PDX Series
PDX SERVICE PROCEDURE VI
Gas Control/Thermal Well Testing and
Replacement
Gas Control Testing
See pages 27 & 28 for gas control input & output testing.
Thermal Well Testing
If Control has gone into TCO lockout due to
excessive tank temperature (four flash, 3 second pause) reset control by rotating knob of temperature control to the minimum setting for at least 6 seconds before returning to desired temperature setting.
Disconnect thermal
well wire harness
Observe heater operation. If control
continues to lockout due to excessive tank temperature, proceed to thermal well testing to determine cause.
Thermal well testing
Position gas control power switch to the “OFF” position and disconnect thermal well harness from gas control.
Using a
19 | 20 |
CAUTION
DO NOT use standard multimeter probes for this test. Doing so will damage connector. Use special pin type electronic probes or small diameter wire pins inserted into connector.
Using a
Alternate the probe on the outside position to the opposite outside wire position (see photo 24).
Once the thermal well resistance values are known, the water |
|
| |
temperature must also be known to determine if the resistance | N | Replace thermal well | |
values are correct. See page 25 to obtain water temperature. | |||
| (see page 27) | ||
|
|
Are thermal well resistance values correct?
Y
Replace gas control
(see page 27)
Page 25
25