Carrier 58HDV installation instructions 40,000, 50,000, 60,000, & 75,000 Btuh Furnaces

Page 32

58HDV

BPVC Vent/Exhaust

C

11/2

(38 mm)

B D PVC Intake/Combustion Air

A

Model

A*

B

C

D**

 

 

 

 

 

KGAVT0801CVT

387/8

3

41/2

211/8

KGAVT0701CVT

333/8

2

31/2

165/8

*= Dimension will change accordingly as dimension D is lengthened or shortened.

**= Dimension D may be lengthened to 60may also be shortened by cutting the pipes provided in the kit to 12minimum.

A09195

Fig. 33 - Concentric Vent Dimensional Drawing

Concentric Termination Kit

Table 5 KGAVT0701CVT & KGAVT0801CVT

Venting Table Dual Piping ONLY

40,000, 50,000, 60,000, & 75,000 Btuh Furnaces

KGAVT0701CVT - 35(10.7m) & (4) 90° elbows

with 2″ (50.8mm) PVC pipe

80,000, 100,000 & 125,000 Btuh Furnaces

KGAVT0801CVT - 35′ (10.7m) & (4) 90° elbows

with 3″ (76.2mm) PVC pipe

1.Do not include the field supplied 45° elbow in the total elbow count.

2.If more than four elbows are required, reduce the length of both the inlet and the exhaust pipes five feet for each additional elbow used.

3.Elbows are DWV long radius type for 2(50.8mm) and 3(76.2mm) vents.

If more than four elbows are required, reduce the length of both the inlet and exhaust pipes 5(1.5m)for each additional elbow used.

*Feet of pipe is whichever pipe run is the longest, either inlet or outlet side.

If assembly needs to be extended to meet height or side wall thickness requirement, the two pipes supplied in the kit may be replaced by using the same diameter solid, single (no coupling connections) field supplied SDR-26 PVC (ASTM D2241) pipes. Do not extend dimension D more than 60(1524mm). (See Fig. 33.)

Do not use field supplied couplings to extend the pipes. Airflow restriction will occur and the furnace pressure switch may cause intermittent operation.

5.Partially assemble the concentric vent termination kit. Clean and cement the parts using the procedures for Joining Pipe and Fittings section of the manual.

a.Cement the Y Concentric fitting to the longest of the two straight kit pipes. See Fig. 34.

b.Cement the rain cap to the shortest of the straight kit parts. (See Fig. 34.)

NOTE: A field supplied stainless steel screw may be used to secure the rain cap to the pipe instead of cementing when field disassembly is desired for cleaning (See Fig. 34.)

Drill clearance hole in rain cap and pilot hole in vent pipe.

Stainless steel screw (Field supplied)

A07722

Fig. 34 - Rain Cap to Vent Pipe Assembly

!WARNING

CARBON MONOXIDE POISONING HAZARD

Failure to follow this warning could result in personal injury or death.

When using the alternate screw assembly method, drill a clearance hole in the rain cap and a pilot hole in the vent pipe for the screw size being used. Failure to drill adequate holes may cause cracking of the PVC components, allowing flue gasses to be recirculated.

6.Install the Y concentric fitting and the pipe assembly through the structure’s hole. For vertical termination, install the parts through the field supplied roof boot/flashing. NOTE: Do not allow insulation or other materials to accumulate inside the pipe assembly when installing through the structure’s hole.

!WARNING

CARBON MONOXIDE POISONING HAZARD

Failure to follow this warning could result in personal injury or death.

Do not operate the furnace with the rain cap removed as recirculating of the flue gasses may occur. Water may also collect inside the larger combustion air pipe and flow to the burner enclosure.

7.Secure the assembly to the structure as shown in Fig. 32 or Fig. 36 using field supplied metal strapping or equivalent material.

NOTE: Ensure the termination height is above the roof surface or anticipated snow level as shown in Fig. 32 for vertical termination. Ensure the termination location clearance dimensions are as shown in Fig. 35 and Fig. 36 for horizontal termination.

