A TYPICAL HEATER INSTALLATION - FIGURE 10

Refer to pages 2, 3, and 4 in this manual for more information about burner series numbers and characteristics for adaptability to the following systems.

SYSTEM TYPES

Single Stage, Supply Line Only: The bottom of the oil storage tank must be above the level of the fuel unit, fig. 11. The fuel oil will flow by gravity to the burner. A single pipe is run between the tank and fuel unit. Burner Series No. 940 is from this type of service as shipped (the bypass plug is not installed).

TABLE 6

Distance

Max.

 

Distance

Max.

Tank

Run length

 

Tank

Run Length

Bottom

Ft. (M)

 

Bottom

Ft. (M)

Below

 

 

 

Below

 

 

 

 

 

 

 

Pump

3/8"

1/2"

 

Pump

3/8"

1/2"

Plug

O.D.

O.D.

 

Plug

O.D.

O.D.

Ft. (M)

Tubing

Tubing

 

Ft. (M)

Tubing

Tubing

1 (0.3)

66 (20.1)

100 (30.4)

 

6 (1.8)

36 (10.9)

100 (30.4)

2 (0.6)

55 (16.7)

100 (30.4)

 

7 (2.1)

31 (9.4)

100 (30.4)

3 (0.9)

50 (15.2)

100 (30.4)

 

8 (2.4)

26 (7.9)

100 (30.4)

4 (1.2)

45 (13.7)

100 (30.4)

 

9 (2.7)

21 (6.4)

83 (25.2)

5 (1.5)

40 (12.1)

100 (30.4)

 

10 (3.0)

16 (4.8)

64 (19.5)

Two Stage, Supply and Return Lines: This system, fig. 13, is required when long lines and high lifts (requiring up to 20" of vacuum and 10' vertical lift) are encountered. Burner Series No. 941 is used in this service. Bypass plug must be installed.

A GRAVITY FEED, SUPPLY LINE ONLY, INSTALLATION

FIGURE 11

If the bottom of the oil tank is at least 2 inches (50.8 mm) higher than the plug opening at which the supply line connects to the fuel pump, a single- line gravity-feed system with 3/8" O.D. tubing may be used with a maximum run length of 100 feet.

A two stage pump may be used on one line, gravity feed installations. The pump will function as a single stage unit when the by-pass plug is not installed.

Single Stage, Supply and Return Lines. This type of system, fig. 12, is self-priming. Burner Series No. 940 with by-pass plug field installed, is for this type of service.

If the tank bottom is no lower than 10 feet below the plug, a single stage pump may be used but, it must be a two line system with maximum tubing runs (which includes lift) as shown in Table 6.

A SINGLE STAGE (LOW LIFT), SUPPLY AND RETURN

LINE INSTALLATION - FIGURE 12

A TWO STAGE (HIGH LIFT), SUPPLY AND RETURN

LINE INSTALLATION - FIGURE 13

If the tank(s) bottom is lower than the plug by more than 10 feet, a two stage pump with a two line system must be used with maximum tubing runs (which includes lift) as shown in Table 7.

TABLE 7

Distance

Max.

 

Distance

Max.

Tank

Run length

 

Tank

Run Length

Bottom

Ft. (M)

 

Bottom

Ft. (M)

Below

 

 

 

Below

 

 

 

 

 

 

 

Pump

3/8"

1/2"

 

Pump

3/8"

1/2"

Plug

O.D.

O.D.

 

Plug

O.D.

O.D.

Ft. (M)

Tubing

Tubing

 

Ft. (M)

Tubing

Tubing

1 (0.3)

74 (22.5)

100 (30.4)

 

9 (2.7)

51 (15.5)

100 (30.4)

2 (0.6)

71 (21.6)

100 (30.4)

 

10 (3.0)

48 (14.6)

100 (30.4)

3 (0.9)

69 (21.0)

100 (30.4)

 

11 (3.3)

45 (13.7)

100 (30.4)

4 (1.2)

66 (20.1)

100 (30.4)

 

12 (3.6)

42 (12.8)

100 (30.4)

5 (1.5)

63 (19.2)

100 (30.4)

 

13 (3.9)

39 (11.8)

100 (30.4)

6 (1.8)

60 (18.2)

100 (30.4)

 

14 (4.2)

37 (11.2)

100 (30.4)

7 (2.1)

57 (17.3)

100 (30.4)

 

15 (4.5)

34 (10.3)

100 (30.4)

8 (2.4)

54 (16.4)

100 (30.4)

 

 

 

 

MULTIPLE HEATER FUEL LINES

Where two or more heaters form a water heating system, each burner shall have an entirely separate oil supply line from the tank to the burner.

