KitchenAid W10284348A Gas Supply Requirements, Type of Gas, Gas Supply Line

Page 9

Gas Supply Requirements

WARNING

Explosion Hazard

Use a new CSA International approved gas supply line.

Install a shut-off valve.

Securely tighten all gas connections.

If connected to LP, have a qualified person make sure gas pressure does not exceed 14" (36 cm) water column.

Examples of a qualified person include:

licensed heating personnel,

authorized gas company personnel, and authorized service personnel.

Failure to do so can result in death, explosion, or fire.

Observe all governing codes and ordinances.

IMPORTANT: This installation must conform with all local codes and ordinances. In the absence of local codes, installation must conform with American National Standard, National Fuel Gas Code ANSI Z223.1/NFPA 54 - latest edition or CAN/CGA B149 - latest edition.

IMPORTANT: Range cooktop must be connected to a regulated gas supply.

IMPORTANT: Leak testing of the range cooktop must be conducted according to the manufacturer’s instructions.

Type of Gas

Natural Gas:

This range is design-certified by CSA International for use with Natural gas or, after proper conversion, for use with LP gas.

This range is factory set for use with Natural gas. The model/ serial rating plate located on the right vertical surface of the oven door frame has information on the types of gas that can be used. If the types of gas listed do not include the type of gas available, check with the local gas supplier.

LP Gas conversion:

Conversion must be done by a qualified service technician.

No attempt shall be made to convert the range cooktop from the gas specified on the model/serial rating plate for use with a different gas without consulting the serving gas supplier. To convert to LP gas, use the LP gas conversion kit provided with your range and see the “Gas Conversions” section. The parts for this kit are in the literature package supplied with the range.

Gas Supply Line

Provide a gas supply line of ¾" (1.9 cm) rigid pipe to the range location. A smaller size pipe on longer runs may result in insufficient gas supply. With LP gas, piping or tubing size can be ½" (1.3 cm) minimum. Usually, LP gas suppliers determine the size and materials used in the system.

NOTE: Pipe-joint compounds that resist the action of LP gas must be used. Do not use TEFLON®† tape.

Flexible metal appliance connector:

If local codes permit, a new CSA design-certified, 4 - 5 ft (122 - 152.4 cm) long, ⁵⁄₈" (1.6 cm) or

¾" (1.9 cm) I.D., flexible metal appliance connector may be used for connecting range to the gas supply line.

A ½" (1.3 cm) male pipe thread is needed for connection to the female pipe threads of the inlet to the range pressure regulator.

Do not kink or damage the flexible metal tubing when moving the range.

Rigid pipe connection:

The rigid pipe connection requires a combination of pipe fittings to obtain an in-line connection to the range. The rigid pipe must be level with the range connection. All strains must be removed from the supply and fuel lines so range will be level and in line.

Must include a manual shutoff valve:

The supply line must be equipped with a manual shutoff valve. This valve should be located in the same room but external to the range opening, such as an adjacent cabinet. It should be in a location that allows ease of opening and closing. Do not block access to shutoff valve. The valve is for turning on or shutting off gas to the range.

B

A

C

A. Gas supply line

B. Shutoff valve “open” position

C. To range

†®TEFLON is a registered trademark of E.I. Du Pont De Nemours and Company.

