Water Flow (Pressure) Switch Adjustment

Locate Water Pressure Switch and Identify Type: Controls Configuration & Adjustments...

Water Flow (Pressure) Switch Adjustment

Occasionally, plumbing system design features will create a situation whereas the heater will abnormally cycle on the water flow circuit. This situation will be evident if the circulator pump is operating, the filter is clean, and all water valves are set to flow water through the heater– but the error code: “FLO” remains displayed (or displays intermittently). In these rare instances where the factory water pressure switch (WPS) setting will not satisfy site conditions, a WPS adjustment, to enable normal heater operation, is possible.

WARNING !

Failure to heed the following may result in permanent injury

or death.

 

 

WPS adjustment procedure to be performed by experienced service personnel only; procedure is NOT a homeowner-based task, and must not be attempted by individuals lacking adequate electrical and mechanical experience. BEWARE: ROTATING FAN PROP HAZARD: fan may start during water switch adjustment. Keep hands clear of fan blade at all times.

Locate Water Pressure Switch and Identify Type:

1. Before proceeding with switch adjustment, be absolutely certain the heater is receiving correct water flow. Leave circulation pump operating during water pressure switch (WPS) adjustment process.

2.Remove heater front cover and locate the water pressure switch. The switch will be found attached outside of the electrical enclosure, at lower edge; exact location will vary by heater model (see photo P-1, on following page).

3.AquaCal heat pumps may come equipped with either of two (2) water pressure switches: “Len Gordon” or “TecMark” brand (see photos P-2 and P-3, on following page, to determine which brand pressure switch is installed). The adjustment procedures differ slightly between the two brands.

To Adjust a “Len Gordon” Switch:

1.Locate the black, rectangular plastic tab, located on the forward-facing side of the switch (reference P-2 on page following). The black rectangle is a wheel lock tab; slide the tab fully LEFT to unlock the adjustment wheel.

2.With water pump operating, and electrical power supplied to the heater, slowly rotate the top of the adjustment wheel TOWARDS you until the FLO code (just) disappears. WARNING: watch for rotating fan blade; depending upon the state of the control circuit time delay, the heater may start simultaneous with the WPS adjustment.

3.Once the adjustment has been completed, slide the wheel locking tab fully back to the right- hand, locked position.

To Adjust a “TecMark” Switch:

1.(Reference photo P-3 on page following.) TecMark switches do not have an adjustment wheel lock.

2.With water pump operating, and electrical power supplied to the heater, slowly rotate the top of the adjustment wheel AWAY from you until the until the FLO code (just) disappears. WARNING: watch for rotating fan blade; depending upon the state of the control circuit time delay, the heater may start simultaneous with the WPS adjustment.

