Start-Up Procedure: Apply power to the system
Verify proper voltage and phase rotation at the UPS
1. Close (turn ON) the Q1 circuit breaker on the PDU to apply power to the UPS.
2.Ensure
3.Verify proper voltage is present at the UPS input terminal block (208V, metered
Start the UPS
1.Set the UPS DC Disconnect circuit breaker to ON, and then set the UPS System Enable switch to ON.
2.If applicable, set the XR Battery Enclosure DC Disconnect circuit breaker to ON.
When the System Enable switch is in the ON position, the Startup screen appears on the display interface of the Symmetra
PX UPS.
Then, the
px0013a
PowerView RM
Rev: 000 English
Please wait...
Fuel %
Load %
In 208V out000V 60Hz Runtime: 1hr 2m
34 | InfraStruXure System - Installation and |