Safety Warnings Norme di Sicurezza MPCMM0002 CMM-Safety Warnings Instrucciones de Seguridad MPCMM0002 CMM-Safety Warnings Chinese Safety Warning MPCMM0002 CMM-Safety Warnings Fpga Working page only. Do not distribute Working page only. Do not distribute Working page only. Do not distribute