8.Install the rain cap and the small diameter pipe assembly in the Y concentric fitting and the large pipe assembly. Ensure that the small diameter pipe is bottomed out and securely cemented in the Y concentric fitting.

9.Cement the furnace combustion air and vent pipes to the concentric vent termination assembly. See Fig. 32 or Fig. 36 for proper pipe attachment.

10.Operate the furnace through one heat cycle to ensure combustion air and vent pipes are properly connected to the concentric termination connections.

32

Image 32
Contents Installation Instructions Required Notice for Massachusetts Installations FIRE, EXPLOSION, and Asphyxiation Hazard Furnace Reliability HazardCUT Hazard Water Damage to Property Hazard Frozen Water Pipe HazardWinter Shutdown Installation Positions Installation RequirementsLocation and Clearances Carbon Monoxide Poisoning HazardFurnace Installation Considerations Horizontal Furnace InstallationCondensate Trap and Drain Lines LevelingDimensions and Clearances Outdoor Combustion Air Method Air Openings and Connecting DuctsKnock Outs Confined Space Installation RequirementsIndoor Combustion Air Unconfined Space Make the Following Check Ventilation AirVenting and Combustion Air Check Contaminated Combustion Air For Two Pipe Installation Direct VentDual Certified Direct or Non- Direct Vent Combustion Air and Vent Piping Insulation Guidelines Sizing Combustion Air and Vent PipeVent Termination Clearances Single Piping onlyDirect Vent Termination Clearance Other than Direct Vent Termination Clearance Condensate Drain Trap Frozen and Burst Water Pipe HazardUpflow Installations Top Vent See Fig OnlyUpflow Installations Vent through Left-Side See Fig Side ViewAll Models Vent through Right-Side See Fig PVCDownflow Left-Side Vent and Trap See Fig ExhaustDownflow Right-Side Vent and Trap See Fig Downflow Right-Side Vent and TrapHorizontal Left through Top See Fig ExhaustHorizontal Left-Side Vent See Fig InletHorizontal Right through Top See Fig Horizontal Right through TopHorizontal Right-Side Vent See Fig ExhaustVent Pipe Connection Connecting Vent and Combustion Air PipingCombustion Air Pipe Connection Direct Vent Horizontal Termination Connecting Vent Pipes and TerminationJoining Pipe and Fittings Using Exterior Risers Vertical TerminationVent Termination Shielding Multi Vent Termination ClearancesConcentric Vent and Combustion-Air Carbon Monoxide POISONING, Fire and Explosion Hazard Concentric Vent TerminationVertical & Horizontal Termination 40,000, 50,000, 60,000, & 75,000 Btuh Furnaces Gas Piping Requirements Gas Supply RequirementsFire and Explosion Hazard Fire HazardElectrical Operation Hazard Typical Gas Piping for UpflowHigh Altitude Air Pressure Switch Propane ConversionGeneral Derating Rules Additional Propane Connection RequirementsChanging Orifices for High Altitude Electrical SHOCK, Fire or Explosion HazardPower Supply Wiring Final Gas Piping CheckJunction Box J- Box Relocation Thermostat HeatingCooling Optional EquipmentFurnace Control Fuse Tap Select Interface BoardInstallation ConnectionsSizing InsulationAddition Of Air Conditioning Filter Installation using Filter RackFilters Combustible Floor Installation Subbase for Combustible FloorGas Supply Pressure Manifold Gas Pressure AdjustmentsStartup Main Burner Flame Check Temperature Rise CheckNatural Gas Input Rating Check Blower Adjustments Continuous- Fan using GHard Wired Continuous Fan Operation Changing Blower SpeedOn = OFF = Continuous Circulating Fan G Request Low Cooling Y1 RequestHigh Cooling Y1 & Y/Y2 or Y/Y2 Request Furnace Control Board Diagnostic Codes See Fig Heating Request with Gas Shut OffWiring Diagram Thermostat Wiring Guide No Connection SINGLE-STAGE Thermostat TWO-STAGE Catalog No 58HDV---01SI