DSCover Satellite Products SCW904x Appendix C Regulatory Approvals Information, North America

Page 58

Self Contained Wireless Alarm System v1.0

Appendix C: Regulatory Approvals Information

North America

This product has been tested and found in compliance with the following standards: UL1023 Household Burglar-Alarm System Units

UL985 Household Fire Warning System Units UL1635 Digital Alarm Communicator System Units

ULC-S545-02Residential Fire Warning System Control Units ORD-C1023-1974Household Burglar-Alarm System Units

This product has also been tested and found in compliance with the ANSI/SIA CP-01-2000 Control Panel Standard – Features for False Alarm Reduction.

This product is UL/ULC listed under the following categories: UTOU/UTOUC Control Units and Accessories, Household System Type NBSX/NBSXC Household Burglar Alarm System Units

AMTB Control Panels, SIA False Alarm Reduction

The product is labeled with the UL and ULC listing marks along with the SIA CP-01 compliance statement (Also Classified in accordance with SIA-CP-01 Stan- dard) as proof of compliance with the above mentioned standards. For further information on this product’s listings please also refer to the official listing guides published at the UL web site (www.ul.com) under Certifications Section.

UL/ULC Residential Fire and Burglary Installations:

For ULC Installations refer to the Standard for the Installation of Residential Fire Warning Systems, CAN/ULC-S540.

All burglary-type zones shall be configured with SEOL or DEOL configuration (refer to section [133] and [134], bit 15 or 16 shall be ON)

Use at least one WS4916 Smoke Detector for Fire Installations (refer to section [001], fire zone shall be programmed as type 89)

The entry delay shall not exceed 60 seconds (refer to section [005])

The exit delay shall not exceed 120 seconds (refer to section [005])

The minimum Bell Time-out is 4 minutes (refer to section [005])

Note: For ULC Residential Fire Installations the minimum Bell Time-out is 5 minutes

Temporal Three Fire Signal shall be enabled (refer to section [013], option 8 shall be ON)

Arm/Disarm Bell Squawk shall be enabled when using wireless key WS4939 (refer to section [014], option 1 shall be ON)

Auxiliary Power boost shall be enabled (refer to section [014], option 4 shall be ON)

A code shall be required for bypassing (refer to section [015], option 5 shall be ON)

Trouble beeps shall be enabled (refer to section [023], option 7 shall be ON)

AC trouble indication LED shall be enabled (refer to Keypad Programming, section [075], options 5 and 6 shall be ON)

DACT Communicator shall be enabled for Supervising Station Monitoring (refer to section [380], option 1 shall be ON).

Note: The DACT communicator for this product has no line security.

Telephone Line Monitoring (TLM) shall be enabled (refer to section [015], option 7 shall be ON)

Note: This product is programmed to perform 5 attempts for communication of an event to the supervising station. If unsuccessful, a Fail To Communicate (FTC) trouble is generated.

Test transmission cycle shall be set for monthly transmission (refer to section [377])

Note: For ULC Residential installations set for daily test transmission

Wireless Supervision window shall be enabled (refer to Wireless Programming, sections [82] to [85])

Wireless Supervision window shall be set to 4h for Fire Installations (refer to Wireless Programming, section [81] shall be programmed with the value [16]

Wireless Supervision window shall be set to 24h for Burglary Installations only (refer to Wireless Programming, section [81] shall be programmed with the value [96]

RF Jam detection shall be enabled (refer to Wireless Programming, section [90], option 7 shall be OFF)

Bells will be active During 2-way Audio (refer to section [600], opt 7 shall be ON)

New Alarms will Disconnect 2-way Audio (refer to section [023], opt 6 shall be OFF)

When the 2- way audio feature is enabled (section [381] option 5 is ON) ensure that section [023] option 6 is OFF and section [600] option 7 is ON

Programming

The notes in the programming sections describing the system configurations for UL/ULC listed installations shall be implemented

Bell Location

The alarm sounding device (bell) shall be located where it can be heard by the person operating the security system during the daily arming and disarming cycle.

Casual Users

The installer should caution the user(s) not to give system information (e.g. codes, bypass methods, etc.) to casual users (baby-sitters or service people). Only the One-Time Use codes shall be given to casual users.

