Electrical Requirements

INSTALLATION

Electrical Requirements

WARNING!

Failure to heed the following may result in permanent injury or death.

Installation made by unqualified persons can result in hazards to the installer and others. The information contained in this Electrical Installation section is intended for use by qualified electrical installation technicians, familiar with electrical service industry safety standards and methods. Electrical installation to be performed by qualified individuals only.

General Requirements

Locate the equipment disconnect means within 3-feet of the heater’s electrical enclosure, or as close to the heater as possible. Always satisfy applicable codes and standards.

AquaCal heat pumps are designed for copper conductors, only.

In sizing power wiring, be especially aware of up-sizing requirements necessary due to wiring distances. Always satisfy applicable codes and standards.

Multiple heaters installed at same site generally require special sequencing controls (an “ASC” controller will be required). If yours is a multi-heater installation, contact AquaCal Technical Support Group (800-786-7751) for application assistance.

Electrical installation should be by licensed electrician only.

Code-Specific Requirements

The electrical installation must conform to the most current version of the National Electrical Code, NFPA No.70, and all applicable local and state codes.

National Electrical Code, Article 680; Swimming Pools, Fountains, and Similar Installations, shall apply.

National Electrical Code, Article 440, Air-Conditioning and Refrigeration Equipment, shall apply.

Connecting External Controllers

See document entitled: “Connecting External Controllers to AquaCal Heat Pumps”; This document is shipped with every AquaCal heater. For extra copies, contact AquaCal Customer Support (800-786-7751); request literature piece: “LTP0050.”

For Call-Flex option, reference instructions received with the Call-Flex kit.

Please contact the AquaCal Technical Support Group (800-786-7751) concerning the application of any external controller, Call-Flex, sequencing control, etc.

