DRAINING

The water heater must be drained if it is to be shut down and exposed to freezing temperatures. Maintenance and service procedures may also require draining the heater.

1.Turn off the oil burner electrical disconnect switch.

If required by the reason for draining the heater, turn off the oil line supply valve.

2.Close the cold water inlet valve to heater.

3.Open a nearby hot water faucet to vent the system.

4.Open the heater drain valve.

5.If the heater is being drained for an extended shutdown, it is suggested the drain valve be left open during this period.

Follow FILLING instructions when restarting hot water service.

MAINTENANCE

GENERAL

Water heater maintenance includes periodic tank flushing and cleaning, and removal of lime scale. The oil burner should be inspected and adjusted to maintain proper combustion. Where used, the water heating system circulating pump should be oiled (See table 9).

The depth of lime buildup should be measured periodically. Heaters will have about 2" (50.8 mm) of lime buildup when the level of lime has reached the bottom of the cleanout opening or about 1" of lime buildup if it has reached the drain valve opening. A schedule for deliming should be setup, based on the amount of time it would take for a 1" (25.4 mm) buildup of lime.

Example 1: Initial inspection shows 1/2" (12.7 mm) of lime accumulation. Therefore, the heater can be delimed once a year.

Example 2: Initial inspection shows 2" (50.8 mm) of lime accumulation. Therefore, the heater should be delimed every 3 months.

Following are the instructions for performing some of the recommended maintenance. Oil burner inspection and adjustment should be performed by a competent technician.

TABLE 9 SUGGESTED MAINTENANCE SCHEDULE

 

 

 

Semi-

 

Relief Valve

Lift Lever

Annually

 

 

 

Flushing

Monthly

 

 

 

Sediment

Semi-

 

 

 

Removal

Annually

 

 

 

Anode

Semi

 

Tank

Inspection

Annually

 

 

 

Lime Scale

As

UN•LIME®

 

 

Removal

Required

Delimer

Circulating

 

Four

SAE No. 20 non-detergent

Pump

Oiling

Months

motor oil

 

 

Inspection

 

Combustion test

 

 

and

Semi-

kit & test specifications

Oil Burner

Adjustment

Annually

(Page 26)

 

 

Nozzle

Semi-

 

 

 

Replacement

Annually

New Nozzle

Flue Baffle

 

 

 

Pipe

Cleaning

Annually

Wire Brush

Venting

 

Semi-

 

System

Inspected

Annually

 

* Replacement gasket, A.O. Smith Part No. 99038

RELIEF VALVES

At least twice a year, the system relief valves should be checked to ensure that they are in operating condition. To check a relief valve, lift the lever at the end of the valve several times. The valve should seat properly and operate freely.

If water does not flow, remove the valve and inspect for obstructions or corrosion. Replace with a new valve of the recommended size as necessary. Inspection of the valve should be performed at least every three years. Do not attempt to repair the valve, as this could result in improper operating and a tank explosion. In areas with poor water conditions, it may be necessary to inspect the T&P valve more often than twice a year.

DANGER

BEFORE MANUALLY OPERATING A RELIEF VALVE, MAKE SURE THAT DRAIN LINE HAS BEEN ATTACHED TO THE VALVE TO DIRECT THE DISCHARGE TOAN OPEN DRAIN. FAILURE TO TAKE THIS PRECAUTION COULD MEAN CONTACT WITH EXTREMELY HOT WATER PASSING OUT OF THE VALVE DURING THIS CHECK OPERATION.

If the temperature and pressure relief valve on the heater discharges periodically or continuously, it may be due to thermal expansion of water in a closed water supply system, or it may be due to a faulty relief valve.

Thermal expansion is the normal response of water when it is heated. In a closed system, thermal expansion will cause the system pressure to build until the relief valve actuation pressure is equaled. Then, the relief valve will open, allowing water to escape, slightly lowering the pressure.

Your water supplier or local plumbing inspector will know how to best correct this situation. Two common corrections are listed in the Checklist and Service Information which appears later in this manual.

ABOVEALL, DO NOT PLUG THETEMPERATUREAND PRESSURE RELIEF VALVE. THIS IS NOT A SOLUTION AND CAN CREATE A HAZARDOUS SITUATION.

FLUSHING

1.Turn off the oil burner electrical disconnect switch.

2.Open the drain valve and allow water to flow until it runs clean.

3.Close the drain valve when finished flushing.

4.Turn on the oil burner electrical disconnect switch.

SEDIMENT REMOVAL

Water borne impurities consist of fine particles of soil and sand which settle out and form a layer of sediment on the bottom of the tank.

For convenience, sediment removal and lime scale removal should be

performed at the same time.

