Carrier 58HDV Natural Gas Input Rating Check, Main Burner Flame Check, Temperature Rise Check

Page 43

1.With gas OFF, connect manometer to manifold pressure tap on the outlet of gas control valve. See Fig. 51Use a manometer with a 0 to 12 inches of water column range.

2.Turn gas ON. Operate the furnace on High Heat by using a jumper wire on the R to W1 & W2 thermostat connections on the furnace control board.

3.Remove manifold pressure adjustment screw cover on

furnace gas control valve. Turn adjusting screw counterclockwise to decrease the manifold pressure and clockwise to increase pressure. See Fig. 51

NOTE: Adjustment screw cover MUST be replaced on gas control valve before reading manifold pressure and operating furnace.

Regulator

Adjustment

Under Cap

 

HONEYWELL

 

HI

 

LO

 

ON

INLET

OFF

Pressure

OUTLET

Tap -- 1/8

Pressure

25--24--98a

Tap -- 1/8

A07792

Fig. 51 - Typical Gas Control Valve (Honeywell)

4.Set manifold pressure to value shown in Table 7,or Table 8.

5.Operate the furnace on Low Heat by using a jumper wire on the R to W1 thermostat connections on the furnace control board.

NOTE: The SW1 DIP switch #3 should be in the ON position to set the Low Heat manifold pressure. (See wiring diagram.)

6.Repeat steps 3 and 4 for Low Heat operation.

7.When the manifold pressures are properly set, replace the adjustment screw covers on the gas control valve.

8.Remove the jumper wires from the thermostat connections on the furnace control board. Remove manometer connection from manifold pressure tap, and replace plug in gas valve.

9.Return SW1 DIP switch #3 to previous setting.

10.Check for leaks at plug.

Natural Gas Input Rating Check

NOTE: The gas meter can be used to measure input to furnace. Rating is based on a natural gas BTU content of 1,000 BTU’s per cubic foot. Check with gas supplier for actual BTU content.

1.Turn OFF gas supply to all appliances and start furnace. Use jumper wire on R to W1 and W2 for High Heat.

2.Time how many seconds it takes the smallest dial on the gas meter to make one complete revolution. Refer to Example.

3.Repeat steps 1 and 2 with jumper wire on R to W1 for Low Heat.

NOTE: If meter uses a 2 cubic foot dial, divide results (seconds) by two.

NOTE: SW1 DIP switch #3 must be in ON position. (See Furnace Wiring Diagram). Return SW1 DIP switch #3 to previous setting after check.

Example (BTUH)

Natural Gas

 

No. of

Time Per

BTU Per

BTU Content

 

Seconds

Cubic Foot in

 

Hour

per cu. foot

 

Per Hour

Seconds

 

 

 

 

 

 

 

1,000

 

3,600

48

75,000

 

 

 

 

 

 

 

1,000 x 3,600 ÷ 48 = 75,000 BTUH

 

To Determine the appliance kW input rate from a .05m3 test dial that has been clocked at 80 seconds for one complete revolution.

 

Example (kW)

 

 

 

Number of

Number of

Size of test

 

 

 

seconds per

kW m3/h

 

 

seconds per

dial

 

 

complete

 

 

hour

(.05m3)

 

 

 

rotation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3,600

80

.05

2.25

 

 

 

 

 

 

 

 

 

3,600 ÷ 80 x .05

= 7.2 m3/h

 

 

 

2.25m3/h x 10.35 kWh/m3 = 23.28 kW

 

 

58HDV

 

23.28 x 3.412 = 79,431 BTU

 

 

 

4. Remove jumper wire from R to W1 and W2.

 

 

 

5. Relight all appliances and ensure all pilots are operating.

 

Main Burner Flame Check

Allow the furnace to run approximately 10 minutes then inspect the main burner and pilot flames. See Fig. 52.

Check for the following (Fig. 52:

Stable and blue flames. Dust may cause orange tips or wisps of yellow, but flames MUST NOT have solid, yellow tips.

Flames extending directly from burner into heat ex- changer.

Flames do NOT touch sides of heat exchanger.

