A.O. Smith COF-199 manual Trouble Cause Remedy, OIL Burner Troubleshooting

Page 23

TROUBLESHOOTING

TABLE 10 - OIL BURNER TROUBLESHOOTING

TROUBLE

CAUSE

REMEDY

 

 

 

 

 

 

Oil level below intake line in supply tank.

Fill tank with oil.

 

 

Clogged strainer or filter.

Remove and clean strainer. Replace filter element.

 

 

 

Clogged nozzle.

Replace nozzle.

 

 

Air leak in intake line.

Tighten all fittings in intake line. Tighten unused intake

 

 

 

 

port plug. Check filter cover and gasket.

 

 

Restricted intake line. (High vacuum reading).

Replace any kinked tubing and check any valves in

No Oil Flow

 

intake line.

A two line pipe system that becomes air bound.

Check for and insert by-pass plug. Make sure return

at Nozzle

 

line is below oil level in tank.

 

 

A single line pipe system that becomes air bound.

Loosen gauge port plug or air bleed valve and bleed oil

 

 

 

for 15 seconds after foam is gone in bleed hose, Check

 

 

 

intake line fittings for tightness. Check all fuel pump plugs

 

 

 

for tightness.

 

 

Slopping or broken coupling.

Replace coupling.

 

 

 

Rotation of motor and fuel unit pump is not the

 

 

 

 

same as indicated by arrow on the pad at top of unit.

Install fuel pump with correct rotation.

 

 

Frozen fuel pump shaft.

Replace fuel pump. Check for water and dirt in tank.

 

 

 

Loosen plugs and fittings.

Tighten with good quality thread sealer.

Oil Leak

Leak at pressure adjusting screw or nozzle plug.

Replace fuel pump.

 

Blown seal (single-pipe system)

Check to see if by-pass plug has been left in fuel pump.

 

 

 

 

Replace fuel pump.

 

 

Seal leaking.

Replace fuel pump.

 

 

Cover.

Tighten cover screws.

 

 

Bad coupling alignment.

Loosen fuel pump mounting screws slightly and shift

Noisy

 

fuel pump in different positions until noise is eliminated.

Operation

 

Retighten mounting screws.

 

 

Air in inlet line.

Check all connections. Use only good flare fittings.

 

 

Tank turn on two line pipe system and inside tank.

Install return line hum eliminator.

 

 

Partially clogged strainer or filter.

Remove and clean strainer.

 

 

 

Air leak in intake line.

Tighten all fittings.

 

 

Air leaking around cover.

Be sure strainer cover screws are tightened securely.

 

 

 

 

Check for damaged cover gasket.

Low Oil

Defective gauge

Check gauge against master gauge or other gauge.

Pressure

Nozzle capacity is greater than fuel pump capacity.

Replace fuel unit with unit of correct capacity.

 

 

 

To determine the cause of improper cut-off, insert

 

 

 

 

a pressure gauge in the nozzle port of the fuel pump.

 

 

 

 

After a minute of operation, shut burner down. If the

 

 

 

 

pressure drops from normal operating pressure and

 

 

 

 

stabilizes, the fuel pump is operating properly and air

 

 

 

 

is the cause of improper cut-off. If, however, the

 

 

 

 

pressure drops to 0 psi, fuel unit should be replaced.

 

 

Improper

NOTE: Never use the amount of pressure drop as an

 

 

Nozzle

indication of the quality or speed of cut-off.

 

 

Cut-Off

Filter leaks.

Check face of cover and gasket for damage.

 

 

 

Strainer cover loose.

Tighten 4 screws on cover.

 

 

Air pocket between cut-off valve and nozzle.

Run burner, stopping and starting unit, until smoke

 

 

 

and after-fire disappears.

 

 

Air leak in intake line.

Tighten intake fittings. Tighten unused intake port and

 

 

 

return plug.

 

 

Partially clogged nozzle strainer.

Clean strainer or change nozzle.

 

 

 

Leak at nozzle adaptor.

Change nozzle and adaptor.

