Aquacal 100 Controls Configuration & Adjustments, Level-2Microprocessor Programming...continued

Page 47

 Controls Configuration & Adjustments... Controls Configuration & Adjustments...

Level-2 Microprocessor Programming...continued:

2.Time Delay [dEL]:

A.With the [dEL] (4 minute time delay) code message displayed use the [UP] or [DOWN] arrow key to select either “1” to allow the time delay to remain active or “0” to deactivate the time delay. Not pressing depressing any buttons for 15 seconds will allow the controller to save the selection and return to the normal operating mode. Pressing the {POOL/SPA] key will also save the selection and step to the next menu parameter [JAO] (External Controller Interface).

B.CAUTION!!!: The time delay should only be deactivated for service convenience and must be reactivated prior to placing the heat pump back is service. Failure to reset the time delay feature could result in permanent damage to the heat pump compressor.

3.Configuring for External Controllers [JAO] or [FS2]:

A.Configuring for External Controllers Using [JAO] Selection :

1)Follow the steps 1a. through 1d. above to enter the service menu. Once [dEL] is displayed, press the [POOL/SPA] key until the display shows [JAO].

2)With the [JAO] (External Controller Interface) code message displayed, use the [UP] or [DOWN] arrow keys to select either “0” to disable the External Controller Interface, “2” to connect a thermostat type controller (2-wire connection), or “3,” to connect a thermostat selector type controller (3-wire connection).

B.Configuring Remote Flow Switch / Automatic Thermostat Switching Using [FS2] Selection:

1)Follow the steps 1a. through 1d. above to enter the service menu. Once [dEL] is displayed, press the [POOL/SPA] key until the display shows [FS2].

2)With the [FS2] (Remote Flow Switch / Automatic Thermostat Switching) code message displayed, use the [UP] or [DOWN] arrows to select either “0” to disable Remote Flow Switch / Automatic Thermostat Switching, “1” to enable Remote Flow Switch / Automatic Thermostat Switching.

NOTE: ALL FLOW SWITCH KITS PRODUCED BY AQUACAL ARE SHIPPED WITH FULL INSTALLATION AND PROGRAMMING INSTRUCTIONS. PLEASE CONTACT AQUACAL CUSTOMER SUPPORT (800-786- 7751) IF ADDITIONAL COPIES OF THESE INSTRUCTIONS ARE NEEDED.

4.Water Sensor Calibration [tSC]:

If it is believed the displayed pool or spa water temperature does not match the actual temperature, follow the steps below to verify and adjust the controller as necessary. Be certain to use an accurate thermometer:

A.With the circulating pump in operation, and water moving through the heater, use a reliable thermometer to measure the temperature of the pool or spa water. Be sure to measure the water temperature away from returns. The object is to accurately determine the temperature of the water entering the heater.

B.Once you have measure the water temperature, compare the result to the heater’s displayed water temperature. If the water temperatures are the same or within 1oF, no calibration is necessary. If the temperatures differ by 2 to 3oF, calibration is necessary…

Perform calibration procedure as follows:

(Continued on Next Page)

 

