IIIi Water piping — snow melt system
Figure 15a Manual bypass valves; for fixed temp operation only
Snow melt |
heat exchanger |
Heating zone(s) |
12" |
max |
Cold water
fill
GV Boiler
85014b
Figure 15b Auto return temp regulation; for outdoor reset or fixed temp
Snow melt
heat exchanger
Heating zone(s)
12" |
max |
Cold water
fill
GV Boiler
85016
Piping snow melt systems or combination snow melt/ space heating systems
Combination snow melt/space heating systems will have widely varying system return temperatures. So these systems require automatic return water temperature as shown in Figure 15a
Select an automatic temperature control valve or motor- operated valve which can be adjusted to provide a return water temperature of at least 60 °F. Any setting higher than 60 °F will also be acceptable.
Circulator zoning — The GV internal circulators must not be removed. Provide a separate circulator for each zone.
The return water temperature to the boiler must be at least 60 °F. Provide and apply means to regulate the return temperature. Failure to do so can result in boiler control operation problems, causing possible significant property damage.
Legend
1Boiler isolation valves
2Automatic air vent (with
3Diaphragm- or
4Zone valve
5System or zone circulator
6Flow/check valve
7Hose bibb purge valve
8Boiler pressure/temperature gauge
9System supply temperature gauge
12Return temperature automatic mixing valve
Part number | 35 |