Carrier 58HDV installation instructions Confined Space Installation, Requirements

Page 9

Confined Space Installation

a. One opening MUST commence within 12(304.8mm)

NOTE: A confined space is defined as an area with less than 50

of the floor and the second opening MUST commence

within 12(304.8mm) of the ceiling.

cubic feet (1.43M)per 1,000 BTUH (2.33 cm2/kW) input rating for

b. Size openings and ducts per Table 1.

all gas appliances installed in the area.

c. Horizontal duct openings require 1 square inch of free

Requirements

area per 2,000 BTUH (11 cm2/kW) of combined input

1. Provide the space with sufficient air for proper combustion

for all gas appliances in the space (see Table 1).

d. Vertical duct openings or openings directly

and ventilation of flue gases using horizontal or vertical

communicating with the outdoors require 1 square inch

ducts or openings.

of free area per 4,000 BTUH (5.5 cm2/kW) for

2. Fig. 6 illustrates how to provide combustion and ventilation

combined input of all gas appliances in the space (see

air. A minimum of two permanent openings, one inlet and

Table 1).

one outlet, are required.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

This installation NOT approved in Canada

Gas Vent

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Gable Vent

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Gas Vent

Ventilated Attic

 

 

 

 

 

 

Top Above Insulation

 

Gable Vent

 

 

 

 

Alternate Inlet Air (1)

 

 

 

 

 

 

Gas Vent

 

Outlet

Outlet

 

 

Ventilated Attic

 

Air (1)

Outlet Air (1)

Soffit Vent

 

Air (2)

Top Above Insulation

 

 

 

 

 

 

 

 

 

 

 

 

OutletAir (1)

Soffit Vent

Inlet

Inlet

 

 

Air (1)

 

 

 

 

 

Air (2)

 

 

 

 

 

 

 

 

 

Inlet

 

Minimum One Inlet and One Outlet Air Supply is Required

 

 

 

 

May be in any Combination Shown

 

 

Inlet

 

Air (2)

 

Inlet Air Opening Must be Within12of floor

 

Ventilated Crawl Space

 

 

 

 

 

 

 

Outlet Air Opening Must be Within12of ceiling

 

alternate Inlet Air (1)

Air (1)

 

 

 

 

 

 

 

 

(1) 1 Square Inch per 4000 BTUH

 

 

 

 

 

 

 

 

 

 

 

 

(2) 1 Square Inch per 2000 BTUH

 

 

 

 

 

 

 

A07704

Fig. 6 - Outside Air

(This is ONLY a guide. Subject to codes of country having jurisdiction).

58HDV

3.One opening MUST be within 12(304.8mm) of the floor and the second opening within 12(304.8mm) of the ceiling.

a.1 sq. in of free area per 3,000 BTUH (7 cm2/kW) for combined input of all gas appliances in the space (see Table 1) and

b.not less than the sum of the areas of all vent connectors in the space.

The opening shall commence within 12(304.8mm) of the top of the enclosure. Appliances shall have clearances of at least 1(25.4mm) from the sides and back and 6(152.4mm) from the front. The opening shall directly communicate with the outdoors or shall communicate through a vertical or horizontal duct to the outdoors or spaces (crawl or attic) that freely communicate with the outdoors.

4.Size openings and ducts per Table 1.

a.Indoor openings that comply with the Indoor Combustion Air Method below and

b.Outdoor openings located as required in the Outdoor Combustion Air Method above and

c.Outdoor openings sized as follows.

(1.) Calculate the Ratio of all Indoor Space volume divided by required volume for Indoor Combustion Air Method.

(2.) Outdoor opening size reduction Factor is 1 minus the Ratio in 1) above.

(3.) Minimum size of Outdoor openings shall be the size required in Outdoor Combustion Air Method above multiplied by reduction Factor.

5.Horizontal duct openings require 1 square inch of free area per 2,000 BTUH of combined input for all gas appliances in area (see Table 1).

6.Vertical duct openings or openings directly to outside require 1 square inch of free area per 4,000 BTUH (5.5 cm2/kW) for combined input of all gas appliances in area (see Table 1).

9

Image 9
Contents Installation Instructions Required Notice for Massachusetts Installations Furnace Reliability Hazard CUT HazardFIRE, EXPLOSION, and Asphyxiation Hazard Frozen Water Pipe Hazard Winter ShutdownWater Damage to Property Hazard Installation Requirements Installation PositionsLocation and Clearances Carbon Monoxide Poisoning HazardHorizontal Furnace Installation Furnace Installation ConsiderationsCondensate Trap and Drain Lines LevelingDimensions and Clearances Air Openings and Connecting Ducts Knock OutsOutdoor Combustion Air Method Requirements Confined Space InstallationIndoor Combustion Air Unconfined Space Ventilation Air Venting and Combustion Air CheckMake the Following Check For Two Pipe Installation Direct Vent Dual Certified Direct or Non- Direct VentContaminated Combustion Air Sizing Combustion Air and Vent Pipe Combustion Air and Vent Piping Insulation GuidelinesSingle Piping only Vent Termination ClearancesDirect Vent Termination Clearance Other than Direct Vent Termination Clearance Frozen and Burst Water Pipe Hazard Condensate Drain TrapOnly Upflow Installations Top Vent See FigSide View Upflow Installations Vent through Left-Side See FigPVC All Models Vent through Right-Side See FigExhaust Downflow Left-Side Vent and Trap See FigDownflow Right-Side Vent and Trap Downflow Right-Side Vent and Trap See FigExhaust Horizontal Left through Top See FigInlet Horizontal Left-Side Vent See FigHorizontal Right through Top Horizontal Right through Top See FigExhaust Horizontal Right-Side Vent See FigConnecting Vent and Combustion Air Piping Combustion Air Pipe Connection Direct VentVent Pipe Connection Connecting Vent Pipes and Termination Joining Pipe and FittingsHorizontal Termination Vertical Termination Using Exterior RisersVent Termination Shielding Multi Vent Termination ClearancesConcentric Vent and Combustion-Air Concentric Vent Termination Vertical & Horizontal TerminationCarbon Monoxide POISONING, Fire and Explosion Hazard 40,000, 50,000, 60,000, & 75,000 Btuh Furnaces Gas Supply Requirements Gas Piping RequirementsFire and Explosion Hazard Fire HazardTypical Gas Piping for Upflow Electrical Operation HazardPropane Conversion High Altitude Air Pressure SwitchGeneral Derating Rules Additional Propane Connection RequirementsElectrical SHOCK, Fire or Explosion Hazard Changing Orifices for High AltitudeFinal Gas Piping Check Power Supply WiringJunction Box J- Box Relocation Thermostat HeatingOptional Equipment CoolingFurnace Control Fuse Tap Select Interface BoardConnections InstallationSizing InsulationFilter Installation using Filter Rack FiltersAddition Of Air Conditioning Subbase for Combustible Floor Combustible Floor InstallationManifold Gas Pressure Adjustments StartupGas Supply Pressure Temperature Rise Check Natural Gas Input Rating CheckMain Burner Flame Check Continuous- Fan using G Blower AdjustmentsHard Wired Continuous Fan Operation Changing Blower SpeedOn = OFF = Low Cooling Y1 Request High Cooling Y1 & Y/Y2 or Y/Y2 RequestContinuous Circulating Fan G Request Heating Request with Gas Shut Off Furnace Control Board Diagnostic Codes See FigWiring Diagram Thermostat Wiring Guide No Connection SINGLE-STAGE Thermostat TWO-STAGE Catalog No 58HDV---01SI