BURNER INSTALLATION

GENERAL

An oil Burner Certificate is packed with the oil burner. Following the burner manual installation the necessary tests shall be performed and the results recorded on the certificate, see BURNER CERTIFICATE. The certificate and this instruction manual must be left with the user for future reference.

Check to be certain the heater and burner model numbers are alike and the oil pump characteristics are proper for the job. See IDENTIFICATION, page 3.

8

Image 8
Contents Place These Instructions Adjacent to Heater Notify Owner to Keep for Future ReferenceCapacity EFF Features and SpecificationsTank Approx Table of Contents ApprovalsSafety InstallationProper Installation on Combustible Flooring ClearancesCombustion and Ventilation AIR Chemical Vapor CorrosionVent Connector and Draft Regulator Flue GAS VentingFuel Systems Water PipingClosed Water System Burner Installation Typical Heater Installation FigureGravity FEED, Supply Line ONLY, Installation System TypesOIL Pump & Nozzle Specifications Assembly of the OIL Burner to the HeaterFuel Pump BurnerSTART-UP OperationFilling Water Temperature Control High Limit Switch E.C.OSELF-CLEANING Eliminator Burner Certificate Combustion TestMaintenance Flo-jug Method of Deliming Deliming the COF Water HeaterCirculating Pump Soot RemovalVent System Typical Heater Flueway and Flue BaffleInstallation Diagrams Install in Accordance with Local CodesInset B Inset aSingle Temperature or Booster Pipe to Open DrainInset B Install in Accordance with Local Codes Inset a Not Enough or no HOT Water Check List and Service InformationElectrical Wiring Replacement Burner STARTS-WONT Operate Water is TOO HOTWater Heater Makes Sounds Water Leakage is SuspectedCombustion Test Specifications Normal START, but Locks OUT on SafetySafety Primary Control ProcedureTrouble Cause Remedy TroubleshootingOIL Burner Troubleshooting Service and Repair Expenses Claim ProcedureTank ALL Other PartsCommercial Water Heater Parts List Smith Water Products CO., INCLabels Cleanout Assembly+WIRE Page Page Asme Impriméaux É.-UDimensions COF Caractéristiques ET Données TechniquesPoids approx Lexpédition StandardTable DES Matières HomologationsIdentification COF 455 940 CO5MOO6721Installation SécuritéInstallation Correcte SUR UN Plancher Combustible Dégagement À PrévoirAIR DE Combustion ET DE Ventilation Corrosion DUE AUX Vapeurs ChimiquesTableau 4 Dimensions Suggérées Pour LES Raccords D’ÉVENT Installation Appropriée DU Raccord D’ÉVENT CheminéeÉvacuation DES GAZ DE Combustion Raccord D’ÉVENT ET Régulateur DE TirageTuyauterie D’EAU Système EN Circuit FerméRobinet DE Vidange ET Panneaux D’ACCÈS Systèmes D’ALIMENTATION EN CombustibleInstallation DU Brûleur Installation Type DE CHAUFFE-EAU FigureTableau Types DE SystèmesPompe À Mazout BrûleurMontage DU Brûleur SUR LE CHAUFFE-EAU Tableau 8 Caractéristiques DES Pompes ET DES Buses À MazoutMise EN Marche Initiale Mise EN Marche ET UtilisationRemplissage Réglage DE LA Température DE L’EAU Limiteur DE TempératureCertificat DU Brûleur Test DE Combustion Système Autonettoyant EliminatorEntretien Méthode de détartrage Flo-Jug Détartrage DU CHAUFFE-EAU COFConduit DE Fumée ET Chicane D’UN CHAUFFE-EAU Type Pompe DE CirculationEnlèvement DE LA Suie Schémas D’INSTALLATION Installer Conformément AUX Codes LocauxEncadré B Encadré aSystème À UNE Seule Température OU Surchauffeur Encadré B Installer Conformément AUX Codes Locaux Encadré B Liste DE Contrôle ET Renseignements SUR LE Service Remplacement DU Câblage ÉlectriqueInsuffisance OU Absence D’EAU Chaude Ensemble DE Collecteur Pour Trois AppareilsLE Brûleur Démarre Mais NE Fonctionne PAS EAU Trop ChaudeBruits EN Provenance DU CHAUFFE-EAU Fuite D’EAU SoupçonnéeCommande Primaire DE Sécurité Spécifications Pour LE Test DE CombustionDémarrage Normal Suivi ’UN Verrouillage DE Sécurité Perte DE LA Flamme Après UN Allumage NormalTableau 10 Dépannage DU Brûleur À Mazout DépannageProblème Cause Mesure Corrective Modèles COF Garantie Limitée Autres PiècesSmith Water Products CO., INC COF Article Description