 

 

 

 

 

 

23

Image 23
Contents Notify Owner to Keep for Future Reference Place These Instructions Adjacent to HeaterCapacity EFF Features and SpecificationsTank Approx Approvals Table of ContentsInstallation SafetyChemical Vapor Corrosion Proper Installation on Combustible FlooringClearances Combustion and Ventilation AIRFlue GAS Venting Vent Connector and Draft RegulatorFuel Systems Water PipingClosed Water System System Types Burner InstallationTypical Heater Installation Figure Gravity FEED, Supply Line ONLY, InstallationBurner OIL Pump & Nozzle SpecificationsAssembly of the OIL Burner to the Heater Fuel PumpSTART-UP OperationFilling Burner Certificate Combustion Test Water Temperature ControlHigh Limit Switch E.C.O SELF-CLEANING EliminatorMaintenance Deliming the COF Water Heater Flo-jug Method of DelimingTypical Heater Flueway and Flue Baffle Circulating PumpSoot Removal Vent SystemInset a Installation DiagramsInstall in Accordance with Local Codes Inset BPipe to Open Drain Single Temperature or BoosterInset B Install in Accordance with Local Codes Inset a Not Enough or no HOT Water Check List and Service InformationElectrical Wiring Replacement Water Leakage is Suspected Burner STARTS-WONT OperateWater is TOO HOT Water Heater Makes SoundsProcedure Combustion Test SpecificationsNormal START, but Locks OUT on Safety Safety Primary ControlTrouble Cause Remedy TroubleshootingOIL Burner Troubleshooting ALL Other Parts Service and Repair ExpensesClaim Procedure TankSmith Water Products CO., INC Commercial Water Heater Parts ListLabels Cleanout Assembly+WIRE Page Page Impriméaux É.-U AsmeStandard Dimensions COFCaractéristiques ET Données Techniques Poids approx LexpéditionCOF 455 940 CO5MOO6721 Table DES MatièresHomologations IdentificationSécurité InstallationCorrosion DUE AUX Vapeurs Chimiques Installation Correcte SUR UN Plancher CombustibleDégagement À Prévoir AIR DE Combustion ET DE VentilationRaccord D’ÉVENT ET Régulateur DE Tirage Tableau 4 Dimensions Suggérées Pour LES Raccords D’ÉVENTInstallation Appropriée DU Raccord D’ÉVENT Cheminée Évacuation DES GAZ DE CombustionSystèmes D’ALIMENTATION EN Combustible Tuyauterie D’EAUSystème EN Circuit Fermé Robinet DE Vidange ET Panneaux D’ACCÈSTypes DE Systèmes Installation DU BrûleurInstallation Type DE CHAUFFE-EAU Figure TableauTableau 8 Caractéristiques DES Pompes ET DES Buses À Mazout Pompe À MazoutBrûleur Montage DU Brûleur SUR LE CHAUFFE-EAUMise EN Marche Initiale Mise EN Marche ET UtilisationRemplissage Système Autonettoyant Eliminator Réglage DE LA Température DE L’EAULimiteur DE Température Certificat DU Brûleur Test DE CombustionEntretien Détartrage DU CHAUFFE-EAU COF Méthode de détartrage Flo-JugConduit DE Fumée ET Chicane D’UN CHAUFFE-EAU Type Pompe DE CirculationEnlèvement DE LA Suie Encadré a Schémas D’INSTALLATIONInstaller Conformément AUX Codes Locaux Encadré BSystème À UNE Seule Température OU Surchauffeur Encadré B Installer Conformément AUX Codes Locaux Encadré B Ensemble DE Collecteur Pour Trois Appareils Liste DE Contrôle ET Renseignements SUR LE ServiceRemplacement DU Câblage Électrique Insuffisance OU Absence D’EAU ChaudeFuite D’EAU Soupçonnée LE Brûleur Démarre Mais NE Fonctionne PASEAU Trop Chaude Bruits EN Provenance DU CHAUFFE-EAUPerte DE LA Flamme Après UN Allumage Normal Commande Primaire DE SécuritéSpécifications Pour LE Test DE Combustion Démarrage Normal Suivi ’UN Verrouillage DE SécuritéTableau 10 Dépannage DU Brûleur À Mazout DépannageProblème Cause Mesure Corrective Autres Pièces Modèles COF Garantie LimitéeSmith Water Products CO., INC COF Article Description