44

Image 44
Contents Models Installation GuideATTENTION INSTALLER 100Page TABLE OF CONTENTS CONTINUED TABLE OF CONTENTSefficient than gas, and, when compared AquaCal’s factory-trainedservice staff isWelcome Tto theImportant Features of Your New Heat Pump ThermoLink Heat ExchangerScroll Compressor Digital ControllerHOW A HEAT PUMP WORKS A Heat Pump Does Not Make Heat…NTERS HEATSAFETY INFORMATION Refrigerant Circuit Service Only by Water Temperature SafetyWater Chemistry Safety Notice Heater NOT Repairable by OwnerHEATING- QUICK START & STOP 1.Verify Electrical Power is Present at HeaterHEATING-QUICKSTART & STOPcontinued 3.To Begin Heating4.Program Filter Pump Run Time 5.Continuous Usage and Water Around HeaterControl Buttons, Indicator Lights, & Display HEATER CONTROLSControl Panel Layout HEATER CONTROLS...continued Operational & Programming CodesStart Up & Setting Operating Controls Owner-LevelProgramming Instructions Complete1.Applying Power to The Controller HEATER CONTROLS...continuedStart Up & Setting Operating Controls 4. Selecting Pool/Spa Thermostat SettingsHEATER CONTROLS...continued Owner-LevelProgramming Instructions...continuedStart Up & Setting Operating Controls HEATER CONTROLS...continuedOwner-LevelProgramming Instructions...continued B.De-Activatingthe User Lock Code ULC functionStart Up & Setting Operating Controls HEATER CONTROLS...continuedOwner-LevelProgramming Instructions...continued 9.Selecting Call-FlexPump Options CFOMAINTENANCE General MaintenanceSafety During Cleaning Operations OPERATIONAL RECOMMENDATIONSMAINTENANCE& OPERATIONcontinued Maintain Proper Water FlowControl Water Chemistry RECOMMENDED WATER CHEMISTRY STANDARDSControl Irrigation and Storm Run Off Maintain Proper Clearances Around HeaterMAINTENANCE& OPERATIONcontinued 100 & 120 MODELS 1- FTMAINTENANCE& OPERATIONcontinued Heating Tips Heating in Cooler WeatherPool/Spa Blankets Pool and Spa Combination HeatingCalculating Initial Heating Time MAINTENANCE& OPERATIONcontinuedSeasonal Use & Shut Down Information Critical to theSurvival of Your Heater Follows During the Swim SeasonLOCATION OF EXTERNAL DRAIN PLUG Winterizing ProcedureMAINTENANCE& OPERATIONcontinued AquaCal Customer Support at Planned Maintenance ProgramMAINTENANCE& OPERATIONcontinued TROUBLESHOOTING Heat Pump Fails to OperateHeat Pump Running but Not Heating Water Coming from the Heat PumpTROUBLESHOOTING FLOWCHART Heat Pump Fails to OperateProblem Problem Solved Solved STARTHeat Pump Running but Not Heating TROUBLESHOOTING FLOWCHARTProblem Problem Solved Solved Problem Problem Solved SolvedWater Coming from Heat Pump TROUBLESHOOTING FLOWCHARTProblem Problem Solved Solved TESTINGPage Installation Specifications Controls ConfigurationSPECIFICDEALERINFORMATION FOLLOWS Models 100DEALER-SPECIFICTABLE of CONTENTS Electrical Requirements DEALER-SPECIFICTABLE of CONTENTSCONTINUED DATA PLATE NOMENCLATURE SAFETY INFORMATIONRefrigerant Circuit Service Only by Notice Heater NOT Repairable by Owner100 & 120 MODELS 155 MODELS SPECIFICATIONSPhysical Characteristics Performance/Size/Weight Water/ElectricalRequirements100 - Heating Only Models 100 - Heat & Cool Models Reversing120 - Heating Only Models 120 - Heat & Cool Models Reversing120AHDE 120BHDE155 - Heating Only Models 155 - Heat & Cool Models Reversing155AHDE 155BHDEINSTALLATION Placement of HeaterIndoorInstallation OutdoorInstallationINSTALLATION- PLACEMENT OF HEATER continuedEquipment Mounting Pad Requirements Anchoring Heater to PadPlumbing Requirements OverviewParts and Materials In-LineChlorine FeedersINSTALLATION Plumbing RequirementsPlumbing Schematic-FlowExceeding 70-GPM Plumbing Schematics-Flow20 to 70-GPMPlumbing Schematics-Flow20 to 70-GPM Water IN & OUT Connections- TypicalINSTALLATION Plumbing RequirementsConnecting External Controllers Electrical RequirementsGeneral Requirements Code-SpecificRequirementsSizing the Electrical Service AWord Concerning Ground-FaultProtectionElectrical Requirements continued Reference the Equipment Data Plate1.Entering Service Menu Controls Configuration & AdjustmentsLevel-2 Dealer-ServiceMicroprocessor Programming Controls Configuration & Adjustments Level-2Microprocessor Programming...continued3.Configuring for External Controllers JAO or FS2 Perform calibration procedure as followsControls Configuration & Adjustments Level-2Microprocessor Programming...continued4. Water Sensor Calibration...continued 5. Defrost Sensor Calibration dSCControls Configuration & Adjustments Level-2Microprocessor Programming...continued5.Defrost Sensor Calibration...continued 6.Spa Dead Band Differential dBS7.Pool Dead Band Differential...continued Controls Configuration & AdjustmentsLevel-2Microprocessor Programming...continued Microprocessor Level-2Set Up & Calibration Codes Microprocessor Factory Default SettingsControls Configuration & Adjustments Service Adjustable ParametersInterpreting Error Codes Troubleshooting Using Displayed CodesControls Configuration & Adjustments Microprocessor Mode Jumper Positioning Controls Configuration & AdjustmentsMode Jumper Explained Verifying the Mode Jumper Position is CorrectControls Configuration & Adjustments Controls Configuration & Adjustments Defrost Systems- DescribedDEFROST CYCLE HEAT ONLY UNITS DEFROST CYCLE HEAT & COOL UNITSWater Flow Pressure Switch Adjustment Controls Configuration & AdjustmentsLocate Water Pressure Switch and Identify Type To Adjust a “Len Gordon” SwitchWater Flow Pressure Switch Adjustment...continued Controls Configuration & AdjustmentsP-2,Len Gordon Style Switch P-1,WPS Location P-3,TecMark Style SwitchWhat We Need to Know When You Call Us Installation DateCONTACTING THE FACTORY ModelPage 2737 24th St. North St. Petersburg, FL