• Installation •
Table 11 Boiler dimensional data (see Figure 40)
Boiler | Supply | Return | Length | Gas | Crate dimensions | Approx. | ||
model |
|
| L | connection | (outside measurement, inches) | shipping | ||
|
|
|
| size (Note 1) |
|
|
| weight |
|
|
|
| Length | Width | Height | ||
| (in. NPT) | (in. NPT) | (inches) | (in. NPT) | (pounds) | |||
|
|
|
|
|
|
|
|
|
1 | 1 | 30¾ | ½ | 33½ | 22 | 36 | 270 | |
|
|
|
|
|
|
|
|
|
1 | 1 | 30¾ | ½ | 33½ | 22 | 36 | 320 | |
|
|
|
|
|
|
|
|
|
1 | 1 | 37¾ | ½ | 33½ | 22 | 43 | 355 | |
|
|
|
|
|
|
|
|
|
1 | 1 | 37¾ | ½ | 33½ | 22 | 43 | 410 | |
|
|
|
|
|
|
|
|
|
Note 1 | Gas piping from meter to boiler to be sized per local utility requirements. |
|
| |||||
|
|
|
|
|
|
|
|
|
Table 12 | Boiler ratings |
|
|
|
|
|
|
|
|
|
|
|
|
Boiler | AGA Input | DOE Heating | Net I=B=R | DOE | Vent/combustion | Boiler water |
model | Btuh | capacity Btuh | ratings Btuh | Seasonal | air diameter | content |
number |
| (Note 1) | (Note 2) | efficiency (%) | (inches) | (gallons) |
|
|
|
|
|
|
|
70,000 | 61,000 | 53,000 | 87.5 | 3 | 3.3 | |
|
|
|
|
|
|
|
105,000 | 92,000 | 80,000 | 87.3 | 3 | 4.2 | |
140,000 | 122,000 | 106,000 | 87.2 | 3 | 5.1 | |
|
|
|
|
|
|
|
175,000 | 153,000 | 133,000 | 87.0 | 3 | 6.0 | |
Notes: |
|
|
|
|
|
|
1. Based on standard test procedures prescribed by the United States Department of Energy. Ratings also referred to as AGA/ | ||||||
CGA Output. |
|
|
|
|
| |
2. Net I=B=R ratings are based on net installed radiation of sufficient quantity for the requirements of the building and nothing | ||||||
need be added for normal piping and pickup. Ratings are based on a piping and pickup allowance of 1.15. An additional | ||||||
allowance should be made for unusual piping and pickup loads. |
|
|
| |||
|
|
|
|
|
|
|
Boilers are tested for 50 lbs working pressure. GV boilers are not available for millivolt systems. |
| |||||
|
|
|
|
|
|
|
Part number | 95 |