User Information

The installer should advise the users and note in the User’s Manual:

Service organization name and telephone number

The programmed exit time

The programmed entry time

Test system weekly

54WWW.DIYALARMFORUM.COM

Image 58
Contents Installation Guide Selecting a Suitable Location For The Alarm Controller Before Installing The EquipmentSafety Precautions required during Installation Table of Contents Page Installation & Wiring Technical SummaryInstallation Ensure connector key is oriented correctlyBurglary Zone Wiring Chart WiringMax wire Length to End-of-line Resistor Self Contained Wireless Alarm System Activate Wireless Device Wireless Device EnrollmentEnter Wireless Enrollment Mode Verify Device Electronic Serial Number ESNZone Dependant Devices Detectors Template Programming Zone Definitions Options 1Digit 3 selects 1 of the 8 following options Installer Lead-in/Lead-out and DLS Lead-in/Lead-out DLS Programming New Installations Refer to .1 Installation onExisting Installations Refer to .1 Installation on Local Programming with PC-LinkOperation Trouble Display Alarm Memory DisplayDoor Chime Enable/Disable Program User CodesAdditional Keypad Functions 7x Command Outputs 1&2Installer Programming 9User Code No-Entry ArmingAdvanced Programming Programming Work Sheets Index to Programming Work Sheets and DescriptionsFunction Key Options Programming WorksheetsFunction Key Programming Zone Definitions009 I/O Programming Installer’s Code Master CodeSystem Times Keypad Lockout OptionsFourth System Options Second System OptionsThird System Options Tenth System OptionsZone Loop Response Options Zone Attributes Options 10-13 are reserved for Future UseNo Activity Arming Pre-alert Timer PGM Output TimerCross Zone/Police Code Timer No Activity Arming TimerMiscellaneous Alarm Reporting Codes Alarm Reporting Codes, ZonesAlarm Restoral Reporting Codes, Zones Priority Alarm and Restoral Reporting CodesTamper Restoral Reporting Codes, Zones Tamper Reporting Codes, ZonesMiscellaneous Opening Disarming Reporting Codes Communicator Format Options Tamper/Restore Communicator Call DirectionsOpening/Closing Communicator Call Directions Communication Variables System Maintenance Communicator Call DirectionsSystem Test Transmissions Communicator Call Directions Test Transmission Time of DayThird Communicator Options Second Communicator OptionsDownloading Options PGM Output Attributes Number of Rings To Answer OnInitiate PC-Link Downloading Attribute600 2-way Audio Control Options Applies to SCW9047 only Automatic Clock AdjustDelay Between Dialing Attempts First International OptionsWireless programming Wireless Zone Programming Wireless Supervisory WindowInstaller Lockout Disable General Wireless OptionsWireless Module Placement Test Installer Lockout Enable Restore Wireless Device Default ProgrammingLocal Keypad Programming Label Programming ZoneCommand Output #1 Label Fire Alarm LabelAlarm When Armed Event Message Command Output #2 LabelSecond Keypad Options Reset Programmable Labels to Factory DefaultsFirst Keypad Options Third Keypad OptionsKeypad Function Key Programming Programming Descriptions002 Zone Definitions Master Code Installer CodeSystem Times O Programming Zones/PGMsSecond System Options First System OptionsThird System Options Tenth System Options Fourth System OptionsOFF Keypad Always Active. The keypad does not blank Daylight Saving Time Move Clock Ahead Zone Loop Response Options134 Zone Attributes Standard Time Set Clock BackNo Activity Arm Timer PGM Output TimerCross Zone/Police Code Timer Call Waiting Cancel StringTest Transmission Time Communicator VariablesFirst Communicator Options Third Communicator Options OFF Closing Confirmation Disabled. The keypad does not beepSecond Communicator Options First Downloading OptionsPanel Identification Code Downloading Access CodeDownloading Computer Phone Number Number of Rings to Answer OnWay Audio Control Options applies to SCW9047 only Automatic Clock AdjustFollowing attributes are available for PGM Output Type First International Options Delay Between Dialing AttemptsWireless Programming Second International OptionsInstaller Lockout Disable Wireless Module Placement TestInstaller Lockout Enable Restore Wireless Device Default Programming069 Command Output Label Fire Alarm LabelsAlarm when Armed Event Message Keypad ProgrammingSecond Keypad Options OFF Power LED is disabled. Option 6 has no effectFirst Keypad Options Option Description Future UseProgrammed LCD Message Label ResetThird Keypad Options Programmed LCD Message DurationTesting & Troubleshooting Trouble 4 Failure to Communicate Trouble 8 Loss of Clock/DateAppendix a Reporting Code Formats Contact IDContact ID Zone Alarm/Restoral Event Codes SIA Format Automatic Zone Alarm/Restoral CodesAppendix B Communicator Format Options Pager Residential DialAppendix C Regulatory Approvals Information North AmericaEurope SIA False Alarm Reduction InstallationsNew Zealand Appendix D SIA False Alarm Reduction Exit TimeAppendix E 2-Way Audio Verification SCW9047 only Format Reporting Code/EventHang-up Auto-detection Key Command DescriptionVOX Support Bell/Buzzer Silent During 2-Way AudioPage FCC Compliance Statement