DSCover Satellite Products SCW904x Wireless Device Enrollment, Enter Wireless Enrollment Mode

Page 9

Section 2: Wireless Device Enrollment

Section 2: Wireless Device Enrollment

Before a wireless device can be recognized by the security system, it must be enrolled.

Devices that are not enrolled will be ignored by the system. See “Section [904]: Wireless Module Placement Test” on page 44.

Device Enrollment must be performed close to the alarm system.

Maximum signal strength is required to ensure that the correct device is being enrolled.

1. Enter Wireless Enrollment Mode

Enter [ ][8] [Installer Code] [898] on the system keypad.

2.Activate Wireless Device

-For FOBs & Panic Pendants - Press any button

-For PIRs, Smoke and Glass Break Detectors - Activate Tamper

-For Contact Switches - Close Contacts

3.Verify Device Electronic Serial Number (ESN)

When a device is activated the Alarm system will display the corresponding 6-digit ESN on the keypad.

Verify that the ESN displayed corresponds to the ESN on the device.

Note: The first digit of the ESN indicates the following:

2

3

4

5

6&9

denotes contact

denotes PIR/Glass Break Detector denotes Smoke Detector denotes Pendant

denotes FOB

4. Press [*] to confirm correct ESN, or press [#] to delete device if incorrect.

If the ESN displayed on keypad does NOT correspond to the ESN on the device being enrolled.

-Deactivate the wireless device

-Press the # key to repeat the enrollment process.

-Perform these steps until the correct ESN is displayed

If the device fails to enroll (i.e., incorrect ESN) attempt manual programming and testing of the device before determining that the device is faulty. Maximum signal strength is required to ensure that the correct device is being enrolled.

5. Enter Zone Number

After confirming that the device ESN is correct, the installer will be prompted to enter a zone number.

If the installer selects a zone that is currently in use, the installer will be prompted to overwrite the current zone or select a new zone. If all zones are in use the installer will be prompted to overwrite the selected zone.

WWW.DIYALARMFORUM.COM5

Image 9
Contents Installation Guide Before Installing The Equipment Selecting a Suitable Location For The Alarm ControllerSafety Precautions required during Installation Table of Contents Page Technical Summary Installation & WiringEnsure connector key is oriented correctly InstallationWiring Burglary Zone Wiring ChartMax wire Length to End-of-line Resistor Self Contained Wireless Alarm System Enter Wireless Enrollment Mode Wireless Device EnrollmentActivate Wireless Device Verify Device Electronic Serial Number ESNZone Dependant Devices Detectors Zone Definitions Options 1 Template ProgrammingDigit 3 selects 1 of the 8 following options Installer Lead-in/Lead-out and DLS Lead-in/Lead-out Existing Installations Refer to .1 Installation on New Installations Refer to .1 Installation onDLS Programming Local Programming with PC-LinkOperation Door Chime Enable/Disable Alarm Memory DisplayTrouble Display Program User CodesInstaller Programming 7x Command Outputs 1&2Additional Keypad Functions 9User Code No-Entry ArmingAdvanced Programming Index to Programming Work Sheets and Descriptions Programming Work SheetsFunction Key Programming Programming WorksheetsFunction Key Options Zone DefinitionsSystem Times Installer’s Code Master Code009 I/O Programming Keypad Lockout OptionsThird System Options Second System OptionsFourth System Options Tenth System OptionsZone Attributes Options 10-13 are reserved for Future Use Zone Loop Response OptionsCross Zone/Police Code Timer PGM Output TimerNo Activity Arming Pre-alert Timer No Activity Arming TimerAlarm Restoral Reporting Codes, Zones Alarm Reporting Codes, ZonesMiscellaneous Alarm Reporting Codes Priority Alarm and Restoral Reporting CodesTamper Reporting Codes, Zones Tamper Restoral Reporting Codes, ZonesMiscellaneous Opening Disarming Reporting Codes Tamper/Restore Communicator Call Directions Communicator Format OptionsOpening/Closing Communicator Call Directions System Test Transmissions Communicator Call Directions System Maintenance Communicator Call DirectionsCommunication Variables Test Transmission Time of DaySecond Communicator Options Third Communicator OptionsDownloading Options Initiate PC-Link Downloading Number of Rings To Answer OnPGM Output Attributes AttributeDelay Between Dialing Attempts Automatic Clock Adjust600 2-way Audio Control Options Applies to SCW9047 only First International OptionsWireless Supervisory Window Wireless programming Wireless Zone ProgrammingWireless Module Placement Test Installer Lockout Enable General Wireless OptionsInstaller Lockout Disable Restore Wireless Device Default ProgrammingLabel Programming Zone Local Keypad ProgrammingAlarm When Armed Event Message Fire Alarm LabelCommand Output #1 Label Command Output #2 LabelFirst Keypad Options Reset Programmable Labels to Factory DefaultsSecond Keypad Options Third Keypad OptionsProgramming Descriptions Keypad Function Key Programming002 Zone Definitions System Times Installer CodeMaster Code O Programming Zones/PGMsFirst System Options Second System OptionsThird System Options Fourth System Options Tenth System OptionsOFF Keypad Always Active. The keypad does not blank 134 Zone Attributes Zone Loop Response OptionsDaylight Saving Time Move Clock Ahead Standard Time Set Clock BackCross Zone/Police Code Timer PGM Output TimerNo Activity Arm Timer Call Waiting Cancel StringCommunicator Variables Test Transmission TimeFirst Communicator Options Second Communicator Options OFF Closing Confirmation Disabled. The keypad does not beepThird Communicator Options First Downloading OptionsDownloading Computer Phone Number Downloading Access CodePanel Identification Code Number of Rings to Answer OnAutomatic Clock Adjust Way Audio Control Options applies to SCW9047 onlyFollowing attributes are available for PGM Output Type Wireless Programming Delay Between Dialing AttemptsFirst International Options Second International OptionsInstaller Lockout Enable Wireless Module Placement TestInstaller Lockout Disable Restore Wireless Device Default ProgrammingAlarm when Armed Event Message Fire Alarm Labels069 Command Output Label Keypad ProgrammingFirst Keypad Options OFF Power LED is disabled. Option 6 has no effectSecond Keypad Options Option Description Future UseThird Keypad Options Label ResetProgrammed LCD Message Programmed LCD Message DurationTesting & Troubleshooting Trouble 8 Loss of Clock/Date Trouble 4 Failure to CommunicateContact ID Appendix a Reporting Code FormatsSIA Format Automatic Zone Alarm/Restoral Codes Contact ID Zone Alarm/Restoral Event CodesAppendix B Communicator Format Options Residential Dial PagerNorth America Appendix C Regulatory Approvals InformationSIA False Alarm Reduction Installations EuropeNew Zealand Exit Time Appendix D SIA False Alarm ReductionFormat Reporting Code/Event Appendix E 2-Way Audio Verification SCW9047 onlyVOX Support Key Command DescriptionHang-up Auto-detection Bell/Buzzer Silent During 2-Way AudioPage FCC Compliance Statement