If any problems with main burner flames are noted, it may be necessary to adjust gas pressures, or check for drafts.

Burner Face

A07734

Fig. 52 - Main Burner

NOTE: For Igniter location see Fig. 53.

 

 

 

21/16(52.4)

 

 

5/

16

(8)

1/

4

(6.4)

 

 

 

 

A07735

Fig. 53 - Igniter Location

Temperature Rise Check

The blower speed MUST be set to give the correct air temperature rise through the furnace as marked on the rating plate for both High Heat and Low Heat operation. Temperature rise is the difference between supply and return air temperatures.

43

Image 43
Contents Installation Instructions Required Notice for Massachusetts Installations CUT Hazard Furnace Reliability HazardFIRE, EXPLOSION, and Asphyxiation Hazard Winter Shutdown Frozen Water Pipe HazardWater Damage to Property Hazard Carbon Monoxide Poisoning Hazard Installation PositionsInstallation Requirements Location and ClearancesLeveling Furnace Installation ConsiderationsHorizontal Furnace Installation Condensate Trap and Drain LinesDimensions and Clearances Knock Outs Air Openings and Connecting DuctsOutdoor Combustion Air Method Requirements Confined Space InstallationIndoor Combustion Air Unconfined Space Venting and Combustion Air Check Ventilation AirMake the Following Check Dual Certified Direct or Non- Direct Vent For Two Pipe Installation Direct VentContaminated Combustion Air Sizing Combustion Air and Vent Pipe Combustion Air and Vent Piping Insulation GuidelinesSingle Piping only Vent Termination ClearancesDirect Vent Termination Clearance Other than Direct Vent Termination Clearance Frozen and Burst Water Pipe Hazard Condensate Drain TrapOnly Upflow Installations Top Vent See FigSide View Upflow Installations Vent through Left-Side See FigPVC All Models Vent through Right-Side See FigExhaust Downflow Left-Side Vent and Trap See FigDownflow Right-Side Vent and Trap Downflow Right-Side Vent and Trap See FigExhaust Horizontal Left through Top See FigInlet Horizontal Left-Side Vent See FigHorizontal Right through Top Horizontal Right through Top See FigExhaust Horizontal Right-Side Vent See FigCombustion Air Pipe Connection Direct Vent Connecting Vent and Combustion Air PipingVent Pipe Connection Joining Pipe and Fittings Connecting Vent Pipes and TerminationHorizontal Termination Multi Vent Termination Clearances Using Exterior RisersVertical Termination Vent Termination ShieldingConcentric Vent and Combustion-Air Vertical & Horizontal Termination Concentric Vent TerminationCarbon Monoxide POISONING, Fire and Explosion Hazard 40,000, 50,000, 60,000, & 75,000 Btuh Furnaces Fire Hazard Gas Piping RequirementsGas Supply Requirements Fire and Explosion HazardTypical Gas Piping for Upflow Electrical Operation HazardAdditional Propane Connection Requirements High Altitude Air Pressure SwitchPropane Conversion General Derating RulesElectrical SHOCK, Fire or Explosion Hazard Changing Orifices for High AltitudeThermostat Heating Power Supply WiringFinal Gas Piping Check Junction Box J- Box RelocationTap Select Interface Board CoolingOptional Equipment Furnace Control FuseInsulation InstallationConnections SizingFilters Filter Installation using Filter RackAddition Of Air Conditioning Subbase for Combustible Floor Combustible Floor InstallationStartup Manifold Gas Pressure AdjustmentsGas Supply Pressure Natural Gas Input Rating Check Temperature Rise CheckMain Burner Flame Check Changing Blower Speed Blower AdjustmentsContinuous- Fan using G Hard Wired Continuous Fan OperationOn = OFF = High Cooling Y1 & Y/Y2 or Y/Y2 Request Low Cooling Y1 RequestContinuous Circulating Fan G Request Heating Request with Gas Shut Off Furnace Control Board Diagnostic Codes See FigWiring Diagram Thermostat Wiring Guide No Connection SINGLE-STAGE Thermostat TWO-STAGE Catalog No 58HDV---01SI