Start-Up Procedure
Apply power to the system
Safety warnings
This section provides instructions on how to perform a system
Electrical Hazard: Only APC Field Service Engineers or qualified,
Warning: Do not install any batteries into the XR Battery Enclosure or power modules into the Symmetra PX UPS until instructed to do so.
1.Set the upstream main utility input circuit breaker to ON.
2.Ensure
3.Set the Main Input switch on the PDU to ON.
4.Verify
5.Verify that the proper voltage is present on the secondary
winding of the transformer
(208 V, metered
gen0168a
InfraStruXure System - Installation and | 29 |