A.O. Smith COF-199 manual Operation, Filling, Start-Up

Page 10

FIGURE 15

OPERATION

GENERAL

Never operate the heater unless the tank is filled with water and a temperature and pressure relief valve is installed.

FILLING

1.Oil burner electrical disconnect switch should be in the "OFF" position

2.Close the heater drain valve.

3.Open a nearby hot water faucet to allow the air in the system to escape.

4.Fully open the cold water inlet valve, filling the heater and piping.

5.Close the hot water faucet as water starts to flow from the opening, Leave the cold water inlet valve fully open. The heater is now ready to start-up if being placed in operation for the first time.

START-UP

The following checks should be made by the installer when the heater is placed into operation for the first time:

1.Check all factory and field made water, oil and electrical connections for tightness. Also check flue gas disposal provisions on top the heater.

Repair any water and oil leaks. Tighten electrical and flue connections as necessary.

2.Where the water heater or water heating systems includes a circulating pump, it may need to be lubricated before operated. The tube of lubricant supplied with the pump includes directions for use.

Field installed circulating pumps should be all bronze construction.

Be sure the oil burner, related piping, valves and controls are in place, adjusted and ready for operation before turning on the electricity.

3.Adjust the heater mounted control as follows:

THERMOSTAT (adjustable) set for desired water temperature.

It is suggested the thermostat be turned to the lowest setting which satisfies the hot water requirements of the system. This helps minimize scale formation in the heater.

HIGH LIMIT (not adjustable, manual reset) factory set to cutout at 195° F (90.5°C).

If the high limit is actuated, the safety primary control will cause the oil burner to shut down. See SAFETY PRIMARY CONTROL, page 21.

To reset the safety primary control, depress and hold the red button on the control for 30 seconds until the LED flashes twice.

Depress red button one time only. If burner does not operate after depressing red button one time, call service man.

4.Turn on the oil burner electrical disconnect switch.

5.The heater will begin normal operation on the thermostat's "call for heat".

10

Image 10
Contents Place These Instructions Adjacent to Heater Notify Owner to Keep for Future ReferenceTank Approx Features and SpecificationsCapacity EFF Table of Contents ApprovalsSafety InstallationCombustion and Ventilation AIR Proper Installation on Combustible FlooringClearances Chemical Vapor CorrosionVent Connector and Draft Regulator Flue GAS VentingClosed Water System Water PipingFuel Systems Gravity FEED, Supply Line ONLY, Installation Burner InstallationTypical Heater Installation Figure System TypesFuel Pump OIL Pump & Nozzle SpecificationsAssembly of the OIL Burner to the Heater BurnerFilling OperationSTART-UP SELF-CLEANING Eliminator Water Temperature ControlHigh Limit Switch E.C.O Burner Certificate Combustion TestMaintenance Flo-jug Method of Deliming Deliming the COF Water HeaterVent System Circulating PumpSoot Removal Typical Heater Flueway and Flue BaffleInset B Installation DiagramsInstall in Accordance with Local Codes Inset aSingle Temperature or Booster Pipe to Open DrainInset B Install in Accordance with Local Codes Inset a Electrical Wiring Replacement Check List and Service InformationNot Enough or no HOT Water Water Heater Makes Sounds Burner STARTS-WONT OperateWater is TOO HOT Water Leakage is SuspectedSafety Primary Control Combustion Test SpecificationsNormal START, but Locks OUT on Safety ProcedureOIL Burner Troubleshooting TroubleshootingTrouble Cause Remedy Tank Service and Repair ExpensesClaim Procedure ALL Other PartsCommercial Water Heater Parts List Smith Water Products CO., INC+WIRE Cleanout AssemblyLabels Page Page Asme Impriméaux É.-UPoids approx Lexpédition Dimensions COFCaractéristiques ET Données Techniques StandardIdentification Table DES MatièresHomologations COF 455 940 CO5MOO6721Installation SécuritéAIR DE Combustion ET DE Ventilation Installation Correcte SUR UN Plancher CombustibleDégagement À Prévoir Corrosion DUE AUX Vapeurs ChimiquesÉvacuation DES GAZ DE Combustion Tableau 4 Dimensions Suggérées Pour LES Raccords D’ÉVENTInstallation Appropriée DU Raccord D’ÉVENT Cheminée Raccord D’ÉVENT ET Régulateur DE TirageRobinet DE Vidange ET Panneaux D’ACCÈS Tuyauterie D’EAUSystème EN Circuit Fermé Systèmes D’ALIMENTATION EN CombustibleTableau Installation DU BrûleurInstallation Type DE CHAUFFE-EAU Figure Types DE SystèmesMontage DU Brûleur SUR LE CHAUFFE-EAU Pompe À MazoutBrûleur Tableau 8 Caractéristiques DES Pompes ET DES Buses À MazoutRemplissage Mise EN Marche ET UtilisationMise EN Marche Initiale Certificat DU Brûleur Test DE Combustion Réglage DE LA Température DE L’EAULimiteur DE Température Système Autonettoyant EliminatorEntretien Méthode de détartrage Flo-Jug Détartrage DU CHAUFFE-EAU COFEnlèvement DE LA Suie Pompe DE CirculationConduit DE Fumée ET Chicane D’UN CHAUFFE-EAU Type Encadré B Schémas D’INSTALLATIONInstaller Conformément AUX Codes Locaux Encadré aSystème À UNE Seule Température OU Surchauffeur Encadré B Installer Conformément AUX Codes Locaux Encadré B Insuffisance OU Absence D’EAU Chaude Liste DE Contrôle ET Renseignements SUR LE ServiceRemplacement DU Câblage Électrique Ensemble DE Collecteur Pour Trois AppareilsBruits EN Provenance DU CHAUFFE-EAU LE Brûleur Démarre Mais NE Fonctionne PASEAU Trop Chaude Fuite D’EAU SoupçonnéeDémarrage Normal Suivi ’UN Verrouillage DE Sécurité Commande Primaire DE SécuritéSpécifications Pour LE Test DE Combustion Perte DE LA Flamme Après UN Allumage NormalProblème Cause Mesure Corrective DépannageTableau 10 Dépannage DU Brûleur À Mazout Modèles COF Garantie Limitée Autres PiècesSmith Water Products CO., INC COF Article Description