47

Image 47
Contents 100 ModelsInstallation Guide ATTENTION INSTALLERPage TABLE OF CONTENTS TABLE OF CONTENTS CONTINUEDTto the efficient than gas, and, when comparedAquaCal’s factory-trainedservice staff is WelcomeDigital Controller Important Features of Your New Heat PumpThermoLink Heat Exchanger Scroll CompressorHEAT HOW A HEAT PUMP WORKSA Heat Pump Does Not Make Heat… NTERSSAFETY INFORMATION Notice Heater NOT Repairable by Owner Refrigerant Circuit Service Only byWater Temperature Safety Water Chemistry Safety1.Verify Electrical Power is Present at Heater HEATING- QUICK START & STOP5.Continuous Usage and Water Around Heater HEATING-QUICKSTART & STOPcontinued3.To Begin Heating 4.Program Filter Pump Run TimeControl Buttons, Indicator Lights, & Display HEATER CONTROLSControl Panel Layout Operational & Programming Codes HEATER CONTROLS...continuedHEATER CONTROLS...continued Start Up & Setting Operating ControlsOwner-LevelProgramming Instructions Complete 1.Applying Power to The ControllerOwner-LevelProgramming Instructions...continued Start Up & Setting Operating Controls4. Selecting Pool/Spa Thermostat Settings HEATER CONTROLS...continuedB.De-Activatingthe User Lock Code ULC function Start Up & Setting Operating ControlsHEATER CONTROLS...continued Owner-LevelProgramming Instructions...continued9.Selecting Call-FlexPump Options CFO Start Up & Setting Operating ControlsHEATER CONTROLS...continued Owner-LevelProgramming Instructions...continuedOPERATIONAL RECOMMENDATIONS MAINTENANCEGeneral Maintenance Safety During Cleaning OperationsRECOMMENDED WATER CHEMISTRY STANDARDS MAINTENANCE& OPERATIONcontinuedMaintain Proper Water Flow Control Water Chemistry100 & 120 MODELS 1- FT Control Irrigation and Storm Run OffMaintain Proper Clearances Around Heater MAINTENANCE& OPERATIONcontinuedPool and Spa Combination Heating MAINTENANCE& OPERATIONcontinued Heating TipsHeating in Cooler Weather Pool/Spa BlanketsMAINTENANCE& OPERATIONcontinued Calculating Initial Heating TimeDuring the Swim Season Seasonal Use & Shut DownInformation Critical to the Survival of Your Heater FollowsLOCATION OF EXTERNAL DRAIN PLUG Winterizing ProcedureMAINTENANCE& OPERATIONcontinued AquaCal Customer Support at Planned Maintenance ProgramMAINTENANCE& OPERATIONcontinued Water Coming from the Heat Pump TROUBLESHOOTINGHeat Pump Fails to Operate Heat Pump Running but Not HeatingSTART TROUBLESHOOTING FLOWCHARTHeat Pump Fails to Operate Problem Problem Solved SolvedProblem Problem Solved Solved Heat Pump Running but Not HeatingTROUBLESHOOTING FLOWCHART Problem Problem Solved SolvedTESTING Water Coming from Heat PumpTROUBLESHOOTING FLOWCHART Problem Problem Solved SolvedPage Models 100 Installation SpecificationsControls Configuration SPECIFICDEALERINFORMATION FOLLOWSDEALER-SPECIFICTABLE of CONTENTS Electrical Requirements DEALER-SPECIFICTABLE of CONTENTSCONTINUED Notice Heater NOT Repairable by Owner DATA PLATE NOMENCLATURESAFETY INFORMATION Refrigerant Circuit Service Only by100 & 120 MODELS 155 MODELS SPECIFICATIONSPhysical Characteristics 100 - Heat & Cool Models Reversing Performance/Size/WeightWater/ElectricalRequirements 100 - Heating Only Models120BHDE 120 - Heating Only Models120 - Heat & Cool Models Reversing 120AHDE155BHDE 155 - Heating Only Models155 - Heat & Cool Models Reversing 155AHDEOutdoorInstallation INSTALLATIONPlacement of Heater IndoorInstallationAnchoring Heater to Pad INSTALLATION- PLACEMENT OF HEATERcontinued Equipment Mounting Pad RequirementsIn-LineChlorine Feeders Plumbing RequirementsOverview Parts and MaterialsPlumbing Schematics-Flow20 to 70-GPM INSTALLATIONPlumbing Requirements Plumbing Schematic-FlowExceeding 70-GPMPlumbing Requirements Plumbing Schematics-Flow20 to 70-GPMWater IN & OUT Connections- Typical INSTALLATIONCode-SpecificRequirements Connecting External ControllersElectrical Requirements General RequirementsReference the Equipment Data Plate Sizing the Electrical ServiceAWord Concerning Ground-FaultProtection Electrical Requirements continued1.Entering Service Menu Controls Configuration & AdjustmentsLevel-2 Dealer-ServiceMicroprocessor Programming Perform calibration procedure as follows Controls Configuration & AdjustmentsLevel-2Microprocessor Programming...continued 3.Configuring for External Controllers JAO or FS25. Defrost Sensor Calibration dSC Controls Configuration & AdjustmentsLevel-2Microprocessor Programming...continued 4. Water Sensor Calibration...continued6.Spa Dead Band Differential dBS Controls Configuration & AdjustmentsLevel-2Microprocessor Programming...continued 5.Defrost Sensor Calibration...continued7.Pool Dead Band Differential...continued Controls Configuration & AdjustmentsLevel-2Microprocessor Programming...continued Service Adjustable Parameters Microprocessor Level-2Set Up & Calibration CodesMicroprocessor Factory Default Settings Controls Configuration & AdjustmentsInterpreting Error Codes Troubleshooting Using Displayed CodesControls Configuration & Adjustments Verifying the Mode Jumper Position is Correct Microprocessor Mode Jumper PositioningControls Configuration & Adjustments Mode Jumper ExplainedControls Configuration & Adjustments DEFROST CYCLE HEAT & COOL UNITS Controls Configuration & AdjustmentsDefrost Systems- Described DEFROST CYCLE HEAT ONLY UNITSTo Adjust a “Len Gordon” Switch Water Flow Pressure Switch AdjustmentControls Configuration & Adjustments Locate Water Pressure Switch and Identify TypeP-3,TecMark Style Switch Water Flow Pressure Switch Adjustment...continuedControls Configuration & Adjustments P-2,Len Gordon Style Switch P-1,WPS LocationModel What We Need to Know When You Call UsInstallation Date CONTACTING THE FACTORYPage 2737 24th St. North St. Petersburg, FL