Carrier 58HDV Gas Piping Requirements, Gas Supply Requirements, Fire and Explosion Hazard

Page 33

Roof Overhang

12(304.8mm) min.

1(25.4mm) max.

Combustion

Air

Vent

Maintain 12(304.8mm) clearance above highest anticipated snow level or grade whichever is greater.

25--22--02

A07736

Fig. 35 - Concentric Vent and Combustion-Air

Side Termination

(See Propane Gas Conversion Kit instruction manual for furnaces converted to Propane gas)

SUse only the Type of gas approved for this furnace. See rating

plate for approved gas type.

SA 1/8NPT plugged tapping, accessible for a test gauge connection,must be installed immediately upstream of the gas

supply connection to furnace.

SGas supply pressure should be within minimum and maximum values listed on rating plate. Pressures are usually set by gas

suppliers.

SGas input must not exceed the rated input shown on the rating

plate. Overfiring will result in failure of heat exchanger and cause dangerous operation.

SDo not allow minimum supply pressure to vary downward. Doing so will decrease input to furnace. Refer to Table 6 for Gas supply. Refer to Tables 7 through 10 for manifold pressures.

58HDV

Strap

(Field Supplied)

Vent

Combustion

Air

Vent

Flush to

Table 6

Gas Type

Natural

Propane

Gas Pressures

 

 

 

 

 

 

Supply Pressure

 

Recommended

 

 

 

 

Max.

Min.

7 in wc

 

 

 

 

14 in wc

4.5 in wc

(1744 Pa)

 

(3487 Pa)

(1121 Pa)

11 in wc

 

 

 

 

14 in wc

11 in wc

(2740 Pa)

 

(3487 Pa)

(2740 Pa)

 

 

 

 

Combustion

Air45° Elbow

(Field Supplied)

1(25.4mm)

max.

25--22--02

Gas Piping Requirements

NOTE: The gas supply line must be installed by a qualified service technician in accordance with all building codes.

Note:

Securing strap must be field installed to prevent movement of termina- tion kit in side wall.

A07723

Fig. 36 - Concentric Vent Sidewall Attachment

GAS SUPPLY AND PIPING

!WARNING

FIRE AND EXPLOSION HAZARD

Failure to follow this warning could result in personal injury, death, and/or property damage.

Models designated for Natural Gas are to be used with Natural Gas ONLY, unless properly converted to use with Propane gas.

NOTE: The rating plate is stamped with the model number, gas type and gas input rating. In addition, models manufactured for sale in Canada have orifice size information stamped on the rating plate.

Gas Supply Requirements

!WARNING

FIRE HAZARD

Failure to follow this warning could result in personal injury or death.

Do NOT set input rating above that shown on rating plate.

Gas supply pressure should be within minimum and maximum values listed on rating plate. Pressures are usually set by gas suppliers.

NOTE: In the state of Massachusetts.

a.Gas supply connections MUST be performed by a licensed plumber or gas fitter.

b.When flexible connectors are used, the maximum length shall not exceed 36(915 mm).

c.When lever handle type manual equipment shutoff valves are used, they shall be T-handle valves.

d.The use of copper tubing for gas piping is NOT approved by the state of Massachusetts.

1.Install gas piping in accordance with local codes, or in the absence of local codes, the applicable national codes. Refer to NFPA 54/ANSI Z223.1 for proper gas pipe size.

2.It is recommended that a manual equipment shutoff valve be installed in the gas supply line outside the furnace. Locate valve as close to the furnace as possible where it is readily accessible. Refer to Fig. 37.

3.Use black iron or steel pipe and fittings or other pipe approved by local code.

4.Use pipe thread compound which is resistant to natural and Propane gases.

5.Use ground joint unions and install a drip leg no less than 3(76.2mm) long to trap dirt and moisture before it can enter gas controlvalve inside furnace.

6.Use two pipe wrenches when making connections to prevent gas valve from turning.

