Carrier 58HDV installation instructions Installation, Connections, Sizing, Insulation

Page 39

Dip Switch

See “Wiring

Diagram

for switch settings

24 VAC

HUM

FUSE

DEHUM

Diagnostic Light

115 VAC HUM

EAC

A07780

!WARNING

CARBON MONOXIDE POISONING HAZARD

Failure to follow this warning could result in personal injury or death.

Cool air passing over heat exchanger can cause condensate to form resulting in heat exchanger failure.

Connections

NOTE: Return air can enter through either side, both sides, the bottom or a side and the bottom. Return air can not enter through rear of the furnace. When the furnace is located in an area near or adjacent to the living area, the system should be carefully designed with returns to minimize noise transmission through the return grille. Any blower moving a high volume of air will produce audible noise which could be objectionable to when the unit is located very close to living areas. It is advisable to route the return

58HDV

Fig. 41 - Control Connections

DUCTWORK AND FILTER

!WARNING

CARBON MONOXIDE POISONING HAZARD

Failure to follow this warning could result in personal injury or death.

Do NOT draw return air from inside a closet or utility room where furnace is located. Return air duct MUST be sealed to furnace casing.

Installation

NOTE: Design and install the air distribution system to comply with Air Conditioning Contractors of America manuals and/or NFPA pamphlets 90A and 90B or other approved methods that conform to local codes and good trade practices.

1.When furnace supply ducts carry air outside furnace area, seal return air duct to furnace casing and terminate duct outside furnace space.

2.Install air conditioning cooling coil (evaporator) on outlet side of furnace.

3.For furnaces installed without a cooling coil, it is recommended that the outlet duct be provided with a removable access panel. This panel should be accessible when the furnace is installed so the exterior of the heat exchanger can be viewed for inspections. The access panel MUST be sealed to prevent leaks.

4.If separate evaporator and blower units are used, install good sealing dampers for air flow control. Chilled air going through the furnace could cause condensation and shorten the furnace life.

NOTE: Dampers (field supplied) can be either automatic or manual. Manually operated dampers MUST be equipped with a means to prevent furnace or air conditioning operation unless damper is in the full heat or cool position.

air ducts under the floor or through the attic.

1.For side connections using a 16x 25(406.4 x 635mm) filter, cut out the embossed area shown in Fig. 42. This will

provide a 141/2x 221/2(368.3 x 571.5mm) approximate opening.

A = 14 /2(368.3mm) Height of Cutout for 16x 25(406.4 x 635mm) Filter B = 221/2(571.5mm) Width of Cutout for 16x 25(406.4 x 635mm) Filter

B

Embossed Area on Side of Furnace

A

Furnace

Bottom

A07728

Fig. 42 - Side Return Air Cutout

NOTE: Furnaces with 5 TONS cooling capacity may require two(2) side returns or one side return with bottom return.

2.Bottom returns can be made by removing the knockout panel in the furnace base. Do NOT remove knock-out except for a bottom return.

3.Installation of locking-type dampers are recommended in all branches, or in individual ducts to balance system’s air flow.

4.Non-combustible, flexible duct connectors are recommended for return and supply connections to furnace.

5.If air return grille is located close to the fan inlet, install at least one, 90° air turn between fan and inlet grille to reduce noise.

NOTE: To further reduce noise, install acoustical air turning vanes and/or line the inside of duct with acoustical material.

Sizing

Existing or new ductwork MUST be sized to handle the correct amount of airflow for either heating only or heating and air conditioning.

Insulation

1.Insulate ductwork installed in attics or other areas exposed to outside temperatures with a minimum of 2(50.8mm) insulation and vapor barrier.

39

Image 39
Contents Installation Instructions Required Notice for Massachusetts Installations Furnace Reliability Hazard CUT HazardFIRE, EXPLOSION, and Asphyxiation Hazard Frozen Water Pipe Hazard Winter ShutdownWater Damage to Property Hazard Carbon Monoxide Poisoning Hazard Installation PositionsInstallation Requirements Location and ClearancesLeveling Furnace Installation ConsiderationsHorizontal Furnace Installation Condensate Trap and Drain LinesDimensions and Clearances Air Openings and Connecting Ducts Knock OutsOutdoor Combustion Air Method Requirements Confined Space InstallationIndoor Combustion Air Unconfined Space Ventilation Air Venting and Combustion Air CheckMake the Following Check For Two Pipe Installation Direct Vent Dual Certified Direct or Non- Direct VentContaminated Combustion Air Sizing Combustion Air and Vent Pipe Combustion Air and Vent Piping Insulation GuidelinesSingle Piping only Vent Termination ClearancesDirect Vent Termination Clearance Other than Direct Vent Termination Clearance Frozen and Burst Water Pipe Hazard Condensate Drain TrapOnly Upflow Installations Top Vent See FigSide View Upflow Installations Vent through Left-Side See FigPVC All Models Vent through Right-Side See FigExhaust Downflow Left-Side Vent and Trap See FigDownflow Right-Side Vent and Trap Downflow Right-Side Vent and Trap See FigExhaust Horizontal Left through Top See FigInlet Horizontal Left-Side Vent See FigHorizontal Right through Top Horizontal Right through Top See FigExhaust Horizontal Right-Side Vent See FigConnecting Vent and Combustion Air Piping Combustion Air Pipe Connection Direct VentVent Pipe Connection Connecting Vent Pipes and Termination Joining Pipe and FittingsHorizontal Termination Multi Vent Termination Clearances Using Exterior RisersVertical Termination Vent Termination ShieldingConcentric Vent and Combustion-Air Concentric Vent Termination Vertical & Horizontal TerminationCarbon Monoxide POISONING, Fire and Explosion Hazard 40,000, 50,000, 60,000, & 75,000 Btuh Furnaces Fire Hazard Gas Piping RequirementsGas Supply Requirements Fire and Explosion HazardTypical Gas Piping for Upflow Electrical Operation HazardAdditional Propane Connection Requirements High Altitude Air Pressure SwitchPropane Conversion General Derating RulesElectrical SHOCK, Fire or Explosion Hazard Changing Orifices for High AltitudeThermostat Heating Power Supply WiringFinal Gas Piping Check Junction Box J- Box RelocationTap Select Interface Board CoolingOptional Equipment Furnace Control FuseInsulation InstallationConnections SizingFilter Installation using Filter Rack FiltersAddition Of Air Conditioning Subbase for Combustible Floor Combustible Floor InstallationManifold Gas Pressure Adjustments StartupGas Supply Pressure Temperature Rise Check Natural Gas Input Rating CheckMain Burner Flame Check Changing Blower Speed Blower AdjustmentsContinuous- Fan using G Hard Wired Continuous Fan OperationOn = OFF = Low Cooling Y1 Request High Cooling Y1 & Y/Y2 or Y/Y2 RequestContinuous Circulating Fan G Request Heating Request with Gas Shut Off Furnace Control Board Diagnostic Codes See FigWiring Diagram Thermostat Wiring Guide No Connection SINGLE-STAGE Thermostat TWO-STAGE Catalog No 58HDV---01SI