DSCover Satellite Products SCW904x manual Appendix D SIA False Alarm Reduction, Exit Time

Page 60

Self Contained Wireless Alarm System v1.0

Appendix D: SIA False Alarm Reduction

SIA Feature

Comments

Range/Default

Require-

Programming Section

 

 

ment

 

 

 

 

Exit Time

Access to Entry and Exit delays and Bell Time Out for the system

Range:45- 255 seconds

Required

[005], 3rd entry

 

Default: 60 sec.

(programmable)

 

 

 

 

Progress Annunciation/

Enables audible exit beeps from the keypad for the duration of exit delay

Keypads may be disabled

Allowed

Disable - for Silent Exit

 

Default: Enabled

 

[014], Option 6 ON

 

 

 

 

 

 

 

Exit Time Restart

Enables the exit delay restart feature

Default: Enabled

Required

[014], Option 2 ON

 

 

 

 

 

 

 

Auto Stay Arm on

Function Key: Stay Arming. All Stay/Away type zones (05, 06) will be automatically

If no exit after full arm

Required

Unvacated Premises

bypassed

Default: Enabled

 

[001]-[002] Zone type 05, 06

 

 

 

 

 

 

 

Exit Time and Progress

System Times and Audible Exit beeps can be disabled when using the Key fob to arm

Default: Enabled

Allowed

Annunciation/Disable

away the system

 

 

or Remote Arming

 

 

 

[005] and [014] bit 6

 

 

 

 

 

 

 

Entry delay(s)

Access to Entry and Exit delays and Bell Time Out for the system

Range: 30 sec. to 4 min.

Required

[005], 1st and 2nd entry

Note: Combined Entry delay and Communications Delay (Abort Window) shall not

Default: 30 sees

(programmable)

 

exceed 60s

 

 

 

 

 

 

Abort Window

Access to zone attributes, i.e, swinger shutdown, transmission delay and cross zone.

May be disabled

Required

for Non-Fire zones

Individual zones attribute bit 6 (Transmission delay) is by default ON

by zone or zone type

 

[101]-[134] bit 6 ON

 

Default: Enabled

 

 

 

 

 

Abort Window - for

Access to the programmable delay before communicating alarms

Range: 15 - 45 sec.

Required

Non-Fire zones

Note: Combined Entry delay and Communications Delay (Abort Window) shall not

Default: 30 sees

(programmable)

[377], 4th entry

exceed 60s

 

 

 

 

 

 

Abort Annunciation

Enables the “Communication Cancelled” message display on keypad

Annunciate that no

Required

[382], Option 3 ON

 

alarm was transmitted

 

 

 

Default: Enabled

 

 

 

 

 

Cancel Annunciation

Access to the reporting code for Alarm Cancelled

Annunciate that a

Required

[328], 8th entry

 

Cancel was transmitted

 

 

 

Default: Enabled

 

 

 

 

 

Duress Feature

Do not derive code from an existing Master/User code (e.g., Master code is 1234, the

No 1+/- derivative of another

Allowed

[*][5] Master Code

duress code should not be 1233 or 1235)

user code. No duplicates with

 

Option 2 ON

 

other user codes

 

 

 

Default: disabled

 

 

 

 

 

Cross Zoning

This option enables Cross Zoning for entire system. Individual zones can be enabled

Programming required

Required

[016] Option 1

for Cross zoning via Zone attribute bit 8 in sections [101] - [134]

Default: Disabled

 

[101]-[134] bit 8 OFF

 

 

 

 

 

 

 

Cross Zone Timer

Access to the programmable Cross Zone timer

May program

Allowed

[176]

 

Range: 001-255 sec./min.

 

 

 

Default: 60 secs

 

 

 

 

 

Swinger Shutdown for Alarms

Access to the swinger shutdown limit for zone alarms

For all non-fire zones

Required

[377] 1st entry

 

shut down at 1 or 2 trips

(programmable)

 

 

Default: 1 Trip

 

 

 

 

 

Swinger Shutdown Enable

Access to zone attributes, i.e., swinger shutdown, transmission delay and cross zone.

For non-police

Allowed

[101] - [134] bit 6 ON

Individual zones attribute bit 6 (Swinger shutdown enabled) is by default ON

response zones

 

 

 

Default: Enabled

 

 

 

 

 

24-Hr. Auto_verified Fire

Access to 24-Hr. Auto_verified Fire (Wireless)

Activates If a restoral is Not

Required

(Wireless) Zone type [89]

 

received within the specified

 

 

 

time

 

 

 

Default: disabled

 

 

 

 

 

Call Waiting Cancel Dial String

Access to the dialing sequence used to disable call waiting

Dependant on user phone

Required

[304], [382], Option 4 OFF

 

line

 

 

 

Default: disabled

 

 

 

 

 

 

Testing

 

 

 

 

 

 

System Test:

The system activates all keypad sounders, bells or sirens for 2 seconds and all keypad lights turn on.

 

[*][6] Master Code, Option 4

Refer to the User Manual (part no. 29007326).

 

 

 

 

 

 

Walk Test Mode:

This mode is used to test each zone on the system for proper functionality.

 

 

[*][6] Opt 8

 

 

 

 

 

 

 

Alarm Communications

Enables Communication of zone alarms while Walk Test is active.

