Aquacal 100 Controls Configuration & Adjustments, Level-2Microprocessor Programming...continued

Page 50

7.Pool Dead Band Differential...continued: Controls Configuration & Adjustments...

Level-2 Microprocessor Programming...continued:

7.Pool Dead Band Differential...continued:

C.Once the desired dead band value has been selected, not pressing depressing any buttons for 15-seconds will allow the controller to save the selection and return to the normal operating mode. Pressing the {POOL/SPA] key will also save the selection and step to the next menu parameter [LOC], (LOCK CODE).

8.Changing the Service Lock Code and “Back Door” Entry:

A.Changing the Code…

The factory default Service Lock Code is “50”. Service personnel are strongly advised to retain the factory default setting. However, should unauthorized access to Level-2 (Service) menu be suspected, it may be necessary to select a code other than “50”. To change the Service Lock Code:

1)Follow the steps 1a. through 1d. above to enter the service menu. Once [dEL] is displayed, press the [POOL/SPA] key until the display shows [LOC] (LOCK CODE).

2)Press the [UP] arrow key to display the current service lock code value. With the current value displayed the [UP] arrow key will increase the value while the [DOWN] arrow key will decrease the value. When the desired value is displayed not pressing depressing any buttons for 15 seconds will allow the controller to save the selection and return to the normal operating mode. Pressing the {POOL/SPA] key will also save the selection and step to the next menu parameter. It is recommended, however, unless attempting to prevent tampering, that the factory setting of: “50” remain in use.

B.Back-door Access (For use when correct Service Lock Code is unknown):

1)Simultaneously depress and hold the [POOL/SPA] and [UP ARROW] keys until the display shows “888”. This operation will reset the controller to the factory default settings.

2)The factory reset will change the service lock code back to the factory setting “50”. In addition, all other settings (including external controller configuration) are returned to the factory defaults. See section in this manual entitled: “Factory Default Settings” for a complete list of factory default parameters.

(End...Level-2 Microprocessor Programming)

