• Installation •
IXb Operation — sequence
Figure 22 Ignition control module sequence of operation — status light indications
Steps |
| POWER TSTAT | LIMIT | PRESS FLAME |
| |
Call for | CIRC |
| SWITCH | Timing | ||
|
|
| ||||
|
| heat? |
|
|
|
|
(Following step 8, cycle goes back to step 1.) |
|
|
|
|
| |
|
|
|
|
|
|
|
1. | Standby | NO |
|
|
| — |
| · Waiting for call for heat |
|
|
| ||
|
|
|
|
|
| |
|
|
|
|
|
|
|
2. | Call for heat |
|
|
|
|
|
| · Circulator on | YES |
|
|
| — |
· Blower on
3.Limit circuit
· | Limit controls closed | YES | — |
· Block switch contacts closed |
|
| |
|
|
| |
4. Pressure circuit |
|
| |
· | Pressure switch contacts closed | YES | 35 sec |
|
|
·Igniter heating
5.Flame proven
·Gas valve open
· | Ignitor remains on | YES | 6 sec |
|
| ||
· | Boiler producing heat |
|
|
|
|
| |
6. Limit cycle |
|
| |
· | Limit circuit open | YES | — |
· Gas valve closed
7.Flame outage *
· Flame out | YES | — |
· Boiler recycles
8.Thermostat satisfied
· Circulator off | NO | 30 sec |
·Blower postpurge
or | = "ON" | = "OFF" |
*If flame is not proven in 4 seconds, boiler recycles 2 times to retry for ignition before going into lockout. Recycle igniter timing is 30 seconds. Postpurge and prepurge are performed on every cycle. In event of lockout, ignition control will automatically restore sequence of operation after either:
1 hour waiting period.
Opening and closing of thermostat circuit.
Removal of 120 VAC power for at least 45 seconds. | 85050 |