Carrier 58HDV installation instructions Horizontal Right through Top See Fig

Page 25

Trap Connection “Clamp ears”

Single Pressure Switch Detail

Alternate Orientation

3/

(4.8mm) ID Rub-

Pointed OUT

 

16

ber Tube

 

 

AIR FLOW

Plastic Cap

 

 

Yellow or black

 

Coupling & Clamps

 

EXHAUST

Preassemble &

(Optional)

 

insert into furnace

 

 

 

 

 

 

Drain Tube Black

 

 

 

Rubber 1/2(12.7mm)

Vent Drain

 

 

ID & Clamps

& Clamps

 

 

 

 

Field

 

 

 

Supplied Tee

Relief Tube Black Rub-

WARNING

 

Add Cap and Clamp

 

ber 3/

(4.8mm) ID

 

 

 

16

 

 

 

Flexible Tubing Connector

 

 

3/ (4.8mm) OD (Loose

 

 

16

 

 

 

Parts Bag)

 

 

 

 

 

 

Tee Trap White PVC

Relief Tube Extension

 

(loose parts bag)

Black Rubber 3/

(4.8mm) ID

 

 

16

 

INLET

Cut to Fit (Loose Parts Bag)

 

 

 

 

OFF

 

 

 

ON

 

 

 

On Some Models

 

 

 

ONLY

 

 

Dual Pressure Switch

Barbed Coupling 1/ (12.7mm)

 

 

 

 

 

 

2

 

Drain Tube Corrugated 5/ (15.9mm) ID &

OD (Loose Parts Bag)

 

 

8

Drain Tube Black Rubber

 

Clamps Cut at straight section

 

 

 

1/ (12.7mm) ID & Clamps

 

 

 

2

 

 

 

Remove KO before

 

Leave room for clamp

Cut Here

mounting Trap

 

 

 

 

 

25--24--70b

Representative drawing only, some models may vary in appearance.

A07711

Fig. 18 - Horizontal Right through Top

58HDV

Horizontal Right through Top (See Fig. 18)

Disconnect the hoses from the trap assembly, and remove trap and trap mounting bracket from the blower compartment. Using cover plate and gasket provided in the loose parts bag, cover the hole from the burner compartment to the blower compartment and secure with screws.

Remove knockout from the side of the furnace casing where drain tube will exit.

Mount the trap externally to the bottom side of the unit using the two(2) screws provided in the location shown.

Cut the corrugated tube as shown in the illustration above. Connect the corrugated hose from the transition to the trap. Secure connections with clamps.

Connect the black 1/2(12.7mm) ID drain tube from the Vent Drain to the trap. If an extension is required, use the black 1/2(12.7mm) OD barbed coupling and the black 1/2(12.7mm) ID drain tube in the loose parts bag. Cut tube to length. Secure connections with clamps.

Connect the 3/16(4.8mm) ID relief tube to the middle port on the trap. If an extension is required, use the clear 3/16(4.8mm) OD flexible tubing connector and the black 3/16(4.8mm) ID relief tube in the loose parts bag. Cut tube to length.

Cut an appropriate length of 2(50.8mm) PVC pipe, fittings and extension pipe long enough to exit the cabinet and connect the vent drain to a standard field supplied 2(50.8mm) PVC tee

SA 2(50.8mm) PVC coupling fastened onto the drain tee Install tee trap into bottom section of tee and glue pipe.

Connect the tee trap and the main drain line exiting the casing as shown in Fig. 18.

NOTE: It is recommended that all PVC piping and fitting connections be fit up and inspected before final cementing. Both the external trap and the external tee trap must be primed before operation. Verify all condensate drain connections are securely clamped. A coupling and clamps (in loose part bag) may be installed as shown for future servicing of the vent system.

25

Image 25
Contents Installation Instructions Required Notice for Massachusetts Installations CUT Hazard Furnace Reliability HazardFIRE, EXPLOSION, and Asphyxiation Hazard Winter Shutdown Frozen Water Pipe HazardWater Damage to Property Hazard Installation Requirements Installation PositionsLocation and Clearances Carbon Monoxide Poisoning HazardHorizontal Furnace Installation Furnace Installation ConsiderationsCondensate Trap and Drain Lines LevelingDimensions and Clearances Knock Outs Air Openings and Connecting DuctsOutdoor Combustion Air Method Requirements Confined Space InstallationIndoor Combustion Air Unconfined Space Venting and Combustion Air Check Ventilation AirMake the Following Check Dual Certified Direct or Non- Direct Vent For Two Pipe Installation Direct VentContaminated Combustion Air Sizing Combustion Air and Vent Pipe Combustion Air and Vent Piping Insulation GuidelinesSingle Piping only Vent Termination ClearancesDirect Vent Termination Clearance Other than Direct Vent Termination Clearance Frozen and Burst Water Pipe Hazard Condensate Drain TrapOnly Upflow Installations Top Vent See FigSide View Upflow Installations Vent through Left-Side See FigPVC All Models Vent through Right-Side See FigExhaust Downflow Left-Side Vent and Trap See FigDownflow Right-Side Vent and Trap Downflow Right-Side Vent and Trap See FigExhaust Horizontal Left through Top See FigInlet Horizontal Left-Side Vent See FigHorizontal Right through Top Horizontal Right through Top See FigExhaust Horizontal Right-Side Vent See FigCombustion Air Pipe Connection Direct Vent Connecting Vent and Combustion Air PipingVent Pipe Connection Joining Pipe and Fittings Connecting Vent Pipes and TerminationHorizontal Termination Vertical Termination Using Exterior RisersVent Termination Shielding Multi Vent Termination ClearancesConcentric Vent and Combustion-Air Vertical & Horizontal Termination Concentric Vent TerminationCarbon Monoxide POISONING, Fire and Explosion Hazard 40,000, 50,000, 60,000, & 75,000 Btuh Furnaces Gas Supply Requirements Gas Piping RequirementsFire and Explosion Hazard Fire HazardTypical Gas Piping for Upflow Electrical Operation HazardPropane Conversion High Altitude Air Pressure SwitchGeneral Derating Rules Additional Propane Connection RequirementsElectrical SHOCK, Fire or Explosion Hazard Changing Orifices for High AltitudeFinal Gas Piping Check Power Supply WiringJunction Box J- Box Relocation Thermostat HeatingOptional Equipment CoolingFurnace Control Fuse Tap Select Interface BoardConnections InstallationSizing InsulationFilters Filter Installation using Filter RackAddition Of Air Conditioning Subbase for Combustible Floor Combustible Floor InstallationStartup Manifold Gas Pressure AdjustmentsGas Supply Pressure Natural Gas Input Rating Check Temperature Rise CheckMain Burner Flame Check Continuous- Fan using G Blower AdjustmentsHard Wired Continuous Fan Operation Changing Blower SpeedOn = OFF = High Cooling Y1 & Y/Y2 or Y/Y2 Request Low Cooling Y1 RequestContinuous Circulating Fan G Request Heating Request with Gas Shut Off Furnace Control Board Diagnostic Codes See FigWiring Diagram Thermostat Wiring Guide No Connection SINGLE-STAGE Thermostat TWO-STAGE Catalog No 58HDV---01SI