7.Install a manual shut-off valve external to furnace casing and tighten all joints securely.

8.If local codes allow the use of flexible gas appliance connectors, always use a new listed connector.

Do not use a connector which has previously serviced another gas appliance.

9.Flexible corrugated metal gas connector may NOT be used inside the furnace or be secured or supported by the furnace or ductwork.

33

Image 33
Contents Installation Instructions Required Notice for Massachusetts Installations Furnace Reliability Hazard CUT HazardFIRE, EXPLOSION, and Asphyxiation Hazard Frozen Water Pipe Hazard Winter ShutdownWater Damage to Property Hazard Installation Requirements Installation PositionsLocation and Clearances Carbon Monoxide Poisoning HazardHorizontal Furnace Installation Furnace Installation ConsiderationsCondensate Trap and Drain Lines LevelingDimensions and Clearances Air Openings and Connecting Ducts Knock OutsOutdoor Combustion Air Method Requirements Confined Space InstallationIndoor Combustion Air Unconfined Space Ventilation Air Venting and Combustion Air CheckMake the Following Check For Two Pipe Installation Direct Vent Dual Certified Direct or Non- Direct VentContaminated Combustion Air Sizing Combustion Air and Vent Pipe Combustion Air and Vent Piping Insulation GuidelinesSingle Piping only Vent Termination ClearancesDirect Vent Termination Clearance Other than Direct Vent Termination Clearance Frozen and Burst Water Pipe Hazard Condensate Drain TrapOnly Upflow Installations Top Vent See FigSide View Upflow Installations Vent through Left-Side See FigPVC All Models Vent through Right-Side See FigExhaust Downflow Left-Side Vent and Trap See FigDownflow Right-Side Vent and Trap Downflow Right-Side Vent and Trap See FigExhaust Horizontal Left through Top See FigInlet Horizontal Left-Side Vent See FigHorizontal Right through Top Horizontal Right through Top See FigExhaust Horizontal Right-Side Vent See FigConnecting Vent and Combustion Air Piping Combustion Air Pipe Connection Direct VentVent Pipe Connection Connecting Vent Pipes and Termination Joining Pipe and FittingsHorizontal Termination Vertical Termination Using Exterior RisersVent Termination Shielding Multi Vent Termination ClearancesConcentric Vent and Combustion-Air Concentric Vent Termination Vertical & Horizontal TerminationCarbon Monoxide POISONING, Fire and Explosion Hazard 40,000, 50,000, 60,000, & 75,000 Btuh Furnaces Gas Supply Requirements Gas Piping RequirementsFire and Explosion Hazard Fire HazardTypical Gas Piping for Upflow Electrical Operation HazardPropane Conversion High Altitude Air Pressure SwitchGeneral Derating Rules Additional Propane Connection RequirementsElectrical SHOCK, Fire or Explosion Hazard Changing Orifices for High AltitudeFinal Gas Piping Check Power Supply WiringJunction Box J- Box Relocation Thermostat HeatingOptional Equipment CoolingFurnace Control Fuse Tap Select Interface BoardConnections InstallationSizing InsulationFilter Installation using Filter Rack FiltersAddition Of Air Conditioning Subbase for Combustible Floor Combustible Floor InstallationManifold Gas Pressure Adjustments StartupGas Supply Pressure Temperature Rise Check Natural Gas Input Rating CheckMain Burner Flame Check Continuous- Fan using G Blower AdjustmentsHard Wired Continuous Fan Operation Changing Blower SpeedOn = OFF = Low Cooling Y1 Request High Cooling Y1 & Y/Y2 or Y/Y2 RequestContinuous Circulating Fan G Request Heating Request with Gas Shut Off Furnace Control Board Diagnostic Codes See FigWiring Diagram Thermostat Wiring Guide No Connection SINGLE-STAGE Thermostat TWO-STAGE Catalog No 58HDV---01SI