56

Image 56
Contents Models Installation GuideATTENTION INSTALLER 100Page TABLE OF CONTENTS CONTINUED TABLE OF CONTENTSefficient than gas, and, when compared AquaCal’s factory-trainedservice staff isWelcome Tto theImportant Features of Your New Heat Pump ThermoLink Heat ExchangerScroll Compressor Digital ControllerHOW A HEAT PUMP WORKS A Heat Pump Does Not Make Heat…NTERS HEATSAFETY INFORMATION Refrigerant Circuit Service Only by Water Temperature SafetyWater Chemistry Safety Notice Heater NOT Repairable by OwnerHEATING- QUICK START & STOP 1.Verify Electrical Power is Present at HeaterHEATING-QUICKSTART & STOPcontinued 3.To Begin Heating4.Program Filter Pump Run Time 5.Continuous Usage and Water Around HeaterControl Buttons, Indicator Lights, & Display HEATER CONTROLSControl Panel Layout HEATER CONTROLS...continued Operational & Programming CodesStart Up & Setting Operating Controls Owner-LevelProgramming Instructions Complete1.Applying Power to The Controller HEATER CONTROLS...continuedStart Up & Setting Operating Controls 4. Selecting Pool/Spa Thermostat SettingsHEATER CONTROLS...continued Owner-LevelProgramming Instructions...continuedStart Up & Setting Operating Controls HEATER CONTROLS...continuedOwner-LevelProgramming Instructions...continued B.De-Activatingthe User Lock Code ULC functionStart Up & Setting Operating Controls HEATER CONTROLS...continuedOwner-LevelProgramming Instructions...continued 9.Selecting Call-FlexPump Options CFOMAINTENANCE General MaintenanceSafety During Cleaning Operations OPERATIONAL RECOMMENDATIONSMAINTENANCE& OPERATIONcontinued Maintain Proper Water FlowControl Water Chemistry RECOMMENDED WATER CHEMISTRY STANDARDSControl Irrigation and Storm Run Off Maintain Proper Clearances Around HeaterMAINTENANCE& OPERATIONcontinued 100 & 120 MODELS 1- FTMAINTENANCE& OPERATIONcontinued Heating Tips Heating in Cooler WeatherPool/Spa Blankets Pool and Spa Combination HeatingCalculating Initial Heating Time MAINTENANCE& OPERATIONcontinuedSeasonal Use & Shut Down Information Critical to theSurvival of Your Heater Follows During the Swim SeasonLOCATION OF EXTERNAL DRAIN PLUG Winterizing ProcedureMAINTENANCE& OPERATIONcontinued AquaCal Customer Support at Planned Maintenance ProgramMAINTENANCE& OPERATIONcontinued TROUBLESHOOTING Heat Pump Fails to OperateHeat Pump Running but Not Heating Water Coming from the Heat PumpTROUBLESHOOTING FLOWCHART Heat Pump Fails to OperateProblem Problem Solved Solved STARTHeat Pump Running but Not Heating TROUBLESHOOTING FLOWCHARTProblem Problem Solved Solved Problem Problem Solved SolvedWater Coming from Heat Pump TROUBLESHOOTING FLOWCHARTProblem Problem Solved Solved TESTINGPage Installation Specifications Controls ConfigurationSPECIFICDEALERINFORMATION FOLLOWS Models 100DEALER-SPECIFICTABLE of CONTENTS Electrical Requirements DEALER-SPECIFICTABLE of CONTENTSCONTINUED DATA PLATE NOMENCLATURE SAFETY INFORMATIONRefrigerant Circuit Service Only by Notice Heater NOT Repairable by Owner100 & 120 MODELS 155 MODELS SPECIFICATIONSPhysical Characteristics Performance/Size/Weight Water/ElectricalRequirements100 - Heating Only Models 100 - Heat & Cool Models Reversing120 - Heating Only Models 120 - Heat & Cool Models Reversing120AHDE 120BHDE155 - Heating Only Models 155 - Heat & Cool Models Reversing155AHDE 155BHDEINSTALLATION Placement of HeaterIndoorInstallation OutdoorInstallationINSTALLATION- PLACEMENT OF HEATER continuedEquipment Mounting Pad Requirements Anchoring Heater to PadPlumbing Requirements OverviewParts and Materials In-LineChlorine FeedersINSTALLATION Plumbing RequirementsPlumbing Schematic-FlowExceeding 70-GPM Plumbing Schematics-Flow20 to 70-GPMPlumbing Schematics-Flow20 to 70-GPM Water IN & OUT Connections- TypicalINSTALLATION Plumbing RequirementsConnecting External Controllers Electrical RequirementsGeneral Requirements Code-SpecificRequirementsSizing the Electrical Service AWord Concerning Ground-FaultProtectionElectrical Requirements continued Reference the Equipment Data Plate1.Entering Service Menu Controls Configuration & AdjustmentsLevel-2 Dealer-ServiceMicroprocessor Programming Controls Configuration & Adjustments Level-2Microprocessor Programming...continued3.Configuring for External Controllers JAO or FS2 Perform calibration procedure as followsControls Configuration & Adjustments Level-2Microprocessor Programming...continued4. Water Sensor Calibration...continued 5. Defrost Sensor Calibration dSCControls Configuration & Adjustments Level-2Microprocessor Programming...continued5.Defrost Sensor Calibration...continued 6.Spa Dead Band Differential dBS7.Pool Dead Band Differential...continued Controls Configuration & AdjustmentsLevel-2Microprocessor Programming...continued Microprocessor Level-2Set Up & Calibration Codes Microprocessor Factory Default SettingsControls Configuration & Adjustments Service Adjustable ParametersInterpreting Error Codes Troubleshooting Using Displayed CodesControls Configuration & Adjustments Microprocessor Mode Jumper Positioning Controls Configuration & AdjustmentsMode Jumper Explained Verifying the Mode Jumper Position is CorrectControls Configuration & Adjustments Controls Configuration & Adjustments Defrost Systems- DescribedDEFROST CYCLE HEAT ONLY UNITS DEFROST CYCLE HEAT & COOL UNITSWater Flow Pressure Switch Adjustment Controls Configuration & AdjustmentsLocate Water Pressure Switch and Identify Type To Adjust a “Len Gordon” SwitchWater Flow Pressure Switch Adjustment...continued Controls Configuration & AdjustmentsP-2,Len Gordon Style Switch P-1,WPS Location P-3,TecMark Style SwitchWhat We Need to Know When You Call Us Installation DateCONTACTING THE FACTORY ModelPage 2737 24th St. North St. Petersburg, FL