50

Image 50
Contents ATTENTION INSTALLER ModelsInstallation Guide 100Page TABLE OF CONTENTS CONTINUED TABLE OF CONTENTSWelcome efficient than gas, and, when comparedAquaCal’s factory-trainedservice staff is Tto theScroll Compressor Important Features of Your New Heat PumpThermoLink Heat Exchanger Digital ControllerNTERS HOW A HEAT PUMP WORKSA Heat Pump Does Not Make Heat… HEATSAFETY INFORMATION Water Chemistry Safety Refrigerant Circuit Service Only byWater Temperature Safety Notice Heater NOT Repairable by OwnerHEATING- QUICK START & STOP 1.Verify Electrical Power is Present at Heater4.Program Filter Pump Run Time HEATING-QUICKSTART & STOPcontinued3.To Begin Heating 5.Continuous Usage and Water Around HeaterControl Buttons, Indicator Lights, & Display HEATER CONTROLSControl Panel Layout HEATER CONTROLS...continued Operational & Programming Codes1.Applying Power to The Controller Start Up & Setting Operating ControlsOwner-LevelProgramming Instructions Complete HEATER CONTROLS...continuedHEATER CONTROLS...continued Start Up & Setting Operating Controls4. Selecting Pool/Spa Thermostat Settings Owner-LevelProgramming Instructions...continuedOwner-LevelProgramming Instructions...continued Start Up & Setting Operating ControlsHEATER CONTROLS...continued B.De-Activatingthe User Lock Code ULC functionOwner-LevelProgramming Instructions...continued Start Up & Setting Operating ControlsHEATER CONTROLS...continued 9.Selecting Call-FlexPump Options CFOSafety During Cleaning Operations MAINTENANCEGeneral Maintenance OPERATIONAL RECOMMENDATIONSControl Water Chemistry MAINTENANCE& OPERATIONcontinuedMaintain Proper Water Flow RECOMMENDED WATER CHEMISTRY STANDARDSMAINTENANCE& OPERATIONcontinued Control Irrigation and Storm Run OffMaintain Proper Clearances Around Heater 100 & 120 MODELS 1- FTPool/Spa Blankets MAINTENANCE& OPERATIONcontinued Heating TipsHeating in Cooler Weather Pool and Spa Combination HeatingCalculating Initial Heating Time MAINTENANCE& OPERATIONcontinuedSurvival of Your Heater Follows Seasonal Use & Shut DownInformation Critical to the During the Swim SeasonLOCATION OF EXTERNAL DRAIN PLUG Winterizing ProcedureMAINTENANCE& OPERATIONcontinued AquaCal Customer Support at Planned Maintenance ProgramMAINTENANCE& OPERATIONcontinued Heat Pump Running but Not Heating TROUBLESHOOTINGHeat Pump Fails to Operate Water Coming from the Heat PumpProblem Problem Solved Solved TROUBLESHOOTING FLOWCHARTHeat Pump Fails to Operate STARTProblem Problem Solved Solved Heat Pump Running but Not HeatingTROUBLESHOOTING FLOWCHART Problem Problem Solved SolvedProblem Problem Solved Solved Water Coming from Heat PumpTROUBLESHOOTING FLOWCHART TESTINGPage SPECIFICDEALERINFORMATION FOLLOWS Installation SpecificationsControls Configuration Models 100DEALER-SPECIFICTABLE of CONTENTS Electrical Requirements DEALER-SPECIFICTABLE of CONTENTSCONTINUED Refrigerant Circuit Service Only by DATA PLATE NOMENCLATURESAFETY INFORMATION Notice Heater NOT Repairable by Owner100 & 120 MODELS 155 MODELS SPECIFICATIONSPhysical Characteristics 100 - Heating Only Models Performance/Size/WeightWater/ElectricalRequirements 100 - Heat & Cool Models Reversing120AHDE 120 - Heating Only Models120 - Heat & Cool Models Reversing 120BHDE155AHDE 155 - Heating Only Models155 - Heat & Cool Models Reversing 155BHDEIndoorInstallation INSTALLATIONPlacement of Heater OutdoorInstallationEquipment Mounting Pad Requirements INSTALLATION- PLACEMENT OF HEATERcontinued Anchoring Heater to PadParts and Materials Plumbing RequirementsOverview In-LineChlorine FeedersPlumbing Schematic-FlowExceeding 70-GPM INSTALLATIONPlumbing Requirements Plumbing Schematics-Flow20 to 70-GPMINSTALLATION Plumbing Schematics-Flow20 to 70-GPMWater IN & OUT Connections- Typical Plumbing RequirementsGeneral Requirements Connecting External ControllersElectrical Requirements Code-SpecificRequirementsElectrical Requirements continued Sizing the Electrical ServiceAWord Concerning Ground-FaultProtection Reference the Equipment Data Plate1.Entering Service Menu Controls Configuration & AdjustmentsLevel-2 Dealer-ServiceMicroprocessor Programming 3.Configuring for External Controllers JAO or FS2 Controls Configuration & AdjustmentsLevel-2Microprocessor Programming...continued Perform calibration procedure as follows4. Water Sensor Calibration...continued Controls Configuration & AdjustmentsLevel-2Microprocessor Programming...continued 5. Defrost Sensor Calibration dSC5.Defrost Sensor Calibration...continued Controls Configuration & AdjustmentsLevel-2Microprocessor Programming...continued 6.Spa Dead Band Differential dBS7.Pool Dead Band Differential...continued Controls Configuration & AdjustmentsLevel-2Microprocessor Programming...continued Controls Configuration & Adjustments Microprocessor Level-2Set Up & Calibration CodesMicroprocessor Factory Default Settings Service Adjustable ParametersInterpreting Error Codes Troubleshooting Using Displayed CodesControls Configuration & Adjustments Mode Jumper Explained Microprocessor Mode Jumper PositioningControls Configuration & Adjustments Verifying the Mode Jumper Position is CorrectControls Configuration & Adjustments DEFROST CYCLE HEAT ONLY UNITS Controls Configuration & AdjustmentsDefrost Systems- Described DEFROST CYCLE HEAT & COOL UNITSLocate Water Pressure Switch and Identify Type Water Flow Pressure Switch AdjustmentControls Configuration & Adjustments To Adjust a “Len Gordon” SwitchP-2,Len Gordon Style Switch P-1,WPS Location Water Flow Pressure Switch Adjustment...continuedControls Configuration & Adjustments P-3,TecMark Style SwitchCONTACTING THE FACTORY What We Need to Know When You Call UsInstallation Date ModelPage 2737 24th St. North St. Petersburg, FL