Carrier 58HDV Upflow Installations Vent through Left-Side See Fig, Side View

Page 19

Plastic Cap

Yellow or black

 

INLET

On Some Models

(50.8mm) PVC

ONLY

2

 

 

Coupling

 

 

Coupling & Clamps (Optional)

Vent Drain

& Clamps

Either: The PVC

EXHAUST

 

 

Drain Tee or a field

 

VENT

supplied 2

 

IN

ON

(50.8mm) PVC Tee

 

 

 

 

 

 

OFF

Dual Pressure Switch Detail

 

 

 

AIR FLOW

 

 

 

Tee Trap White PVC

 

 

(loose parts bag)

 

 

Drain Tube

Black Rubber

1/2(12.7mm) ID

& Clamps Drain Tube

Corrugated

Single Pressure Switch

Relief Tube

Black Rubber 3/16

(4.8mm) ID

58HDV

Drain Connector Black PVC 3/4(19.1mm) PVC X 1/2

(12.7mm) CPVC (Loose parts bag)

Casing Grommet Black Rubber

5/8(15.9mm) ID (Loose parts bag)

5/8(15.9mm) ID

& Clamps

Drain Line Vent Tee 3/4(18.1mm) PVC or 1/2

(12.7mm) CPVC (Field supplied)

SIDE VIEW

Rotate downward 5° to 10°

NOTE: Built--in channel will be angled 5° to 10° also.

25--24--67a

Representative drawing only, some models may vary in appearance.

A07707

Fig. 12 - Upflow Installations Vent through Left Side

Upflow Installations Vent through Left-Side (See Fig. 12)

Remove drain tee from inducer discharge and remove black drain tube 1/2(12.7mm) ID from bottom of drain tee.

Install Vent Pipe grommet in side of casing.

Cut an appropriate length of 2(50.8mm) PVC pipe long enough to exit the cabinet and connect the vent drain to either:

SA 2(50.8mm) PVC coupling fastened onto the drain tee Install tee trap into bottom of tee.

Remove knockout from the side of the furnace casing where drain tube will exit.

Install the 1/2(12.7mm) CPVC street elbow on discharge of trap

Install the black PVC drain connector [3/4(19.1mm) PVC x 1/2CPVC from loose parts bag] as shown in the illustration above.

Cut the black drain tube [5/8(15.9mm) ID - in loose parts bag] to length to fit between trap and tube connector through grommet.

Clamp both ends of the drain tube using clamps provided.

Glue the CPVC street elbow to the trap using appropriate cleaner and solvent cement.

Connect the tee trap and the main drain line exiting the casing as shown in Fig. 12

Note: It is recommended that all PVC piping and fitting connections be fit up and inspected before final cementing. Both the internal trap and the external tee trap must be primed before operation. Verify all condensate drain connections are securely clamped. A coupling and clamps (in loose part bag) may be installed as shown for future servicing of the vent system.

19

Image 19
Contents Installation Instructions Required Notice for Massachusetts Installations CUT Hazard Furnace Reliability HazardFIRE, EXPLOSION, and Asphyxiation Hazard Winter Shutdown Frozen Water Pipe HazardWater Damage to Property Hazard Carbon Monoxide Poisoning Hazard Installation PositionsInstallation Requirements Location and ClearancesLeveling Furnace Installation ConsiderationsHorizontal Furnace Installation Condensate Trap and Drain LinesDimensions and Clearances Knock Outs Air Openings and Connecting DuctsOutdoor Combustion Air Method Requirements Confined Space InstallationIndoor Combustion Air Unconfined Space Venting and Combustion Air Check Ventilation AirMake the Following Check Dual Certified Direct or Non- Direct Vent For Two Pipe Installation Direct VentContaminated Combustion Air Sizing Combustion Air and Vent Pipe Combustion Air and Vent Piping Insulation GuidelinesSingle Piping only Vent Termination ClearancesDirect Vent Termination Clearance Other than Direct Vent Termination Clearance Frozen and Burst Water Pipe Hazard Condensate Drain TrapOnly Upflow Installations Top Vent See FigSide View Upflow Installations Vent through Left-Side See FigPVC All Models Vent through Right-Side See FigExhaust Downflow Left-Side Vent and Trap See FigDownflow Right-Side Vent and Trap Downflow Right-Side Vent and Trap See FigExhaust Horizontal Left through Top See FigInlet Horizontal Left-Side Vent See FigHorizontal Right through Top Horizontal Right through Top See FigExhaust Horizontal Right-Side Vent See FigCombustion Air Pipe Connection Direct Vent Connecting Vent and Combustion Air PipingVent Pipe Connection Joining Pipe and Fittings Connecting Vent Pipes and TerminationHorizontal Termination Multi Vent Termination Clearances Using Exterior RisersVertical Termination Vent Termination ShieldingConcentric Vent and Combustion-Air Vertical & Horizontal Termination Concentric Vent TerminationCarbon Monoxide POISONING, Fire and Explosion Hazard 40,000, 50,000, 60,000, & 75,000 Btuh Furnaces Fire Hazard Gas Piping RequirementsGas Supply Requirements Fire and Explosion HazardTypical Gas Piping for Upflow Electrical Operation HazardAdditional Propane Connection Requirements High Altitude Air Pressure SwitchPropane Conversion General Derating RulesElectrical SHOCK, Fire or Explosion Hazard Changing Orifices for High AltitudeThermostat Heating Power Supply WiringFinal Gas Piping Check Junction Box J- Box RelocationTap Select Interface Board CoolingOptional Equipment Furnace Control FuseInsulation InstallationConnections SizingFilters Filter Installation using Filter RackAddition Of Air Conditioning Subbase for Combustible Floor Combustible Floor InstallationStartup Manifold Gas Pressure AdjustmentsGas Supply Pressure Natural Gas Input Rating Check Temperature Rise CheckMain Burner Flame Check Changing Blower Speed Blower AdjustmentsContinuous- Fan using G Hard Wired Continuous Fan OperationOn = OFF = High Cooling Y1 & Y/Y2 or Y/Y2 Request Low Cooling Y1 RequestContinuous Circulating Fan G Request Heating Request with Gas Shut Off Furnace Control Board Diagnostic Codes See FigWiring Diagram Thermostat Wiring Guide No Connection SINGLE-STAGE Thermostat TWO-STAGE Catalog No 58HDV---01SI