Installation Instructions
DUCTWORK CALCULATIONS
Calculate Total Equivalent Ductwork Length
| Equivalent | Number | Equivalent | ||
Duct Pieces | Length* x | Used = | Length | ||
6″ round |
|
|
|
|
|
straight | 1 ft. | x | ( | )† = | ft. |
31⁄4″ x 10″ |
|
|
|
|
|
straight | 1 ft. | x | ( | )† = | ft. |
6″ , 90° |
|
|
|
|
|
elbow | 15 ft. | x | ( | ) = | ft. |
6″ , 45° |
|
|
|
|
|
elbow | 9 ft. | x | ( | ) = | ft. |
24″ max. |
|
|
|
|
|
flexible |
|
|
|
|
|
metal offset |
|
|
|
|
|
adapter | 34 ft. | x | ( | ) = | ft. |
31⁄4″ x 10″ |
|
|
|
|
|
90° elbow | 16 ft. | x | ( | ) = | ft. |
31⁄4″ x 10″ |
|
|
|
|
|
45° elbow | 5 ft. | x | ( | ) = | ft. |
31⁄4″ x 10″ |
|
|
|
|
|
90° flat elbow | 18 ft. | x | ( | ) = | ft. |
6″ round |
|
|
|
|
|
to 31⁄4″ x 10″ |
|
|
|
|
|
transition | 7 ft. | x | ( | ) = | ft. |
| Subtotal Column 1 = | ft. |
*Equivalent lengths of duct pieces are based on actual tests and reflect requirements for good venting performance with any downdraft cooktop.
†Measure and list feet of straight duct used. Count and list the quantity of all other duct pieces for the “Number Used” of each type.
IMPORTANT:
For maximum efficiency, use the shortest and straightest duct run possible, with as few fittings as possible.
For satisfactory performance, the duct run should not exceed 100 feet equivalent length.
Venting performance is improved by using larger diameter duct.
|
|
|
|
|
|
|
| Equivalent | Number | Equivalent |
|
| |||
|
| Duct Pieces |
| Length* x | Used = | Length |
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
| 6″ round |
|
|
|
|
|
|
|
| |
|
|
|
|
|
| to 31⁄4″ x 10″ |
|
|
|
|
|
|
|
| |
|
|
|
|
|
| transition |
|
|
|
|
|
|
|
| |
|
|
|
|
|
| 90° elbow | 20 ft. | x | ( | ) = |
| ft. |
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 31⁄4″ | x 10″ |
|
|
|
|
|
|
|
|
|
|
|
|
|
| to 6″ | round |
|
|
|
|
|
|
|
|
|
|
|
|
|
| transition | 5 ft. | x | ( | ) = |
| ft. |
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 31⁄4″ | x 10″ |
|
|
|
|
|
|
|
|
|
|
|
|
|
| to 6″ | round |
|
|
|
|
|
|
|
|
|
|
|
|
|
| transition |
|
|
|
|
|
|
|
| |
|
|
|
|
|
| 90° elbow | 12 ft. | x | ( | ) = |
| ft. |
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
| 6″ round |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
| wall cap |
|
|
|
|
|
|
|
| |
|
|
|
|
|
| with damper | 21 ft. | x | ( | ) = |
| ft. |
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 31⁄4″ | x 10″ |
|
|
|
|
|
|
|
|
|
|
|
|
|
| wall cap |
|
|
|
|
|
|
|
| |
|
|
|
|
|
| with damper | 27 ft. | x | ( | ) = |
| ft. |
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
| 6″ round |
|
|
|
|
|
|
|
| |
|
|
|
|
|
| roof cap | 20 ft. | x | ( | ) = |
| ft. |
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
| 6″ round |
|
|
|
|
|
|
|
| |
|
|
|
|
|
| roof vent | 24 ft. | x | ( | ) = |
| ft. |
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
| Subtotal Column 2 = | ft. |
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
| Subtotal Column 1 = | ft. |
|
| ||||
|
|
|
|
|
|
|
| TOTAL DUCTWORK = | ft. |
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
| Should not exceed 100 feet. |
|
|
|
DO NOT use flexible plastic ducting.
Vent installation should not exceed 100 feet equivalent length.