PDX Series
Specifications
Control Timings
| Ignition State |
| Timing | ||
|
|
|
|
|
|
2 Seconds | |||||
|
| ||||
Trial for Ignition | 90 Seconds | ||||
|
| ||||
Flame Stabilization Period | 3 Seconds | ||||
|
| ||||
15 Seconds | |||||
|
| ||||
Flame Failure Response Time | 1.5 Seconds (2 second. Maximum; 1 second minimum.) | ||||
|
| ||||
15 Seconds | |||||
|
| ||||
PS Fault Delay (failed open/close) | Retry after 2 Minutes | ||||
|
| ||||
Soft Lockout | Retry after 5 Minutes | ||||
|
| ||||
TCO Limit Lockout | Indefinite (cycle power to restart) | ||||
|
| ||||
Verify Resistive Delay | Retry after 2 Minutes (repeats 5 times) | ||||
|
| ||||
Simulated Resistive Load Lockout | Indefinite (cycle power to restart) | ||||
|
| ||||
Hardware Error Lockout | Indefinite (self clears if fault clears for at least 15 seconds) | ||||
|
|
|
|
|
|
Wiring Diagram
Page 8