58HDV
Alternate Orientation
EXHAUST
Field
Supplied Tee
Tee Trap White PVC (loose parts bag)
INLET
On Some Models ONLY
Single Pressure Switch Detail
Yellow or black
Plastic Cap
Level or Sloped towards Tee
|
|
| Vent Drain |
|
| Dual Pressure Switch |
| & Clamps |
|
Relief Tube Black Rub- |
|
|
| |
ber | 3/ ″ (4.8mm) ID |
| Elbow Tube Black Rubber 1/ ″ (12.7mm) |
|
| 16 |
|
| |
|
|
| 2 |
|
|
| AIR FLOW | ID & Clamps (Loose Parts Bag) |
|
|
|
| Barbed Coupling 1/ ″ (12.7mm) OD |
|
|
|
| 2 |
|
|
|
| (Loose Parts Bag) |
|
| ON |
|
|
|
| OFF |
|
|
|
|
|
| Drain Tube Black Rubber |
|
|
|
| 1/ ″ (12.7mm) ID & Clamps |
|
|
|
| 2 |
|
|
|
| Drain Tube Corrugated |
|
|
|
| 5/ ″ (15.9mm) ID & Clamps |
|
| Flexible Tube Connector 3/ | ″ | 8 |
|
|
|
| ||
|
| 16 |
|
|
| (4.8mm) OD (Loose Parts Bag) |
|
| |
| Relief Tubing Extension |
| Cut at straight section | |
|
|
|
| |
| Black Rubber 3/ ″ (4.8mm) ID | WARNING |
| |
| 16 |
|
| |
| Cut to Fit (Loose Parts Bag) | Move Caps to |
| |
|
|
|
| |
|
|
| top of trap |
|
|
|
| Leave room for clamp | Cut Here |
Representative drawing only, some models may vary in appearance.
A07710
Fig. 17 - Horizontal Left-Side Vent
Horizontal Left-Side Vent (See Fig. 17)
Remove the drain tee from the Vent Drain if installed.
Rotate the inducer 180° for a side vent after loosening the 4 inducer attachment screws. Reinstall and retighten the inducer screws to 20 in. lbs. (2.3 Nm) torque.
Disconnect the hoses from the trap assembly, and remove trap and trap mounting bracket from the blower compartment. Using cover plate and gasket provided in the loose parts bag, cover the hole from the burner compartment to the blower compartment and secure with screws.
Remove knockout from the side of the furnace casing where drain tube will exit.
Mount the trap externally to the bottom side of the unit using the two screws provided in the location shown.
Cut the corrugated tube as shown in the illustration above. Connect the corrugated hose from the transition to the trap. Secure connections with clamps.
Connect the black 1/2″ (12.7mm) ID drain tube from the Vent Drain to the trap. If an extension is required, use the black 1/2″ (12.7mm) OD flexible tubing connector and the black 1/2″ (12.7mm) ID drain tube in the loose parts bag. Cut tube to length. Secure connections with clamps.
Connect the 3/16″ (4.8mm) ID relief tube to the middle port on the trap. If an extension is required, use the 3/16″ (4.8mm) OD flexible tubing connector and the black 3/16″ (4.8mm) ID relief tube in the loose parts bag. Cut tube to length.
Cut an appropriate length of 2″ (50.8mm) PVC pipe, fittings and extension pipe long enough to exit the cabinet and connect the vent drain to either:
SA 2″ (50.8mm) PVC coupling fastened onto the drain tee Install tee trap into bottom section of tee and glue pipe.
Important: The pipe to the tee trap must be level or sloping towards the tee trap
Connect the tee trap and the main drain line exiting the casing as shown in Fig. 17.
NOTE: It is recommended that all PVC piping and fitting connections be fit up and inspected before final cementing. Both the external trap and the external tee trap must be primed before operation. Verify all condensate drain connections are securely clamped. A coupling and clamps (in loose part bag) may be installed as shown for future servicing of the vent system.
24