PDX SERVICE PROCEDURE VIII

Safety Circuit Voltage Trace

Safety Circuit Voltage Trace

NOTE: This procedure assumes a cool tank.

WARNING

120 volt potential exposure. Use caution

making voltage checks to avoid personal injury.

27

Step 2. Remove three screws (Phillips Screw driver) from control access cover on blower and remove cover (see photo 26).

Position gas control switch to the “ON”

 

 

 

position and adjust thermostat dial to call

 

 

 

for heat, Is there 10 to 13 VAC between

Is LED on gas valve flashing

 

red wire leading to blower temperature N

Y

 

 

 

the “heartbeat” code

 

switch and green ground wire?

 

(alternating bright/dim)

 

Blower must be running during this

 

 

 

 

voltage check.

 

N

 

 

 

(see photo 28)

 

 

 

 

 

 

Y

Verify 120VAC to gas

 

 

 

 

 

 

 

 

 

 

control (see page 30)

 

 

 

 

 

 

 

No voltage from gas control,

call for technical support.

Is there 10 to 13 VAC between yellow

Is there continuity

 

Check for loose or

wire leading from pressure switch and N

through blower

Y

broken wire

green ground wire?

 

temperature switch?

 

connection at switch

(see photo 28)

(see page 21)

 

terminals

 

Y

 

N

 

 

 

 

 

 

 

 

 

Determine cause of blower

 

 

 

Correct igniter/

temperature switch

 

 

 

 

sensor problem.

activation and correct.

 

 

 

 

 

 

 

 

 

Do you hear or can you N see the igniter sparking?

Y

Safety circuit voltage is OK.

If burner does not light, observe LED flash code on gas valve and refer to troubleshooting section on page 12

Check igniter/sensor

Y

Faulty cord set or

(see page 16)

 

gas control.

is igniter/sensor OK?

 

 

Green ground wire

 

 

28

 

 

 

 

Red wire leading to

 

 

blower temp. switch

Yellow wire leading from pressure switch

Page 30

30

Image 30
Contents Service Manual Denotes Warranty YearsTable of Contents PDX Series Introduction Tools Required for Service How to Use This ManualSpecifications PDX Series Control Timings Power up Sequence Sequence of OperationAbnormal Operation Pressure Switch/Blower Temperature Fault Green LED Indicator TroubleshootingProbable Cause Service Status Procedure LED StatusTroubleshooting LED Status Burner Inspection and Air Shutter Adjustment Cast Iron Burner Air Shutter AdjustmentAir Shutter Nut Burner Cleaning Burner Surface area Feedline nut Pilot tubing nut Port areaFeedline nut Pilot tubing nut Ferrule Pilot Inspection, Testing and ReplacementIgniter/flame Sense wire OrificeExhaust Pressure Switch Testing Volt potential exposure. Use cautionMaking voltage checks to avoid personal injury From blower housing Exhaust Pressure Switch ReplacementSlide pressure switch in direction To avoid personal injuryTo call for heat, this will start the blower Inlet Pressure SwitchSwitch for blockage Is there blockage? SeeInlet Pressure Switch Replacement Remove screwsBlower Testing Volt potential exposure. Use caution whenRemove exhaust Blower InstallationBlower removal Blower Cord Sets Blower Mounting ScrewsBlower Temperature Switch Testing Blower Temperature Switch Replacement Gas Control Testing Thermal Well TestingIf Control has gone into TCO lockout due to Determine Water Temperature Inside Tank Sensor Resistance at Various TemperaturesGas Control & Thermal Well Removal From Water Heater Gas Control Removal From Thermal WellGas Control Assembly to Thermal Well Flammable Vapor Device Testing Safety Circuit Voltage Trace Shown in photo Wires as shown ControlVAC Circuit Trace Across black & white YDip Tube Inspection and Replacement Anode Inspection and Replacement Flue baffle Inner Door Removal Procedure Installation of Inner Door With Gasket Installation of inner door with gasket from Glossary of Terms Parts List Parts@bradfordwhite.com Techserv@bradfordwhite.com
Related manuals
Manual 28 pages 24.42 Kb