Hearth and Home Technologies PALOMA-GR, PALOMA-BL How to Use the Vent Graph, Venting Guidelines

Page 12

D. How to Use the Vent Graph

1.Measure the distance from the top of appliance to the center of the 90° elbow. On the graph below, draw a horizontal line from that measurement on the vertical axis across until it intersects with the slanted line.

2.From the point of this intersection, draw a vertical line to the bottom of the graph.

3.The point at which this line meets the bottom line of the graph is the maximum length of the horizontal run.

Example 1: If the vertical dimension from the top of the appliance to the center of the 90° elbow is 7 ft. (2 m), the horizontal run to the outer wall flange must not exceed 13 ft. (4 m).

Example 2: If the vertical dimension from the top of the appliance is 21 ft. (6.4 m), the horizontal run to the outer wall flange must not exceed 9 ft. (3 m).

4.Each 90° elbow is equivalent to 3 ft. (914 mm) of vent pipe and each 45° elbow is equivalent to 1 ft. (305

mm)of vent pipe, and must be subtracted from vent pipe run. A single vertical to horizontal 90° elbow is already calculated into the allowable 15 ft. (5 m) run. Each additional 90° elbow reduces the maximum horizontal distance by 3 ft. (914 mm).

Example: The use of three elbows would reduce the allowable horizontal run to 9 ft. (3 - 1 = 2 elbows x 3 ft. = 6 ft.; 15 ft. max. - 6 ft. = 9 ft. max.)

E. Venting Guidelines

The maximum horizontal vent run is 15 ft. (5 m) when the vertical vent rise is 10 ft. (3 m).

The minimum horizontal vent run is 11-5/8 in. (295 mm).

Horizontal sections require a 1/4 in. (6 mm) rise for every 12 in. (305 mm) of horizontal travel.

Horizontal sections require noncombustible support every 3 ft. (914 mm), e.g. wall strap.

Wall thickness: Minimum 4 in. (102 mm). Maximum 20 in. (508 mm).

Vent Diameter: Exterior 6-5/8 in. (168 mm); Inner 4 in. (102 mm).

EXCEPTION FOR REAR VENT KIT (Snorkel Kit SLK-

SNKD), HORIZONTAL INSTALLATION:

The maximum horizontal vent run is 3 ft. (914 mm).

The maximum horizontal vent run with a 45° elbow is 2 ft. (610 mm).

No external minimum rise is required. The minimum horizontal vent run is 11-5/8 in. (295 mm).

For any vertical rise when rear venting, a minimum of 2 ft. (610 mm) vertical must be used prior to any horizontal run.

Snorkel Kit (SLK-SNKD) must be used for horizontal vent runs with no vertical rise.

EX. 2

VERTICAL DISTANCE

FROM APPLIANCE TO THE 90º ELBOW

EX. 1

35'

 

 

 

 

 

 

 

 

 

 

34'

 

 

 

 

 

 

 

 

 

 

32'

 

 

 

 

 

 

 

 

 

 

30'

 

 

 

 

 

 

 

 

 

 

28'

 

 

 

 

 

 

 

 

 

 

26'

 

 

 

 

 

 

 

 

 

 

24'

 

 

 

 

 

 

 

 

 

 

22'

 

 

 

 

 

 

 

 

 

 

20'

 

 

 

TOR

 

 

 

 

 

18'

 

 

 

 

 

 

 

 

 

RESTRIC

D

 

 

 

 

TOTAL HORIZONTAL RUN TO

 

 

 

 

 

 

16'

 

 

 

 

 

 

 

 

 

 

 

 

OUTSIDE OF EXTERIOR WALL

 

 

 

 

 

 

 

14'

TE

REQUIRE

 

 

 

 

(INCLUDING ELBOWS)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12'

VENT

 

 

 

 

 

 

 

 

To adjust the vent restrictor

PLA

 

 

 

 

 

 

 

10'

 

 

 

 

 

 

 

 

 

plate, see page 34.