 

 

During Walk Test

 

 

 

[382] Option 2:

 

 

 

 

 

 

 

Walk Test End and Begin

Access to the reporting codes for Walk Test Begin and Walk Test End.

 

 

Reporting Codes

 

 

 

[348], 1st and 2nd Entries

 

 

 

56WWW.DIYALARMFORUM.COM

Image 60
Contents Installation Guide Before Installing The Equipment Selecting a Suitable Location For The Alarm ControllerSafety Precautions required during Installation Table of Contents Page Installation & Wiring Technical SummaryInstallation Ensure connector key is oriented correctlyWiring Burglary Zone Wiring ChartMax wire Length to End-of-line Resistor Self Contained Wireless Alarm System Wireless Device Enrollment Enter Wireless Enrollment ModeActivate Wireless Device Verify Device Electronic Serial Number ESNZone Dependant Devices Detectors Template Programming Zone Definitions Options 1Digit 3 selects 1 of the 8 following options Installer Lead-in/Lead-out and DLS Lead-in/Lead-out New Installations Refer to .1 Installation on Existing Installations Refer to .1 Installation onDLS Programming Local Programming with PC-LinkOperation Alarm Memory Display Door Chime Enable/DisableTrouble Display Program User Codes7x Command Outputs 1&2 Installer ProgrammingAdditional Keypad Functions 9User Code No-Entry ArmingAdvanced Programming Programming Work Sheets Index to Programming Work Sheets and DescriptionsProgramming Worksheets Function Key ProgrammingFunction Key Options Zone DefinitionsInstaller’s Code Master Code System Times009 I/O Programming Keypad Lockout OptionsSecond System Options Third System OptionsFourth System Options Tenth System OptionsZone Loop Response Options Zone Attributes Options 10-13 are reserved for Future UsePGM Output Timer Cross Zone/Police Code TimerNo Activity Arming Pre-alert Timer No Activity Arming TimerAlarm Reporting Codes, Zones Alarm Restoral Reporting Codes, ZonesMiscellaneous Alarm Reporting Codes Priority Alarm and Restoral Reporting CodesTamper Reporting Codes, Zones Tamper Restoral Reporting Codes, ZonesMiscellaneous Opening Disarming Reporting Codes Tamper/Restore Communicator Call Directions Communicator Format OptionsOpening/Closing Communicator Call Directions System Maintenance Communicator Call Directions System Test Transmissions Communicator Call DirectionsCommunication Variables Test Transmission Time of DaySecond Communicator Options Third Communicator OptionsDownloading Options Number of Rings To Answer On Initiate PC-Link DownloadingPGM Output Attributes AttributeAutomatic Clock Adjust Delay Between Dialing Attempts600 2-way Audio Control Options Applies to SCW9047 only First International OptionsWireless programming Wireless Zone Programming Wireless Supervisory WindowGeneral Wireless Options Wireless Module Placement Test Installer Lockout EnableInstaller Lockout Disable Restore Wireless Device Default ProgrammingLocal Keypad Programming Label Programming ZoneFire Alarm Label Alarm When Armed Event MessageCommand Output #1 Label Command Output #2 LabelReset Programmable Labels to Factory Defaults First Keypad OptionsSecond Keypad Options Third Keypad OptionsProgramming Descriptions Keypad Function Key Programming002 Zone Definitions Installer Code System TimesMaster Code O Programming Zones/PGMsFirst System Options Second System OptionsThird System Options Fourth System Options Tenth System OptionsOFF Keypad Always Active. The keypad does not blank Zone Loop Response Options 134 Zone AttributesDaylight Saving Time Move Clock Ahead Standard Time Set Clock BackPGM Output Timer Cross Zone/Police Code TimerNo Activity Arm Timer Call Waiting Cancel StringCommunicator Variables Test Transmission TimeFirst Communicator Options OFF Closing Confirmation Disabled. The keypad does not beep Second Communicator OptionsThird Communicator Options First Downloading OptionsDownloading Access Code Downloading Computer Phone NumberPanel Identification Code Number of Rings to Answer OnAutomatic Clock Adjust Way Audio Control Options applies to SCW9047 onlyFollowing attributes are available for PGM Output Type Delay Between Dialing Attempts Wireless ProgrammingFirst International Options Second International OptionsWireless Module Placement Test Installer Lockout EnableInstaller Lockout Disable Restore Wireless Device Default ProgrammingFire Alarm Labels Alarm when Armed Event Message069 Command Output Label Keypad ProgrammingOFF Power LED is disabled. Option 6 has no effect First Keypad OptionsSecond Keypad Options Option Description Future UseLabel Reset Third Keypad OptionsProgrammed LCD Message Programmed LCD Message DurationTesting & Troubleshooting Trouble 4 Failure to Communicate Trouble 8 Loss of Clock/DateAppendix a Reporting Code Formats Contact IDContact ID Zone Alarm/Restoral Event Codes SIA Format Automatic Zone Alarm/Restoral CodesAppendix B Communicator Format Options Pager Residential DialAppendix C Regulatory Approvals Information North AmericaSIA False Alarm Reduction Installations EuropeNew Zealand Appendix D SIA False Alarm Reduction Exit TimeAppendix E 2-Way Audio Verification SCW9047 only Format Reporting Code/EventKey Command Description VOX SupportHang-up Auto-detection Bell/Buzzer Silent During 2-Way AudioPage FCC Compliance Statement