Simer Pumps 3307P, 3310P, 3305P owner manual Wiring Connections, Connection Procedure

Page 10

Electrical

10

Hazardous voltage. Can shock, burn, or kill. Connect ground wire before connecting power sup- ply wires. Use the wire size (including the ground wire) specified in the wiring chart. If possible, connect the pump to a separate branch circuit with no other appli- ances on it.

Explosion hazard. Do not ground to a gas

supply line.

WIRING CONNECTIONS

Fire hazard. Incorrect voltage can cause a fire or seriously damage the motor and voids the warran- ty. The supply voltage must be within ±10% of the motor nameplate voltage.

NOTICE: Dual-voltage motors are factory wired for 230 volts. If necessary, reconnect the motor for 115 volts, as shown. Do not alter the wiring in single voltage motors.

Install, ground, wire, and maintain your pump in compli- ance with the National Electrical Code (NEC) or the Canadian Electrical Code (CEC), as applicable, and with all local codes and ordinances that apply. Consult your local building inspector for code information.

Connection Procedure:

Step 1. Connect the ground wire first as shown in Figure

14.The ground wire must be a solid copper wire at least as large as the power supply wires.

Step 2. There must be a solid metal connection between the pressure switch and the motor for motor grounding protection. If the pressure switch is not connected to the motor, connect the green ground screw in the switch to the green ground screw under the motor end cover. Use a solid copper wire at least as large as the power supply wires.

Step 3. Connect the ground wire to a grounded lead in a service panel, to a metal underground water pipe, to a metal well casing at least ten feet (3M) long, or to a ground electrode provided by the power company or the hydro authority.

Step 4. Connect the power supply wires to the pressure switch as shown in Figure 14.

You have just completed the wiring for your pump. Please go to Page 11 or 12 for startup preparations.

Wiring Chart – Recommended Wire and Fuse Sizes

 

 

 

 

 

DISTANCE IN FEET FROM MOTOR TO SUPPLY

 

 

 

Max. Load

Branch Fuse

0 - 50

51 - 100

101 - 200

201 - 300

301 - 400

401 - 500

Motor HP

Volts

Amp

Rating Amp

 

 

 

 

 

 

 

 

 

 

 

AWG WIRE SIZE (mm2)

 

 

 

 

 

 

 

 

 

1/2

115

9.4

15

14 (2)

14 (2)

 

12 (3)

10

(5)

8 (7)

8 (7)

3/4

115/230

12.2/6.1

20/15

14/14 (2/2)

14/14 (2/2)

 

10/14 (5/2)

8/14

(7/2)

8/14 (7/2)

6/12 (9/3)

1

115/230

14.8/7.4

20/15

14/14 (2/2)

12/14 (3/2)

 

10/14(5/2)

8/12

(7/3)

8/12 (7/3)

6/12 (9/3)

For parts or assistance, call Simer Customer Service at 1-800-468-7867 /1-800-546-7867

Image 10
Contents Models 3305P, 3307P, 3310P Composer le 1 800 Llame alElectrical Safety SafetyRead and Follow Safety Instructions General SafetyTable of Contents Deep Well Replacing an Existing PumpShallow Well New Shallow Well Installation Cased Well INSTALLATION, 2 or Larger Casing FigureInstallation for Surface Water ScaleOr Larger Well Figure New Deep Well InstallationWell Figure PRE-CHARGE Tank Connection Figure Discharge Pipe and Pressure Tank ConnectionsStandard Tank Connection Figure Electrical Dial Type Voltage SelectorConnection Procedure Wiring ConnectionsWiring Chart Recommended Wire and Fuse Sizes Congratulations on a successful installation Preparing to Start the Pump Deep WellPreparing to Start the Pump Shallow Well Open Control ValveTroubleshooting Capacitor, hold insulated handle screwdriver by the HandleModel and HP Repair PartsPart 3305P 3307P 3310P Description 2HP 4HP Shallow Well Kit FP4875 or Shallow Well InstallationEjector Package Key Part Description NumberDouble Pipe Kit FP4800 or Deep Well InstallationSingle Pipe Kit FP4840 or Sécurité Concernant Lélectricité SécuritéLire Toutes CES Instructions ET LES Suivre Sécurité GénéraleTable des matières Garantie limitée SimerPuits Profonds Remplacement dune pompe existantePuits PEU Profonds Installation DE LA Installation sur un nouveau puits peu profondPointe Filtrante Figure Installation Dans LE CAS Deaux EN Surface Poser léjecteurInstallation sur un nouveau puits profond Puits DE 2 Pouces FigureBranchement SUR UN Réservoir Standard Figure Électricité Sélecteur de tension à cadranConnexions DES Fils Félicitations pour une installation réussie Préparations avant le démarrage de la pompe Puits profondOuvrir la vanne de réglage Diagnostic des pannes Symptômes Causes Probables Remèdes3305P 3307P 3310p Pièces de rechangeModèle et puissance en ch Désignation des piècesTrousse pour puits peu profonds FP4875 ou Installation dans un puits peu profondEnsemble éjecteur Désignation Numéro Réf Des piècesInstallation dans un puits profond Désignation NuméroSeguridad Electrica SeguridadLEA Y Siga LAS Instrucciones DE Seguridad Seguridad GeneralIndice de Contenido Garantía limitada de SimerPozo Profundo Reemplazo de una Bomba ExistentePozo Poco Profundo Instalación de un Pozo Nuevo de Poca Profundidad Instalacion DEL Punto DE Pozo FiguraInstalacion Para Agua Superficial Figura 8 Instale el EyectorPozo DE 4 Ó MAS Figura Instalación De Un Pozo Nuevo ProfundoPozo DE 2 Figura Conexión DE Tanque DE PRE- Carga Figura Conexión Para Tanque Estándar FiguraElectricidad Selector de tensión de tipo cuadranteÉléctricas y a Tierra Conexiones DE LOS CablesPreparación Para Arrancar La Bomba Pozo Profundo Felicidades por una instalación exitosaPreparación Para Arrancar La Bomba Pozo Poco Profundo Solución de Problemas Síntoma Causas Probables Acción CorrectivaModelo y HP Refacciones3305P 3307P 3310P Descripción de la Parte Instalación en pozos poco profundos Paquete eyectorDescripción Número de De la Parte Repuesto Instalación en pozos profundos Clave Descripción Número de De la Parte Repuesto