The 4-20 mA passive receivers must not contain a voltage source to power the loop current. They do require the addition of a separate isolated power supply. Typically a supply that delivers 15 to 20 volts DC at 50 mA is sufficient. Wire these as in Figure 3. Note that some 12-volt DC wall transformers (as used on portable equipment) may deliver 15 to 20 volts when they are lightly loaded. The CUI/Stack #AD-1220M is a commonly available example of a 12 volt 200mA supply that will deliver around 18 volts nominal when loaded below 20 mA.

Be sure that both the power supply used and the passive receiver are floating (not connected to earth ground). If either is not floating, the circuit will not work and damage may occur.

Ensure that jumper SW101 is set to the “I” position before power-up.

Page 44 of 50

AZI Customer Service 800-528-7411 or 602-470-1414

Image 44
Contents Jerome Jerome Table of Contents For Those WHO Cant Read the Whole Manual NOW AZI Customer Service 800-528-7411 or Introduction FeaturesOptional Accessories Applications Principle of OperationGas Flow Schematics Zero Air FilterAZI Customer Service 800-528-7411 or Display to read H after sampling has started Instrument OperationLCD Codes Daily Operations Sensor Regeneration Do not Interrupt this CycleZero Adjust Do not turn the Zero Adjust potentiometer between samplesSample Mode Accuracy at MID-RANGESurvey Mode External battery power Operating on AC Power or GeneratorOperating on Internal Battery Power Obtaining Maximum Battery Life Charging BatteriesMaintenance Preventive Maintenance CalendarInch Fritware Filter Flow SystemPart Part Number Internal Filters Replacing the Battery Pack Setting the Input VoltageChanging the Fuse Calibration Verification of Calibration and Quality ControlRegeneration & Zero Problems TroubleshootingPower Problems Sampling Problems Miscellaneous Problems Jerome 631-X Technical Specifications Optional Communications Capability Instrument I/O InterfaceAZI Customer Service 800-528-7411 or Accessories & Maintenance Parts Functional Test ModuleJerome Data Logger Jerome Communication Software KitSpare Parts AZI Customer Service 800-528-7411 or AZI Customer Service 800-528-7411 or Factory Calibration Service Appendix a 631-X Functional Test Module Simple OperationMain Appendix B Jerome Communications SoftwareInstrument Control with Real-Time Graphics Data Logger Option JCI Kit ContentsSystem Requirements Appendix C Internal DIP Switch Settings DIP Switch SettingsSwitch # Position Function Comment Switch # Function CommentInstrument Zeroing Appendix D Jerome 631-X Option BoardAuto-Zero Timed Regeneration SW101 Functions Auto-SampleMA Analog Output Connection and Setup AZI Customer Service 800-528-7411 or Fresh Air Solenoid Required Parts Suggested Part Similar AZI P/NDC Power Operation DC Power Adaptor Kit, AZI P/N Y031AZI Customer Service 800-528-7411 or Molecular weight of H 2S Appendix E Calculation of Dynacalibrator H2S ConcentrationWarranty Trademark and Copyright Protection Arizona Instrument LLC Part Number January