Plastic Cap
Yellow or black
On Some Models
ONLY
INLET
Dual Pressure Switch
58HDV
Vent Drain
& Clamps
Drain Tube
Corrugated
5/8″ (15.9mm) ID &
Clamps
VENT
IN | ON |
| OFF |
AIR FLOW
Relief Tube
Black Rubber
3/16″ 〈4.8mm) ID
2″ (50.8mm) |
|
PVC |
|
Coupling | EXHAUST |
|
Either: The PVC Drain Tee or a field supplied 2″ (50.8mm) PVC Tee
Single Pressure Switch Details
Tee Trap White PVC (loose parts bag)
Elbow Tubes (2) Black Rubber 1/2″ (12.7mm) ID & Clamps (loose parts bag)
SIDE VIEW
Rotate downward 5° to 10°
Barbed Coupling, 1/2″ (12.7mm) OD (loose parts bag)
Drain Line Vent Tee 3/4″ (18.1mm) PVC or 1/2″
(12.7mm) CPVC (Field sup- plied)
Drain Connector Black PVC 3/4″ (19.1mm) PVC X 1/2″
(12.7mm) CPVC (Loose parts bag)
NOTE:
Casing Grommet |
|
Black Rubber 5/ ″ (15.9mm) CPVC | |
8 |
|
(Loose parts bag) |
A07708
Fig. 13 - All Models Vent Through Right Side
All Models Vent through Right-Side (See Fig. 13)
Disconnect the black drain tube between the drain vent and the trap. Rotate the inducer 180° for a right side vent after loosening the four
(4)inducer attachment screws. Reinstall and retighten the inducer screws to 20 in. lb. (2.3Nm) torque.
Using the 1/2″ (12.7mm) OD barbed coupling in the loose parts bag connect together with the two short 1/2″ (12.7mm) ID elbow tubes and connect the lower discharge port of the vent drain to the trap. Secure all connections with clamps.
Install the vent pipe grommet into the casing
Cut an appropriate length of 2″ (50.8mm) PVC pipe long enough to exit the cabinet and connect the vent drain to either:
SA 2″ (50.8mm) PVC coupling fastened onto the drain tee
Install tee trap into bottom section of tee.
Remove knockout from the side of the furnace casing where drain tube will exit.
Install casing grommet black rubber [5/8″ (15.9mm) ID grommet - in loose parts bag]
Install the 1/2″ (12.7mm) CPVC street elbow on discharge of trap.
Install the black PVC tube connector [3/4″ (19.1mm) PVC x 1/2″ (12.7mm) CPVC from loose parts bag] as shown in the illustration above.
Cut the black drain tube [5/8″ (15.9mm) ID - in loose parts bag] to length to fit between trap and tube connector through grommet.
Clamp both ends of the drain tube using clamps provided.
Glue the CPVC street elbow to the trap using appropriate cleaner and solvent cement.
Connect the tee trap and the main drain line exiting the casing as shown in Fig. 13
NOTE: It is recommended that all PVC piping and fitting connections be fit up and inspected before final cementing. Both the internal trap and the external tee trap must be primed before operation. Verify all condensate drain connections are securely clamped. A coupling and clamps (in loose part bag) may be installed as shown for future servicing of the vent system.
20