GOLD GV Water boiler series 3 — manual
IIIf Water piping — radiator system
Figure 12a Radiator system — zone-valve zoning
Zone 2
Zone 1
12"
max
Cold water
fill
GV Boiler
85013b
Figure 12b Radiator system — circulator zoning
Zone 2
Zone 1 |
12" |
max |
Cold |
water |
fill |
GV Boiler
Radiator system piping
Apply Figure 12a
The suggested piping for
The boiler internal circulators must be left in the boiler. They cannot be removed for use a a zoning circulator. Provide a circulator for each zone when circulator zoning, and pipe the system as in Figure 12b.
Legend
1Boiler isolation valves
2Automatic air vent (with
3Diaphragm- or
4Zone valve
5System or zone circulator
6Flow/check valve
7Hose bibb purge valve
85017 | 8 | Boiler pressure/temperature gauge |
| ||
32 |
| Part number |