8'

 

 

 

 

 

 

 

 

 

 

6'

 

 

 

 

 

 

 

 

 

 

4'

 

 

 

 

 

 

 

 

 

 

2'

 

 

 

 

 

 

 

 

 

 

0'

 

 

 

 

 

 

 

 

 

 

11-5/8” 2'

 

4'

 

6'

8'

10'

12'

14'

15'

(MIN)

 

 

 

 

 

 

 

 

(MAX)

Figure 5.2

6 ft. (2 m) Minimum Vertical Termination

C

L

CL For rear vent or top of appliance for top vent.

3 ft. (914 mm) Maximum Horizontal run with no vertical pipe and with 1/4 in. (6 mm) rise per foot.

6 in. (152 mm) Minimum starter pipe

12

Heat & Glo • Paloma • 7031-220 Rev. P • 10/08

Image 12
Contents Models What to do if you smell gasDo Discardnot Hot glass will cause burnsCongratulations Homeowner Reference InformationTable of Contents Listing and Code Approvals Installation of Carbon Monoxide Detectors Requirements for the Commonwealth of MassachusettsInstallation to ensure maximum safety and benefit Getting StartedTools and Supplies Needed Framing and Clearances Selecting Appliance LocationClearances to Combustibles ModelOptional Stone Surround Installed Paloma Surround Termination Locations Vent Termination Minimum Clearances See .4 for specific clearances Alcove Applications Vent Information Venting ComponentsUse of Elbows Measuring StandardsHow to Use the Vent Graph SNKD, Horizontal InstallationVenting Guidelines Exception for Rear Vent KIT Snorkel Kit SLKHorizontal Termination Female Locking Lugs Male Locking203 mm 178 mm 152 mm Vinyl Siding Vertical Termination Hole as shown in Figure Twist-lock the vent cap and seal Cathedral Ceiling Class a Metal Chimney Existing Masonry Chimney Type aTo determine the length of flex needed, measure from Flex Liner Flex Coupler Sheet Metal Screws Installing Slim Line Trim Ring and Heat Shield Slim Line Wall ThimbleAssembling Slim Line Trim Ring and Heat Shield FIG. C Minimum Clearance Procedure for Conversion Gas InformationFuel Conversions Converting to LP GasReattach Pilot Shield Gas Pressures Verify the performance of the ignition systemPressure Natural Gas Propane Gas Connection Check for GAS LeaksRecommendation for Wire Connecting to the ApplianceIntelliFire Ignition System Wiring Wire Size Max. LengthLoss of Power and Battery Backup Usage Wall Switch Installation for Fan Optional Junction Box Wired to Wall SwitchAppliance Setup Remove Shipping MaterialsUnbolting Appliance from the Pallet Accessories Leveling and Lagging Down the ApplianceTop to Rear Vent Conversion Shutter Adjustment Installing the Vent RestrictorInstalling the Baffle Positioning the LogsInstallation precautions Mineral WoolOptional Blower Black Wires Recommended operating procedures Variable Remote Controls Installing flame control solenoidRemote receiver Wiring the flame control solenoid RED Orange BlueFront Door Glass Assembly Installation Inner Glass Door Assembly ReplacementOperating Instructions Before Lighting ApplianceControls Turn off all electric power to the appliance On position. The ON/OFF switch mayLighting Appliance IPI Ignition Final inspection byFrequently Asked Questions Initial Break-in ProcedureAfter Appliance is Lit Troubleshooting Symptom Possible Cause Corrective ActionIntellifire Ignition System flame has been lit, flame Maintaining and Servicing Appliance Maintenance Tasks Inspect Maintenance TasksAppliance Dimension Diagram Without Stone Surround Reference MaterialsHearth Pad Location Inches MillimeterAppliance Dimension Diagram With Stone Surround Appliance Dimensions with Stone SurroundVent Components Diagram SLP Series Vent ComponentsVent Components List MiscellaneousLog Set Assembly Service PartsService Parts List StockedAt Depot Description Comments Part NumberStocked Bottom Plate Assembly PalomaCONDITIONS, Exclusions & Limitation of Liability Limited Lifetime Warranty Contact Information