9

Image 9
Contents W10284348A Commercial Style Dual Fuel Convection RangeTable of Contents Your safety and the safety of others are very important Range SafetyTools and Parts Installation RequirementsProduct Dimensions 30 76.2 cm models Mobile Home Additional Installation RequirementsLocation Requirements High Altitude ConversionCabinet Dimensions 36 91.4 cm models48 121.9 cm models Water Filtration System Location Requirements Water Supply RequirementsElectrical Requirements U.S.A. Only If connecting to a 3-wire system If connecting to a 4-wire systemWire receptacle 14-50R Wire receptacle 10-50RGas Supply Requirements Type of GasGas Supply Line Gas Supply Pressure Testing Installation InstructionsUnpack Range Gas Pressure RegulatorInstall Anti-Tip Bracket Install Optional BackguardElectrical Connection U.S.A. Only 30 76.2 cm and 36 91.4 cm ModelsUL listed strain relief Wire connection Power supply cord Block screw Power supply cordGround-link screw Ground link bent away from range Install Water Filtration System on some models Make Gas Connection Pipe thread Adapter Flexible connectorComplete Connection Closed valve Open valveInstall Grill Grease Trays Verify Anti-Tip Bracket LocationLevel Range Install Griddle Install Burner Heads and CapsElectronic Ignition System To Adjust Flame Height Initial Lighting and Gas Flame AdjustmentsCheck Operation of Cooktop Burners If burners do not light properlyComplete Installation Reinstall KickplateIf you need Assistance or Service Check Operation of OvensGAS Conversions Gas Supply Pressure TestingLP Gas Conversion To Convert Gas Pressure RegulatorComplete Installation To Convert Grill Burner on some modelsBurner orifice spud Grill orifice hood Natural Gas Conversion Burner cap Burner headBurner head Gas opening Burner base Size stamp Strip Circuits Wiring Diagrams Cooktop SchematicsBurner Cooktop AC Drive Motor Relay Coil Relay Contact Left OvenBK 48 121.9 cm Oven Schematic for Kdrs ModelsL2 L1 Left Oven 48 121.9 cm Oven Schematic for Kdru ModelsVotre sécurité et celle des autres est très importante Sécurité DE LA CuisinièreOutillage et pièces Exigences D’INSTALLATIONPièces fournies Outils nécessairesExigences demplacement Pièces nécessairesConversion pour utilisation en haute altitude Dimensions du produit Modèles de 30 76,2 cm Modèles de 36 91,4 cmModèles de 48 121,9 cm Dimensions du placard Exigences demplacement du système de Filtration de leauConfiguration dinstallation typique ½ 3,8 cm J 7,6 cm K 12,7 cmSpécifications de l’alimentation en eau Spécifications de l’installation électriqueSpécifications de lalimentation en gaz Alimentation en eau par osmose inverseCanalisation de gaz Type de gazDétendeur Débit thermique des brûleurs AltitudeInstallation du dosseret facultatif Instructions D’INSTALLATIONInstallation de la bride antibasculement Déballage de la cuisinièreInstallation du modèle de filtre à eau W10049700 Installation du système de filtration de leauRaccordement à lentrée du filtre à eau jaune Raccordement à l’alimentation en eau du domicileSi lon doit dégager le tuyau Raccordement à la sortie du filtre à eau bleuRaccordement au gaz Vérification de lemplacement de la bride AntibasculementRéglage de laplomb de la cuisinière Achever le raccordementInstallation des plateaux à graisse du gril Installation des têtes et des chapeaux de brûleur Installation de la plaque à frireSystème dallumage électronique Allumage initial et réglages des flammes de gazHauteur de flamme Si les brûleurs ne sallument pas correctementRéglage de la taille des flammes Brûleur à double flammeAchever linstallation Réinstallation du garde-piedsSi vous avez besoin d’assistance ou de service Contrôle du fonctionnement du/des foursConversion pour lalimentation au propane Conversions Pour Changement DE GAZConversion du détendeur Chapeau de louverture daccès Position LP Joint détanchéitéConversion des brûleurs de surface Conversion du brûleur du gril sur certains modèlesGicleur de brûleur Injecteur femelle du gril Conversion pour lalimentation au gaz naturel Achever linstallationOuverture de la virole de réglage Vis Chapeau de louverture daccèsMarquage pour identification De la taille Chapeau de brûleurOuverture de gaz Base du brûleur Achever linstallation Schémas des circuits du four Schémas de la table de cuisson Schéma de câblageLégende Schéma du four 48 121,9 cm pour les modèles Kdrs Tableau de commande ClavierLégende Porte du four fermée Schéma du four 48 121,9 cm pour les modèles KdruAll rights reserved