• Installation •
Symptom | Common Causes | Possible Corrections | |
|
|
| |
Popping or percolating | Mineral deposits in sections due to | Call qualified service technician to | |
noise heard in boiler | constant use of makeup water | boiler, if necessary. In some cases, | |
|
| deposits will be too heavy to remove with | |
|
| ||
|
|
| |
|
| Have qualified service technician repair | |
|
| leaks to eliminate need for constant | |
|
| makeup water. | |
|
|
| |
| Incorrect pH of boiler water | Call qualified service technician to check | |
|
| pH level and correct. pH should be | |
|
| maintained between 7.0 to 8.5. | |
|
|
| |
| Insufficient water flow through | Check all valves to and from boiler. Return | |
| boiler | to proper setting. | |
|
|
| |
|
| Confirm circulator size. | |
|
|
| |
Metal flakes found in vent | Contaminated combustion air | Remove any contaminating products, see | |
outlet or vent starter tee — | supply — See manual page 13. | manual page 13. | |
flueway corrosion |
|
| |
| Provide outside air for combustion. Kit | ||
|
| ||
|
| available through | |
|
| Have qualified service technician | |
|
| kit. | |
|
|
| |
| Condensation of combustion | Have qualified service technician check | |
| gases in boiler sections | operation of mixing system. Repair/replace | |
|
| if necessary. | |
|
|
| |
Some radiators or | Air in system | Bleed air from system through air vents in | |
baseboard units do not |
| radiators or baseboard units. | |
heat or are noisy |
|
| |
Low system pressure | Fill to correct pressure. | ||
| |||
|
|
| |
|
| Check for leaks in boiler or piping. Have | |
|
| qualified service technician repair at once. | |
|
|
| |
| High limit set too low | Adjust high limit to higher setting. | |
|
|
| |