58HDV
2.Insulate ductwork in indoor unconditioned areas with a minimum of 1″ (25.4mm) insulation with indoor type vapor barrier.
Filters
A filter must be used:
Filters are supplied with these furnaces, and additional filters may be purchased from your distributor.
Use either filter type:
SWashable, high velocity filters are based on a maximum air flow rating of 600 FPM.
SDisposable, low velocity filters are based on a maximum air flow of 300 FPM when used with filter grille.
SSee Service & Maintenance Manual, Circulation Air Blower Data for additional data.
NOTE: Disposable, low velocity filters may be replaced with washable, high velocity filter providing they meet the minimum size areas. Washable, high velocity filters can be replaced ONLY with same type and size.
11/2″
(38.1)
3″(76.2)
| 11/4″ (31.8) |
26 Ga. Galvanized Steel | 11/16″ (27) |
FAST part number 1008482 |
A07730
Fig. 45 - Filter Clip Construction
Refer to Fig. 46 and for guidelines to install filters. Furnaces which require larger filter media and have limited clearances on one side of furnace, require a standoff filter rack, see Fig. 46, available from your distributor.
NOTE: If filters are only suitable for heating application, advise homeowner that filter size may need to be increased if air conditioning is added.
Using Optional
Standoff Filter
Rack
A07729
Fig. 43 - Side Mounted Filter Rack
Filter Installation using Filter Rack
When installing or removing a bottom mounted filter, slide the two side filter clips to the back of the furnace BEFORE installing or removing. This will allow the filter to clear the front raised edge of the furnace. Insert filter into side clips first and push filter back until it is fully engaged into back clip. When filter is in place, slide clips back into place midway on filter as shown in Fig. 44 or Fig. 45
Center Clip
9″ (152.4mm) |
|
|
Slide filter clips towards back before removing
A07691
Fig. 44 - Bottom Mounted Filter Rack
A07731
Fig. 46 - Standoff Filter Rack
Addition Of Air Conditioning
When a refrigeration coil is used in conjunction with this unit, it must be installed parallel with or on the discharge side of the unit to avoid condensation on the heat exchanger. All furnaces are designed with a
A 3″ clearance is required on the right side of the furnace in order to run the condensate drain line. Copper or plastic tubing may be used for the condensate drain line.
Downflow Furnace Installation Non- Combustible Floor Installation
Fabricate a plenum to the dimensions given in Fig. 47, for the furnace outlet. Plenum should be flanged, approximately 3/4″ (19.1mm) for support.
40