LIME SCALE REMOVAL

The amount of calcium carbonate (Lime) released from water is in direct proportion to water temperature and usage, see chart. The higher the water temperature or water usage , the more lime deposits are dropped out of the water. This is the lime scale which forms in pipes, heaters and on cooking utensils.

WATER USAGE IN GALLONS PER DAY POUNDS OF LIME DEPOSITED VS. TEMPERATURE AND WATER USAGE

12

Image 12
Contents Place These Instructions Adjacent to Heater Notify Owner to Keep for Future ReferenceFeatures and Specifications Tank ApproxCapacity EFF Table of Contents ApprovalsSafety InstallationProper Installation on Combustible Flooring ClearancesCombustion and Ventilation AIR Chemical Vapor CorrosionVent Connector and Draft Regulator Flue GAS VentingWater Piping Closed Water SystemFuel Systems Burner Installation Typical Heater Installation FigureGravity FEED, Supply Line ONLY, Installation System TypesOIL Pump & Nozzle Specifications Assembly of the OIL Burner to the HeaterFuel Pump BurnerOperation FillingSTART-UP Water Temperature Control High Limit Switch E.C.OSELF-CLEANING Eliminator Burner Certificate Combustion TestMaintenance Flo-jug Method of Deliming Deliming the COF Water HeaterCirculating Pump Soot RemovalVent System Typical Heater Flueway and Flue BaffleInstallation Diagrams Install in Accordance with Local CodesInset B Inset aSingle Temperature or Booster Pipe to Open DrainInset B Install in Accordance with Local Codes Inset a Check List and Service Information Electrical Wiring ReplacementNot Enough or no HOT Water Burner STARTS-WONT Operate Water is TOO HOTWater Heater Makes Sounds Water Leakage is SuspectedCombustion Test Specifications Normal START, but Locks OUT on SafetySafety Primary Control ProcedureTroubleshooting OIL Burner TroubleshootingTrouble Cause Remedy Service and Repair Expenses Claim ProcedureTank ALL Other PartsCommercial Water Heater Parts List Smith Water Products CO., INCCleanout Assembly +WIRELabels Page Page Asme Impriméaux É.-UDimensions COF Caractéristiques ET Données TechniquesPoids approx Lexpédition StandardTable DES Matières HomologationsIdentification COF 455 940 CO5MOO6721Installation SécuritéInstallation Correcte SUR UN Plancher Combustible Dégagement À PrévoirAIR DE Combustion ET DE Ventilation Corrosion DUE AUX Vapeurs ChimiquesTableau 4 Dimensions Suggérées Pour LES Raccords D’ÉVENT Installation Appropriée DU Raccord D’ÉVENT CheminéeÉvacuation DES GAZ DE Combustion Raccord D’ÉVENT ET Régulateur DE TirageTuyauterie D’EAU Système EN Circuit FerméRobinet DE Vidange ET Panneaux D’ACCÈS Systèmes D’ALIMENTATION EN CombustibleInstallation DU Brûleur Installation Type DE CHAUFFE-EAU FigureTableau Types DE SystèmesPompe À Mazout BrûleurMontage DU Brûleur SUR LE CHAUFFE-EAU Tableau 8 Caractéristiques DES Pompes ET DES Buses À MazoutMise EN Marche ET Utilisation RemplissageMise EN Marche Initiale Réglage DE LA Température DE L’EAU Limiteur DE TempératureCertificat DU Brûleur Test DE Combustion Système Autonettoyant EliminatorEntretien Méthode de détartrage Flo-Jug Détartrage DU CHAUFFE-EAU COFPompe DE Circulation Enlèvement DE LA SuieConduit DE Fumée ET Chicane D’UN CHAUFFE-EAU Type Schémas D’INSTALLATION Installer Conformément AUX Codes LocauxEncadré B Encadré aSystème À UNE Seule Température OU Surchauffeur Encadré B Installer Conformément AUX Codes Locaux Encadré B Liste DE Contrôle ET Renseignements SUR LE Service Remplacement DU Câblage ÉlectriqueInsuffisance OU Absence D’EAU Chaude Ensemble DE Collecteur Pour Trois AppareilsLE Brûleur Démarre Mais NE Fonctionne PAS EAU Trop ChaudeBruits EN Provenance DU CHAUFFE-EAU Fuite D’EAU SoupçonnéeCommande Primaire DE Sécurité Spécifications Pour LE Test DE CombustionDémarrage Normal Suivi ’UN Verrouillage DE Sécurité Perte DE LA Flamme Après UN Allumage NormalDépannage Problème Cause Mesure CorrectiveTableau 10 Dépannage DU Brûleur À Mazout Modèles COF Garantie Limitée Autres PiècesSmith Water Products CO., INC COF Article Description