58HDV
For
Heat anticipator setting will need to be measured if 24VAC humidifier is installed. Measure current in series from R to W1 at the thermostat. Be sure 24VAC humidifier is operating during this check. Allow furnace to operate for 2 minutes before recording the AC amperage reading. Set anticipator on thermostat to recorded value.
Thermostat location has an important effect on the operation of the furnace. Follow instructions included with thermostat for correct mounting and wiring.
Low voltage connections to furnace must be made on terminal board to furnace control board. (See Fig. 41)
Cooling
If
If
Optional Equipment
All wiring from furnace to optional equipment MUST conform to local codes or, in the absence of local codes with the latest edition of The National Electric Code, ANSI NFPA 70 and/or The Canadian Electric Code CSA C22.1. Install wiring in accordance with manufacturer’s instructions. The wiring MUST have a minimum temperature rating of 105° C.
Humidifier/Electronic Air Cleaner
The furnace is wired for humidifier and/or electronic air cleaner connection.
HUMIDIFIER - The HUM (24V) terminal is energized when the low pressure switch closes on a call for heat. The HUM (115V) is energized when the inducer is energized.
ELECTRONIC AIR CLEANER - EAC terminal is energized when there is a blower speed call, except it is NOT energized when blower operates in the
!CAUTION
REDUCED FURNACE LIFE HAZARD
Failure to follow this caution may result in reduced furnace life.
Do NOT exceed 115V/1.0 amp. maximum current load for both the EAC terminal and the HUM terminal combined.
Furnace Control Board
The furnace control board has a fixed blower ON delay of 30 seconds for High Heat calls and 45 seconds for Low Heat calls. The blower OFF timing is factory preset at 140 seconds. If desired, the fan OFF delay can be reset to obtain the longest delay times while still maintaining comfort levels. See “Furnace Wiring Diagram”.
Dehumidification
The furnace control board has a dehumidification feature which reduces cooling airflow by 20% when the DEHUM terminal (1/4” male quick connect) is energized by 24VAC and there is a cooling call. DEHUM may be operated by a thermostat dehumidify (24VAC for dehumidify) command or a dehumidistat (switch closes on call for dehumidification) with one terminal connected to (Y1 for
Furnace Control Fuse
The 24V circuit contains a
| 115V. 60 Hz. |
| ||
HOT | NEUT. | W |
| |
|
|
| ||
|
| BK | ||
|
| G |
| |
|
| Connection | ||
|
| Box |
| |
Ground |
| |||
|
|
| R | |
LowVoltage | C | |||
TerminalBoard | ||||
W2 | ||||
|
|
| ||
|
|
| W1 | |
|
|
| Y/Y2 | |
|
|
| G | |
W |
|
|
| |
R | G | SingleStage | ||
|
| Thermostat | ||
LowVoltage | R | |||
C | ||||
TerminalBoard | ||||
| ||||
|
|
| W2 | |
|
|
| W1 | |
|
|
| Y/Y2 | |
|
|
| G | |
W2 |
| TwoStage |
| |
R W1 |
| |||
Thermostat |
| |||
G |
|
|
|
Operatingvoltagerange*:127VACmax,104VACmin.
* Permissible limits of voltage at which unit will operate satisfactorily
A07779
Fig. 40 - Electrical Connections
Tap Select Interface Board
The Tap Select Interface Board is used with the Variable Speed motor. There are DIP switches (SW2) for continuous blower adjust, heating blower adjust, cooling blower adjust and cooling on/off delay profiles. There is a jumper (J1) for slight blower adjustment, increase (+)/no change (NOM)/decrease
The O terminal is available for use for Heat Pump applications, if desired.
The Y1 terminal (if a
38