Carrier 58HDV installation instructions Vent Termination Clearances, Single Piping only

Page 14

58HDV

Table 3

Pipe Diameter Table

Single Piping ONLY

 

40,000, 50,000, 60,000 & 75,000 Btuh Furnaces

40(12.2m) & (5) 90° elbows with 2″ (50.8mm) PVC pipe

80,000 & 100,000 Btuh Furnace

40(12.2m) & (5) 90° elbows with 3″ (76.2mm) PVC pipe

125,000 Btuh Furnace

40(12.2m) & (5) 90° elbows with 3″ (76.2mm) PVC pipe

The minimum vent length is 5’ (1.5m) of PVC. Elbows are DWV Long Radius Type for 2” (50.8mm) and 3” (76.2mm) vents.

If more than five elbows are required, reduce the length of both the inlet and exhaust pipes 5(1.5m) for each additional elbow used. If less than five elbow are required, the length can be INCREASED by 5(1.5m) for each additional elbow NOT used.

NOTE: It is allowable to use larger diameter pipe and fitting than shown in the tables but not smaller diameters than shown.

Table 4

Pipe Diameter Table

Dual Piping ONLY

 

40,000, 50,000, 60,000 & 75,000 Btuh Furnaces

40(12.2m) & (5) 90° elbows with 2″ (50.8mm) PVC pipe

80,000 & 100,000 Btuh Furnace

40′ (12.2m) & (5) 90° elbows with 3″ (76.2mm) PVC pipe

125,000 Btuh Furnace

40′ (12.2m) & (5) 90° elbows with 3″ (76.2mm) PVC pipe

The minimum vent length is 5’ (1.5m) of PVC. Elbows are DWV Long Radius Type for 2” (50.8mm) and 3” (76.2mm) vents.

If more than five elbows are required, reduce the length of both the inlet and exhaust pipes 5(1.5m) for each additional elbow used. If less than five elbow are required, the length can be INCREASED by 5(1.5m) for each additional elbow NOT used.

*Feet (M) of pipe is whichever pipe run is the longest, either inlet or outlet side.

For venting table, see“Concentric Termination Kit” in this manual.

Vent Termination Clearances

!WARNING

CARBON MONOXIDE POISONING HAZARD

Failure to follow this warning could result in personal injury or death.

Inlet and outlet pipes may NOT be vented directly above each other.

1.Determine termination locations based on clearances specified in following steps and as shown in Fig. 8, 9, and 22 through 30.

For “Concentric Termination Kit” clearances, see Fig. 32, 33, 34, 35 and 36 in this manual.

2.This furnace is Dual Certified and can be installed as a single pipe appliance (all combustion from inside the structure) or as a direct vent appliance where all combustion air is taken from outside the structure.

3.For Direct Vent installation, refer to Fig. 8 for vent termination.

4.For Single Pipe installation refer to Fig. 9 for vent termination clearances.

14

Image 14
Contents Installation Instructions Required Notice for Massachusetts Installations FIRE, EXPLOSION, and Asphyxiation Hazard Furnace Reliability HazardCUT Hazard Water Damage to Property Hazard Frozen Water Pipe HazardWinter Shutdown Location and Clearances Installation PositionsInstallation Requirements Carbon Monoxide Poisoning HazardCondensate Trap and Drain Lines Furnace Installation ConsiderationsHorizontal Furnace Installation LevelingDimensions and Clearances Outdoor Combustion Air Method Air Openings and Connecting DuctsKnock Outs Confined Space Installation RequirementsIndoor Combustion Air Unconfined Space Make the Following Check Ventilation AirVenting and Combustion Air Check Contaminated Combustion Air For Two Pipe Installation Direct VentDual Certified Direct or Non- Direct Vent Combustion Air and Vent Piping Insulation Guidelines Sizing Combustion Air and Vent PipeVent Termination Clearances Single Piping onlyDirect Vent Termination Clearance Other than Direct Vent Termination Clearance Condensate Drain Trap Frozen and Burst Water Pipe HazardUpflow Installations Top Vent See Fig OnlyUpflow Installations Vent through Left-Side See Fig Side ViewAll Models Vent through Right-Side See Fig PVCDownflow Left-Side Vent and Trap See Fig ExhaustDownflow Right-Side Vent and Trap See Fig Downflow Right-Side Vent and TrapHorizontal Left through Top See Fig ExhaustHorizontal Left-Side Vent See Fig InletHorizontal Right through Top See Fig Horizontal Right through TopHorizontal Right-Side Vent See Fig ExhaustVent Pipe Connection Connecting Vent and Combustion Air PipingCombustion Air Pipe Connection Direct Vent Horizontal Termination Connecting Vent Pipes and TerminationJoining Pipe and Fittings Vent Termination Shielding Using Exterior RisersVertical Termination Multi Vent Termination ClearancesConcentric Vent and Combustion-Air Carbon Monoxide POISONING, Fire and Explosion Hazard Concentric Vent TerminationVertical & Horizontal Termination 40,000, 50,000, 60,000, & 75,000 Btuh Furnaces Fire and Explosion Hazard Gas Piping RequirementsGas Supply Requirements Fire HazardElectrical Operation Hazard Typical Gas Piping for UpflowGeneral Derating Rules High Altitude Air Pressure SwitchPropane Conversion Additional Propane Connection RequirementsChanging Orifices for High Altitude Electrical SHOCK, Fire or Explosion HazardJunction Box J- Box Relocation Power Supply WiringFinal Gas Piping Check Thermostat HeatingFurnace Control Fuse CoolingOptional Equipment Tap Select Interface BoardSizing InstallationConnections InsulationAddition Of Air Conditioning Filter Installation using Filter RackFilters Combustible Floor Installation Subbase for Combustible FloorGas Supply Pressure Manifold Gas Pressure AdjustmentsStartup Main Burner Flame Check Temperature Rise CheckNatural Gas Input Rating Check Hard Wired Continuous Fan Operation Blower AdjustmentsContinuous- Fan using G Changing Blower SpeedOn = OFF = Continuous Circulating Fan G Request Low Cooling Y1 RequestHigh Cooling Y1 & Y/Y2 or Y/Y2 Request Furnace Control Board Diagnostic Codes See Fig Heating Request with Gas Shut OffWiring Diagram Thermostat Wiring Guide No Connection SINGLE-STAGE Thermostat TWO-STAGE Catalog No 58HDV---01SI